![fergo Switchmaster M2 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/fergo/switchmaster-m2/switchmaster-m2_documentation_553200006.webp)
D
esig
n and ma
ter
ials can be changed without notic
e. Er
rors and omissions e
xc
ept
ed
DOCUMENTATION -
SWITCHMASTER
- 6 -
F. Closing of the transparent cap
Adjust the red arrow shown on the transparent cap to the marking on the casing:
1. press down the cap…
2. …and turn until the red arrow is showing on the marking
l
General Data
Mounting measurements
According to VDI/VDE 3845 for flange facing 30 x 80 and 30 x 130 (see dimensioned
drawing)
Materials
- Cap
Lexan 143 R (PC)
- Stem
Delrin (POM)
- Seals
Perbunan (NBR)
- Cable gland/nut
Polyamid (PA)
- Other parts of plastic
Bayblend T45, (ABS + PC)
- Hexagon socket screw
Stainless steel AISI 304
Protection
IP67, VDE 0470/EN 60529
Temperature range
-20 °C to +70 °C
Indication and switching range
0°...90° pivoting angle
Cable gland
With strain relief,
Clamp range 7-13 mm
Cable
Ø 7-13 mm, max. 2,5 mm²
Weight
ca. 0,325 kg
SWITCHMASTER Versions
Typ M, Microswitches
Typ SM - M2 (Signal „Open + Close“)
Voltage range
4 V/DC - 250 V/DC
Current range
1mA - 5A
Switches functions
Change over contact, contacts old plated
Typ D, inductive sensor, direct switching,
three-wire system, with LED
Typ SM - D2 (Signal „Open + Close“)
Typ SM - DA (Signal „Open“)
Typ SM - DZ (Signal „Close“)
Voltage range
10 - 30 V/DC
Current range
100 mA
Switches functions
puls schaltend, PNP Schließer, in Endlage bedämpft oder unbedämpft
Typ N, inductive sensor, Namur EN 60947-
5-6, with LED, explosion-proofed
Typ SM - N2 (Signal „Open + Close“)
Typ SM - NA (Signal „Open“)
Typ SM - NZ (Signal „Close“)
Voltage supply
rated voltage 8 V/DC, max. 16 V/DC
Output current
damped </= 1 mA; undamped >/= 3 mA
Switching function
damped or undemped in end-position
Switching power
max. 34 mW
ATEX- Version (different from „general data“)
Material
ATEX- Series
Cover
Lexan 143R CPC antistatic coated
Casting, feet
Bayblend T45 (ABS + PC) antistatic coated
ATEX- Name
EX II 2 G EEx ia IIB T6
-20°C C < Ta < +70°C
geschlossen
16
closed open
Blindeisenweg 31
D-41468 Neuss
Tel.: +49(0) 2131 - 15 39 28-0
Fax: +49(0) 2131 - 15 39 28-99
Web: www.fergo.biz
E-Mail: [email protected]
copyright © by
FERGO® Armaturen GmbH