background image

MOUNTING AND WIRING

CAUTIONS:

1. Ceramic insulators should nor be in or close to the flame.
2. Electrode assemblies should not be adjusted or disassem bled. 

Electrodes should have a gap spacing of 0.125± 0.031 in 
(3.12± 0.81 mm). If this spacing is not correct, the assembly must 
be replaced. Electrodes are NOT field adjustable.

3. Exceeding the temperature limits can cause nuisance lockouts and 

premature electrode failure.

4. Electrodes must be placed where they could not be exposed to the 

appliance user in normal operation.

SEQUENCE OF OPERATION / FLAME

RECOVERY / SAFETY LOCKOUT

Power Up/Stand-By

•  Upon applying power (24 VAC) to 24V terminal, the control will 

reset, perform a self check routine, initiate full time flame sensing, 

flash the diagnostic LED for up to four seconds, and enter the 

thermostat scan state.

Heat Mode

•  When a call for heat is received from the thermostat supplying 24 

volts to TH/W, a pre-purge delay begins, then the gas valve is 

energized and the sparks commence at both burners for the trial 

for ignition period.

• When flame is detected during the trial for ignition, sparks are 

shutoff immediately and the gas valve remains energized. The 

thermostat and burner flame are constantly monitored to assure 

the system continues to operate properly. When the thermostat 

is satisfied and the demand for heat ends, the main valve is

de-energized immediately.

Failure to Light - Lockout

SINGLE TRIAL MODEL

Should either burner fail to light, or flame is not detected during the

trial for ignition period, the control will go into lockout and the valve

will be turned of immediately.

MULTI TRIAL MODEL

Should either burner fail to light, or flame is not detected during 

the first trial for ignition period, the gas valve is de-energized 

and the control goes through an interpurge delay before another 

ignition attempt. The control will attempt two additional ignition 

trials before going into lockout and the valve relay will be de-

energized  immediately.

Recovery from lockout requires a manual reset by either resetting 

the thermostat or removing 24 volts for a period of 5 seconds.

FLAME FAILURE- RE-IGNITION

If the established flame signal is lost from either burner while the 

burners are operating, the control will respond within 0.8 seconds. 

The HV spark will be energized for a trial for ignition period in an 

attempt to relight the burners. If either burner does not light the 

control will de-energize the gas valve. Multi-try models will make 

two more attempts to relight the burners. If either burner does not 

relight  the control will go into lockout as noted above in “Failure 

to light”. If flame is re-established, normal operation resumes.

Flame Fault

If at any time the main valve fails to close completely and main

tains a flame, the full time flame sense circuit will detect it and 

flash an error code of 2.

CAUTION: 

Label all wires prior to disconnection when servicing controls. 
Wiring errors can cause improper and dangerous operation.  
A functional checkout of a replacement control is recommended.

WARNING: 

Operation outside specifications could result in failure of the
Fenwal product and other equipment with injury to people 
and product.

TERMINAL DESIGNATIONS

TH/W

THERMOSTAT INPUT

GND

SYSTEM GROUND

V1

VALVE POWER

V2

VALVE GROUND

NC

ALARM

S1

REMOTE FLAME SENSOR

S2

REMOTE FLAME SENSOR

FC1

FLAME CURRENT TEST PIN

FC2

FLAME CURRENT TEST PIN

24V

24 VAC INPUT (FULL TIME)

WARNING:

The Series 35-62 uses voltages of shock hazard potential. Wiring 
and initial operation must be done by a qualified service technician.

The Series 35-62 is not position sensitive and can be mounted 

vertically or horizontally. The control may be mounted on any 

surface with #6 sheet metal screws.

All wiring must be done in accordance with both local and 

national electrical code. The control must be secured in a area

that will experience a minimum of vibration and remain below the

maximum operating temperature of 160°F.

All connections should be made with UL approved 105°C rated 

18 gauge, stranded,.054 thick insulated wire. Refer to wiring 

diagram when connecting the Series 35-62 to other components 

in the system.

PROPER ELECTRODE LOCATION

Proper location of the electrode assembly is important for 
optimum system performance. It is recommended that electrode
assembly be mounted temporarily using clamps or other suitable
means so that the system can be checked before permanently
mounting the assembly. The electrode assembly should be 
located so that the tips are inside the flame envelope and about
1/2 inch (1 cm) above the base of the flame. See Figure 3.

Page 2

Series 35-62, 24 VAC Dual Point DSI Control

www.fenwalcontrols.com 

1-800-FENWAL-1

Содержание 35-62 Series

Страница 1: ...e relay energized control only Gas Valve Rating 1 5A 24 VAC Inrush 3 0A maximum Operating Temperature 40 F to 160 F 40 C to 71 C Flame Sensitivity 1 0uA minimum Flame Failure 0 8 seconds Response Time Types of Gases Natural LP or manufactured Spark Rate Line frequency 50 60 sparks sec Enclosure Gray Noryl N 190 fire retardant plastic integral standoffs optional Moisture Resistance Conformal coated...

Страница 2: ...respond within 0 8 seconds The HV spark will be energized for a trial for ignition period in an attempt to relight the burners If either burner does not light the control will de energize the gas valve Multi try models will make two more attempts to relight the burners If either burner does not relight the control will go into lockout as noted above in Failure to light If flame is re established n...

Страница 3: ...kay during TFI A Bad electrode no flame sense after TFI B Bad S1 or HV wire C Poor ground at burner D Poor flame check flame current 6 Flame with no call for heat A Stuck valve check LED for 2 flashes FLAME CURRENT CHECK Flame current is the current which passes through the flame from the sensor to ground The minimum flame current necessary to keep the system from lockout is 7 microamps To measure...

Страница 4: ...rovide for every possible contingency to be met in connection with installation operation and maintenance All specifications subject to change without notice Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to KIDDE FENWAL Inc Ashland Massachusetts P N 35 62 03 10 30 03 Page 4 Ser...

Отзывы: