OMNIA S HYBRID H 3.2
Level 1
Level 2
Level 3
Level 4
Description
Lower
limit
Upper
limit
Remedy
Unit
of meas-
urement
Default
value
Counters
Burner
Burner operating hours
0
99999
1
hr
-
Ignition ok
Number of ignitions
Ignition error
Number of failed ignitions
CH pump time
CH pump operating hours
DHW pump time
DHW pump operating hours
Alarm
Alarm1 XX
Alarm2 YY
...... - -
Alarm10 - -
Clear
9.2.2 Boiler service menu
ACCESS TO THE SERVICE MENU AND CHANGING PARAMETERS CAN ONLY BE CARRIED OUT BY QUALIFIED
PERSONNEL.
To continue, you must enter the password “1234”. Set the cell value with the SW6 and SW7 buttons while you can change positions with the SW1 and SW2 buttons.
Confirm with the button.
Menu for modifying the [TSP] parameters
You can scroll the list by pressing the SW1 and SW2 buttons while the value is displayed with the button. To modify, press the SW6 and SW7 buttons, confirm
with the button or cancel with the button.
Index Description
Modulation
Default
b01 Boiler type selection
2 = BOILER (DO NOT MODIFY)
2
b02 Boiler type
1 = 24_H
2 = 28_H
3 = 34_H
4 = 45_H
5 = 24_H (high range)
6 = 28_H (high range)
7 = 34_H (high range)
6
b03 Gas type
0 = Methane
1 = LPG
2 = Propane-air
0
b04 Water system pressure
protection selection (DO NOT MODIFY)
0 = Pressure switch
1 = Pressure transducer
1
b05 Summer/Winter function
0 = WINTER - SUMMER - OFF
1 = WINTER - OFF
0 = Enabled
b06 Variable input contact function selection
(NOT USED)
0 = Flowmeter exclusion
1 = System thermostat
2 = Second Room thermostat
3 = Warning/Notification
4 = Thermostat safety device
2
b07 LC32 relay board operation selection
0 = External gas valve
0
1 = Alarm
2 = System loading solenoid valve
3 = Solar 3-way valve
4 = Second heating pump
5 = Alarm2
6 = Burner on
7 = Antifreeze active
b08 Hours without DHW
withdrawal
0-24 hours (time for temporary deactivation of comfort without withdrawal)
24
b09 Fault 20 status selection
0 = Disabled
1 = Enabled (Only for versions with pressure transducer)
0
b10 Not implemented
--
--
b11
Boiler preparation
0 = Fixed primary (P44)
1 = Linked to DHW Set Point (P51)
0
b12 Boiler priority
0 ÷ 255 min
30
b13 Heating priority
0 ÷ 255 min
15
b14 DHW factor (NOT USED)
0 - 1
0
b15 Not implemented
--
3
b16 Not implemented
--
--
b17 Not implemented
--
--