background image

 

 

730110

 

K0 

   

11 

ES1613 

Page 

5.2.

 

Periodic Inspection 

The items that must be inspected one or two times every 6 months to 1 year are listed below. 

When  the  equipment  is  moved  or  modified,  or  layout  of  the  wiring  is  changed,  also  perform  this 

inspection. 

Do not needs to check smoke detect function with real smoke such as Tobacco, incense, etc. Because 

this smoke detector has self check functions. 

№ 

Item 

Object 

Content 

Method 

Judgment 

Criteria 

Treatment 

Operating Temperature 

Common  Used  within  the 

specification? 

Measure 
with 

thermometer. 

-10

℃~

60

 

Meets 

the 

specification. 

Operating Humidity 

Common  Used  within  the 

specification? 

Measure 
with 

hygrometer. 

30

85

RH Non 

condensing 

Meets 

the 

specification. 

Atmosphere 

Common  IS  there  volatile 

or 

corrosive 

gas? 

Measure 
corrosive 
gas. 

No  tolerance  to 
acid and alkaline. 

Meets 

the 

specification. 

Power Supply Voltage 

Common  Used  within  the 

Power 

Supply 

Voltage 
specification? 

Measure 

Power 
Supply 
voltage. 

DC10.0V

DC30.0V 

Meets 

the 

specification. 

Ripple Voltage 

Common  Used  within  the 

Ripple  Voltage 

 

specification? 

Measure 

ripple 
voltage. 

300mVp-p 

Meets 

the 

specification. 

Installation 

Common  Securely 

locked? 

Move 

the 

detector 

to 

check.   
 

The detector must 
be 

installed 

securely. 

Retighten 

the 

screws 

on 

the 

base  with  proper 
torque. 
 

 

 

 

Obstacle 

near 

the 

inlet/outlet 

of detector? 

Check 
Visually 

Obstacle  must not 
be present. 

Removed. 

Appearance 

Common  Adhesion  of  dirt 

and 

foreign 

matter? 

Check 
Visually 

Dirt  and  foreign 
matter  must  not 
be present. 

Removed 

and 

Clean. 

 

 

 

Damages? 

Check 
Visually 

Damages 

must 

not be present. 

Change 

the 

detector. 

Wiring 

Common  Damages 

or 

Breakages? 

Check 
Visually 

Damages 

must 

not be present. 

Change 

the 

connector cable. 

 

 

 

Adhesion  of  dirt 
and 

foreign 

matter  on  the 
connector? 

Check 
Visually 

Dirt  and  foreign 
matter  must  not 
be present. 

Removed 

and 

Clean. 

 

 

 

Looseness of 
connectors 

Move 

the 

wire 

to 

check.   
 

Connectors  must 
not be loose 

Change 

the 

connector cable. 

Behavior  Normal 

supervision 

Detector 

State  Indication 
LED 

Check 
Visually 

Blink  10  seconds 
interval. 

Check  the  State 
Indication 

LED 

behavior. 

 

 

 

 

 

 

 

 

 

 

 

 

Please do not touch the terminal while the unit is energized. It may get an electric 

shock. 

Please  do  the  cleaning  and  the  increase  tightening  of  the  screw  after  the  power 

supply off. If not the power supply off, it may get an electric shock. 

Do not soak a detector in water, and do not put a detector into water. 

 

Warning

 

 

Содержание F1H-Q-RYW1K

Страница 1: ...nual we have shown the important notice in order for you to use the device just and the method of handling this system In additional to you read this manual well before the utilization understanding well and use After you read in the place where it seen with it is seen with anytime please to be sure to keep ...

Страница 2: ...ge Table of contents 1 Safety Instructions 3 2 Name and Function of each section 4 3 Install 5 4 Specification 8 5 Maintenance and Inspection 10 6 Parts of Replacement 13 7 Term of replacement 13 8 Disposal 13 9 Support 14 ...

Страница 3: ... moving and falling etc at your corporation breakdown and the loss with inadequate handling 3 When cause of breakdown due to the reason other than the payment item 4 Error in regard to use of the consumer breakdown and the loss with repairing remodeling other than our company and error connecting Furthermore the guarantee referred to here being something which means the guarantee of the payment it...

Страница 4: ...730110 K0 4 ES1613 Page 2 Name and Function of each section ...

Страница 5: ...ronmental specification It causes trouble Do not install wrong location The smoke detector cannot detect a smoke Be sure to install the detector away from sources of electrical noise such as high voltage and high current switches Isolation from electric noise source such as power line The signal conductor which is connected to the detector please wires over 20cm separating from the power line Case...

Страница 6: ...lfunction failure or drop Tighten the screw in the specified torque range torque 0 5N m Reference value Under tightening can cause a drop short circuit or malfunction Over tightening can cause a drop short circuit or malfunction due to damage to the screw or he equipments and malfunction and fire Put Insert guides Detector Terminal and Attachment together correctly It causes trouble Do not turning...

Страница 7: ... between Relay and Relay Relay and Power supply Do not place obstacle as wiring etc near the slit of the detector It will disturb inflow of smoke Please provide a dedicated power supply as much as possible This Detector does not have over voltage protection device Before using Please add an external over current circuit breaker Smoke detectors are detecting light scattered by smoke particles in th...

Страница 8: ...ow 6 3 Sensitivity Depend on Type of Product 0 5 m Nominal 4 State Indication LED RED LED State of LED Normal mode 10 seconds interval Alarm mode 1 seconds interval Trouble mode Off not blinking Alarm will override trouble 5 Output Alarm Trouble Relay Output Capacity of Relay DC24V 0 5A Resistance loading State depends on Type of relay Type Contact Normal mode Alarm mode Trouble mode Power OFF AA ...

Страница 9: ...etector becomes trouble condition before exceeding correctable limit 4 2 Mechanical Specification 1 quantity of suction 1L min 2 Filter Medium efficiency particulate airlifter Over 70 rate of collection 3 External Φ28 H57mm Installation Base 10mm is contained 4 Mass Approx 25g Installation Base is contained 5 Main Material ABS resins 4 3 Environmental Specification 1 Operating Temperature Range 10...

Страница 10: ...ors Move the wire to check Connectors must not be loose Change the connector cable 4 Behavior Normal supervision Detector State Indication LED Check Visually Blink 10 seconds interval Check the State Indication LED behavior Please do not touch the terminal while the unit is energized It may get an electric shock Please do the cleaning and the increase tightening of the screw after the power supply...

Страница 11: ...p p Meets the specification 6 Installation Common Securely locked Move the detector to check The detector must be installed securely Retighten the screws on the base with proper torque Obstacle near the inlet outlet of detector Check Visually Obstacle must not be present Removed 7 Appearance Common Adhesion of dirt and foreign matter Check Visually Dirt and foreign matter must not be present Remov...

Страница 12: ...unction Please use the dry cloth or wring the water out tightly cloth for the cleaning After Cleaning Do not leave a foreign substance such as sawdust or wiring debris on a detector Such debris could cause erroneous operation Do not clean with a solvent such as a ph balanced detergent Bleach Benzene Thinner Alcohol It causes the detector surface is damaged Caution ...

Страница 13: ...pull it out until it clicks 7 Term of replacement Since deterioration over time of the suction fan may vary with temperature Life of this product depends on the operating temperature of the product 10 45 Recommended Temperature Range 5 years 46 60 3 years 8 Disposal This product is as general industrial waste disposal Disposal methods are specific criteria depending on each municipality Do not wir...

Страница 14: ...613 Page 9 Support Please inquire about this product to Fenwal Controls of Japan Co Ltd Tokyo headquarters Fenwal Controls of Japan Co Ltd 1 5 10 Iidabashi Chiyoda Tokyo 102 0072 Japan Tokyo headquarters 81 3 3237 3565 ...

Отзывы: