BLUEHELIX TECH RRT 24 C
29
EN
cod. 3541P250 - Rev. 01 - 07/2018
"Sc" - Combustion Control Parameters Menu
ONLY FERROLI TRAINER & QUALIFIED PERSONNEL CAN ACCESS THE "SC" MENU TO MODIFY THE RELE-
VANT PARAMETERS.
Press the Heating buttons to scroll the list of parameters “+“ increasing “-“ decreasing order. Press the DHW buttons to
view or modify the value of a parameter. To save the edited parameter press either the
h”
or
“-”
button (details
3 and 4 - fig. 1).
PARAMETERS "SC12" AND "SC13" MUST ONLY BE MODIFIED, IF STRICTLY NECESSARY, BY QUALIFIED
PERSONNEL AND ONLY WHEN THE CO
2
VALUES ARE OUTSIDE THE RANGE INDICATED IN “- Technical data
table” on page 47. CARRY OUT THE PROCEDURE AFTER AT LEAST 500 HOURS OF BOILER OPERATION.
* SC12
regulates the CO
2
at the same time at maximum and minimum power. By increasing the parameter value the
CO
2
reduces; by decreasing the parameter value the CO
2
increases.
** SC13
regulates the CO
2
at minimum power. By increasing the parameter value the CO
2
reduces; by decreasing the
parameter value the CO
2
increases.
Contents Description
Functional description
Range
Default
Sc01
Gas type selection
Allows the change of gas type. See “Gas conversion” on
page 21
na / LP
na
Sc02
Ignition gas calibration
Allows the amount of gas to be increased or decreased in the
ignition phase (Due to poor ignition).
-9 ÷ 20
0
Sc03
Ignition power
Allows the fan speed to be increased or decreased in the igni-
tion phase in case of poor ignition.
-16 ÷ 14
0
Sc04
N/A For the UK market.
-2 ÷ 13
0
Sc05
Minimum output calibration
Allows the minimum output to be increased, if necessary.
0 ÷ 25
0
Sc06
Minimum gas valve calibration
Self-adaptive parameter.
DO NOT MODIFY
.
Sc07
Flame ionisation signal
Displays the actual ionisation current signal.
Read only
Sc08
Current power in DHW mode
Displays the actual output related to maximum power in DHW
mode.
Read only
Sc09
MAX ionisation value
Displays the maximum ionisation value reached.
Read only
Sc10
Minimum ionisation value during ignition
Displays the minimum ionsation value reached during the
ignition phase.
Read only
Sc11
Ignition time
Displays the time from fan activation to ionisation.
Read only
Sc12
*
Ionisation reduction value (BASE)
Allows the adjustment of CO
2
at the same time as maximum
and minimum power, translating the entire value curve.
-5 ÷ 10
0
Sc13
**
Ionisation reduction value (min.)
Allows the adjustment of CO
2
at minimum power.
-5 ÷ 10
0
Sc14
Internal error K1
Displays the SCOT system error code.
Read only
Sc15
100% CALIBRATION
Allows 100% Calibration (see “100% calibration” on page 23)
when replacing some components (see “Replacement of
major components & testing” on page 34)
0 - CAL
0
Sc16
DO NOT MODIFY
.