![Ferroli MAXIMA 35 C Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/ferroli/maxima-35-c/maxima-35-c_instructions-for-use-installation-and-maintenance_2282023018.webp)
18
Maxima 35 C
* = between
10 and 60 mm
* = between
10 and 60 mm
240
240
Install level
50*
115
95
80
30
50*
30
95
80
80
S
50*
P
115
L
D
S
P
125
S
30
95
D
S
50*
L
30
95
240
240
180
240
240
180
Drill the wall 10
÷
20 mm
more than the pipe diameter
Install level
Install level
Install level
Drill the wall 10
÷
20 mm
more than the pipe diameter
Standard 1KWMA53A
Flue kit
Connection with concentric fl ue system
The unit can be connected to a concentric air/flue duct with a wall or rooftop outlet as shown on the
following drawings. Numerous accessories are available on request to meet the various installation
requirements. Please refer to our “flue manual” or the price list.
Standard concentric fl ue installation
Side view
View from above
fig. 9a
Side Outlet
fig. 9b
Front view
View from above
P = S + 165 mm
Rear Outlet
L = S + D + 175 mm
Horizontal fl ue installation
1. Define the position for installing the unit.
2. If using standard flue (1KWMA53A) this must be installed level, for non-standard flue lenghts
over im a fall of 3 mm per metre should be incorporated.
3. Make a hole of diameter 10 - 20 mm greater than the nominal diameter of the concentric
pipe used.