730110
K0
11
ES1613
Page
5.2.
Periodic Inspection
The items that must be inspected one or two times every 6 months to 1 year are listed below.
When the equipment is moved or modified, or layout of the wiring is changed, also perform this
inspection.
Do not needs to check smoke detect function with real smoke such as Tobacco, incense, etc. Because
this smoke detector has self check functions.
№
Item
Object
Content
Method
Judgment
Criteria
Treatment
1
Operating Temperature
Common Used within the
specification?
Measure
with
a
thermometer.
-10
℃~
60
℃
Meets
the
specification.
2
Operating Humidity
Common Used within the
specification?
Measure
with
a
hygrometer.
30
~
85
%
RH Non
condensing
Meets
the
specification.
3
Atmosphere
Common IS there volatile
or
corrosive
gas?
Measure
corrosive
gas.
No tolerance to
acid and alkaline.
Meets
the
specification.
4
Power Supply Voltage
Common Used within the
Power
Supply
Voltage
specification?
Measure
a
Power
Supply
voltage.
DC10.0V
~
DC30.0V
Meets
the
specification.
5
Ripple Voltage
Common Used within the
Ripple Voltage
specification?
Measure
a
ripple
voltage.
300mVp-p
Meets
the
specification.
6
Installation
Common Securely
locked?
Move
the
detector
to
check.
The detector must
be
installed
securely.
Retighten
the
screws
on
the
base with proper
torque.
Obstacle
near
the
inlet/outlet
of detector?
Check
Visually
Obstacle must not
be present.
Removed.
7
Appearance
Common Adhesion of dirt
and
foreign
matter?
Check
Visually
Dirt and foreign
matter must not
be present.
Removed
and
Clean.
Damages?
Check
Visually
Damages
must
not be present.
Change
the
detector.
8
Wiring
Common Damages
or
Breakages?
Check
Visually
Damages
must
not be present.
Change
the
connector cable.
Adhesion of dirt
and
foreign
matter on the
connector?
Check
Visually
Dirt and foreign
matter must not
be present.
Removed
and
Clean.
Looseness of
connectors
Move
the
wire
to
check.
Connectors must
not be loose
Change
the
connector cable.
9
Behavior Normal
supervision
Detector
State Indication
LED
Check
Visually
Blink 10 seconds
interval.
Check the State
Indication
LED
behavior.
・
Please do not touch the terminal while the unit is energized. It may get an electric
shock.
・
Please do the cleaning and the increase tightening of the screw after the power
supply off. If not the power supply off, it may get an electric shock.
・
Do not soak a detector in water, and do not put a detector into water.
!
Warning