FEMA ELECTRÓNICA . Series S . S40-T
5
Functions included
Section
‘Fast access’
yes
Manual offset
configurable
Thermocouple cold junction configurable
Sensor break detection
configurable
Display filters
steps
Memory
max. and min. readings
Password
configuration block
Alarms
double setpoints
activation delays
deactivation delays
hysteresis
inverted relays
locked alarms
Display brightness
5 levels
‘On Power Up’
yes
Table 2 - Functions included
Mechanical
mounting
panel
connections
plug-in screw terminal
housing material
ABS, polycarbonate (V0)
weight
<150 grams
front size
72 x 36 mm
panel cut-out
69 x 32.5 mm
depth from panel
98 mm (including terminals)
Temperature
operation
from 0 to +50 ºC
storage
from -20 to +70 ºC
warm-up time
15 minutes
Messages and errors
‘h.oVr’
Hardware overrange (‘
h.ovr
’). Input signal is higher than
the maximum signal the instrument can detect (80 mV)
‘h.udr’
Hardware underrange (‘
h.udr
’). Input signal is lower than
the minimum signal the instrument can detect (-30 mV).
‘d.udr’
‘d.oVr’
display underrange (‘
d.udr
’) / overrange (‘
d.ovr
’). The
instrument already displays the minimum / maximum
value possible (-1999 / 9999).
‘brk’
instrument will display ‘brk’ message in the following
cases
• when measuring Pt100 / RTD, the resistance measured
is higher than 390 Ohms (higher than 850 ºC)
• when measuring Pt100 / RTD, the third wire (sense
wire) presents an impedance higher than 15 Ohms
• when measuring thermocouples, the thermocouple cir
-
cuit is open circuit
‘Err.1’
incorrect password.
‘Err.2’
at ‘
oPt.X
’ menu entry. Installed module is not recognized.
Table 3 - Messages and error codes
The error messages are shown on display in flash mode.
1.9 Messages and errors
1.8 Technical specifications (cont.)