MODENA S HE
16
EN
cod. 3541C364 - Rev. 00 - 12/2012
Connection with separate pipes
fig. 20 - Examples of connection with separate pipes (
= Air /
= Fumes)
For the connection of separate ducts, fit the unit with the following starting accessory:
fig. 21 - Starting accessory for separate ducts
Before proceeding with installation make sure the maximum permissible length has not been exceeded, by means of a
simple calculation:
1. Completely establish the layout of the system of split flues, including accessories and outlet terminals.
2. Consult the table 3 and identify the losses in m
eq
(equivalent metres) of every component, according to the instal-
lation position.
3. Check that the sum total of losses is less than or equal to the maximum permissible length in table 2.
Table. 2 - Max. length separate ducts
Table. 3 - Accessories
Separate ducts
MODENA 18 S HE
MODENA 25 S HE
MODENA 32 S HE
Max. permissible length
70m
eq
70m
eq
70m
eq
Losses in m
eq
Air
inlet
Fume exhaust
Vertical
Horizontal
Ø 80
PIPE
1 m M/F
1.0
1.6
2.0
BEND
45° M/F
1.2
1.8
90° M/F
1.5
2.0
PIPE SECTION
with test point
0.3
0.3
TERMINAL
air, wall
2.0
-
fumes, wall with antiwind
-
5.0
FLUE
Split air/fumes 80/80
-
12.0
Ø 81
Ø 81
Ø
65
Ø
87
Ø
65
041039X0