DOMIcompact F 24 D
Tegola inclinata
1KWMA82U
Adattatore
concentrico 60/100
1KWMA33K
Prolunga 60/100
1KWMA56U
194
266
950
50
Terminale tetto
1KWMA83U
68
950
50
50
950
50
1000
125
10
Vertical Outlet
For the installation:
1. Define the position for installing the unit
2. Drill the wall for the air/fume pipe outlet accor-
ding to the references stated in the figures,
considering that the horizontal sections of
piping must have a gradient of approxima-
tely 3 mm per metre of length downwards
to prevent any rainwater getting into the
boiler.
3. Make a hole of diameter 10 - 20 mm greater
than the nominal diameter of the coaxial pipe
used to facilitate insertion.
4. If necessary, cut the end pipe to size, consi-
dering that the external pipe must protrude
from the wall by between 10 and 60 mm (Fig.
9a and 9b). Eliminate the cutting burrs.
5. Connect the ducts to the boiler, positioning
the gaskets correctly and seal the wall cou-
pling points with special sleeves.
Fig. 9c
The total length in linear metres of the coaxial
duct must not exceed the maximum lengths
stated in the following table, considering that
each bend gives rise to the stated reduction.
For example, a duct D= 60/100 composed of 1
bend of 90° +1 horizontal metre + 2 bends of
45° + 1 horizontal metre has a total equivalent
length of 4 metres.
Ø mm
60/100
Ø mm
80/125
Maximum permissible
flue length
5 m
5 m
Reduction factors for bends
Concentric bend at 90° - Ø 60/100 mm
1 m
Concentric bend at 45° - Ø 60/100 mm
0,5 m
Concentric bend at 90° - Ø 80/125 mm
0,5 m
Concentric bend at 45° - Ø 80/125 mm
0,25 m
Roof end piece
1KWMA83U
Angled roof tile
1KWMA82U
Extension 60/100
1KWMA56U
Concentric
adapter 60/100
010006X0