background image

Effective: January 2020

F-35-53-CE

5

CONTROL WIRE HARNESS

Select the proper harness based on the 35-53CE control's ter

-

mination connection. Standard wire lengths are 12, 18, 24 30, 

36 and 48 inches. Refer to Fenwal Controls datasheet F-05-

1000 for details.

High Voltage and Remote Sense Cable 

Requirements

The HV Ignition Cable must meet a voltage rating of 25 KV and 

an insulation rating of 200 °C. Suppression type UL 3257 or SAE

J2031 ratings are recommended. Recommend length of 3ft 

(.9m) or less. Consult factory for longer lengths.

Remote flame sense cable must meet a voltage rating of 250V 

and an insulation rating of 200 °C. Recommended length of 10ft 

(3m) or less. Consult Factory for longer lengths.

Refer to Fenwal Controls datasheet F-05-1000 for details.

SPARK ELECTRODES/FLAME SENSORS

Critical for gas-fired appliances, proper design, construction, 

and application assures reliable ignition and optimal perfor

-

mance. Fenwal Controls uses only glazed Alumina ceramics and 

certified rod materials suitable up to 2175°F (1190°C). Spark 

electrodes typically have a 0.125” gap between the high voltage 

(HV) rod tip and the ground rod or burner. Flame sensors are a 

single rod used in flame rectification circuit of the ignition con

-

trol to confirm the presence (or absence) of the flame. 

Refer to Fenwal Controls datasheet F-22-100 for details.

Proper Electrode Location

Proper location of electrode assembly is important for optimum 

system performance. The electrode assembly should be located 

so that the tips are inside the flame envelope and about 1/2-inch 

(1.2 cm) above the base of the flame as shown:

Notes:

Ceramic insulators must not be in or close to the flame.

Electrode assemblies must not be adjusted or 

disassembled. Electrodes are NOT field adjustable.

Electrodes should have a gap spacing of 0.125 in (3.12 

mm), unless otherwise specified by the appliance 

manufacturer. Larger gaps may not perform as 

intended in all conditions. If spacing is not correct, the 

assembly must be replaced.

Exceeding temperature limits can cause nuisance 

lockouts and premature electrode failure.

Electrodes must be located where they are not exposed 

during normal operation.

Flame Current Measurement

Flame current is the current which passes through the flame 

from the sensor to ground to complete the primary safety cir

-

cuit. The minimum flame current necessary to keep the system 

from lockout is 0.7µA. To measure flame current:

1.

Disconnect Input Voltage.

2.

Insert a 0-50µA DC meter and capacitor in series with the 

sensor electrode and wire as shown below.

The meter should read 0.7µA or higher while flame is estab

-

lished. If the meter reads below “0” on the scale, the meter 

leads are reversed. Disconnect power and reconnect meter 

leads for proper polarity.

CAUTION

When monitoring flame current, use a 1.0µF, 

250 VDC bypass capacitor to protect the meter 

from damage.

Control

Unit

µA Meter

Spark
Output

1µF

Содержание 35-53CE Series

Страница 1: ...s the blower function if not required allowing one part to address all service or OEM needs Agency Certifications EN298 CE 584099 Classification BMRVXN Mobile Applications DC supply type A B C Code Compliant to AS 4625 2008 AS 4622 2004 CAN CSA E60730 1 ANSI Z21 20 CAN CSA C22 2 No 60730 2 5 Compliant with current RoHS standards SPECIFICATIONS Input Power Control 9 2 to 15 VDC from a stor age batt...

Страница 2: ...stic LED will indicate the fault code for igni tion lockout 3 Flashes Flame Failure FLAME FAILURE RECYCLE MODE Standard With the Recycle after Loss of Flame option upon loss of flame the gas valve is de energized and the control proceeds to inter purge before attempting to relight the flame Multi try models permit three tries for ignition including inter purges If the burner relights normal operat...

Страница 3: ...t has been exposed to water must be replaced WARNING All wiring must be done in accordance with both local and national electrical code and by a trained service technician Wiring must be at least 18 AWG rated for 105 C or higher WARNING The 35 53CE uses voltages of shock hazard potential Wiring and initial operation must be done by qualified service technician WARNING Operation outside specificati...

Страница 4: ...wer Relay Figure 2 Local Sense without Blower Relay Figure 3 Remote Sense with Blower Relay Figure 4 Remote Sense without Blower Relay DIMENSIONS INTEGRAL STANDOFF 4 250 3 750 250 3 250 2 750 250 6 PIN EDGE CONNECTOR 1 25 NOM 218 MAX 250 Q C H V TERMINAL 164 010 DIA 4 MOUNTING HOLES ...

Страница 5: ...lectrode Location Proper location of electrode assembly is important for optimum system performance The electrode assembly should be located so that the tips are inside the flame envelope and about 1 2 inch 1 2 cm above the base of the flame as shown Notes Ceramic insulators must not be in or close to the flame Electrode assemblies must not be adjusted or disassembled Electrodes are NOT field adju...

Страница 6: ...s void Troubleshooting Guide Symptom Recommended Actions 1 Dead A Miswired B Transformer battery fault C Fuse circuit breaker fault D No voltage at PWR or AIR E Bad control 2 Thermostat on no blower output A Miswired or failed air flow switch B Faulty thermostat no voltage at thermostat terminal TH C Faulty control 3 Airflow Switch input okay but no TFI after purge delay A Miswired B Faulty contro...

Страница 7: ... X X X X DESCRIPTION Trial for Ignition Time 1 5 econds 3 7 econds 5 10 econds 7 25 econds S S S S Inter Purge 0 None 1 15 econds 3 25 econds S S Product Designation 2 CE EN298 Standard Recycle 3 CE EN298 Special Configuration A 3 in this location indicates a special configuration Consult Fenwal controls for operating characteristics of this control Pre Purge 0 None 1 15 Seconds 3 25 Seconds Tries...

Страница 8: ...3 SERIES 35 60 61 63 608 SERIES 35 65 66 SERIES 35 9X The object of the declaration described above is in conformity within the relevant union harmonization legislation Gas Appliance Regulation EU 2016 426 Low Voltage Directive 2014 35 EC EMC Directive 2014 30 EC Rohs 2011 65 EU The following harmonized standards and technical specifications have been applied EN298 2012 Automatic Burner Control sy...

Отзывы: