QUADRIFOGLIO B
89
EN
cod. 3541D501 - Rev. 03 - 12/2013
A direct heating circuit and a DHW circuit with diverter valve (3-wire)
- Schematic diagram
Use diverter valves with 3 wires:
- OPENING PHASE 230V
- CLOSING PHASE 230V
- NEUTRAL
with switching times (from all closed to all open) of not more than 90 seconds.
fig. 42
- Electrical connections
After installation, carry out the necessary electrical connections as shown on the wiring
diagram.
Then configure the controller as described in the specific section.
fig. 43
Legend
- Parameters
Each system requires a different parameterisation. Follow the access procedure given
below.
“Service Menu”
Check/change parameter
b02
of the “Transparent Parameters Menu” to
9
(for models B
70, B 125 and B 320) and to
6
(for model B 220).
- Optional functions
As well as the electrical connections of the previous figure (required for this system con-
figuration) there are options that do not require settings.
fig. 44
Legend
32
Heating circulating pump
a
1st zone (direct)
72
Room thermostat 1st zone (direct)
b
Hot water tank circuit
138
External probe
M
Delivery
155
Hot water tank probe
RA
High Temperature Return
306
Circulating pump 1st zone (direct)
RB
Low Temperature Return
348
3-way valve (3-wire)
A =
OPENING PHASE
B =
NEUTRAL
C =
CLOSING PHASE
I*
ISPESL safety devices (When required - not supplied)
To manage sliding temperature it is necessary to purchase the external probe accessory code 013018X0
If a hot water tank probe (not supplied) is used, it is necessary to purchase the NTC probe accessory code
1KWMA11W (2 mt.) or code 043005X0 (5 mt.)
If a hot water tank thermostat (not supplied) is used, it is necessary to purchase the kit accessory code
013017X0 (to be connected in place of the Hot Water Tank Probe)
155
348
32
M
RA
RB
M
I*
b
a
72
138
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44
FUSE
3.15A
155
L
N
32
L
N
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18
348
C
B
A
72
138
139
Remote Control: it can be installed in place of 72 to manage the request of the 1st zone (direct)
300
Burner On indication (voltage-free output): the example shows the connection of an hour counter at 230Vac
301
Fault indication (voltage-free contact output): the example shows the connection of a lamp at 230Vac
302
Remote reset input (230Vac): the example shows the connection of a double-pole switch at 230Vac, allowing
the resetting of a block type fault
357
Fault indication (230Vac): the example shows the connection of a lamp at 230Vac
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44
FUSE
3.15A
L
N
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18
300
357
139
301
302
N
L
T