13. Configuration menu

13.1 Scaling

At the ‘

Scaling

’ (

ScAL

) menu entry, configure the display reading. See 

section 8 for a detail on the 2 points associated to scaling.

 at the ‘

Decimal point

’ (‘

dP

’) parameter configure the position for the 

decimal point. Use key ‘

LE

’ (

3

) to move the decimal point position. 

Press key ‘

SQ

’ (

<

) to validate.

  at  the  ‘

Display  low

’  (‘

d.Lo

’)  parameter  configure  the  reading 

associated  to  an  input  signal  low  of  4 mA.  Input  signal  low  can  be 

modified by using the ‘

field correction

’ function (see section 13.2) or by 

direct configuration of ‘

input low

’ parameter (see section 13.5).

  at  the  ‘

Display  high

’  (‘

d.hI

’)  parameter  configure  the  reading 

associated to an input signal high of 20 mA. Input signal high can be 

modified by using the ‘

field correction

’ function (see section 13.2) or by 

direct configuration of ‘

input high

’ parameter (see section 13.5).

0 to 100

Scaling

Decimal point

Display low

Display high

Field correction

Correction low

Correction high

Wait for 3 seconds

Wait for 3 seconds

13.2 Field correction

At the ‘

Field correction

’ (

F.cor

) menu entry, access the ‘

field correction

’ 

functions.  Use  the  ‘

field  correction

’  functions  to  associate  the  actual 

input  signal  at  terminals,  to  the  ‘

display low

’  or  ‘

display  high

’  display 

values. See section 8 for a detail on the 2 points associated to scaling.

 at ‘

Correction low

’ (

F.Lo

) press key ‘

SQ

’ (

<

) to activate the function. 

The display reads ‘

wait

’ while performs the reading of the actual input 

signal  value  and  associates  this  value  to  the  ‘

input low

’  parameter. 

When finished, the instrument goes back to the ‘

Correction low

’ (

F.Lo

menu entry.

 at ‘

Correction high

’ (

F.hI

) press key ‘

SQ

’ (

<

) to activate the function. 

The display reads ‘

wait

’ while performs the reading of the actual input 

signal value and associates this value to the ‘

input high

’ parameter. 

When finished, the instrument goes back to the ‘

Correction high

’ (

F.hI

menu entry.

Display

Square root

Average filter

Steps

Left zeros

Memory of max.

Memory of min.

13.3 Display

The  ‘

Display

’  (

dISP

)  menu  entry  groups  configuration  parameters 

associated to the display.

 activate the ‘

Square root

’ (

Sq.rt

) parameter to ‘

on

’ to apply a ‘

square 

root

’ function to the reading. The instrument reads the input signal 

value  in  milliamperes,  and  scales  the  reading  as  configured  at  the 

scaling

’ section. Then applies the ‘

square root

’ function to the scaled 

value. The last action applies the filter values (‘

average

’, ‘

steps

’, etc) 

and reads the final value on display. The ‘

square root

’ function is to be 

applied when working with differential pressure flow meters.

 the ‘

Average filter

’ (

AVr

) applies a recursive filter upon the reading 

values, in order to reduce oscillations due to noisy signals. Configure 

the  filter  strength  between  ‘0’  and  ‘100’.  The  filter  is  stronger  with 

higher values. Value ‘0’ disables the filter. Increasing the strength of 

the filter slows the reading.

 the ‘

Steps

’ (

StEP

) function configures the reading to be done in steps 

of 1, 2, 5, 10, 20 or 50 counts.

 the ‘

Left zeros

’ (

LZEr

) parameter activates the reading with active 

left zeros.

Содержание LP4

Страница 1: ...www fema es SPECIAL YOUR METER APPLICATIONS Model LP4 USER S MANUAL Loop mA LOOP POWERED PROCESS METER SERIES SPECIAL 5137r01...

Страница 2: ...6 13 4Key UP fast access 7 13 5 Tools menu 7 14 Technical specifications 8 15 Error codes 8 16 Mechanical dimensions mm inch 8 17 Precautions on installation 9 18 Warranty 9 19 Factory default paramet...

Страница 3: ...d connections Inverted connections will not damage the instrument the loop will remain open and the instrument does not operate display does not light Terminal 2 is not connected Connecting any of the...

Страница 4: ...ries parameters and select configuration values Key SQ functions as the ENTER key It selects the menu entry currently displayed At numerical value entries it validates the number displayed Key UP 5 mo...

Страница 5: ...r appears and select by pressing the SQ key or wait without pressing any key until the automatic rollback activates When exiting the fast access menu the instrument returns to normal mode of operation...

Страница 6: ...ads wait while performs the reading of the actual input signal value and associates this value to the input low parameter When finished the instrument goes back to the Correction low F Lo menu entry a...

Страница 7: ...ect Measure function MEAS to activate an access to visualize the actual input signal value in milliamperes without the scaling 13 5 Tools menu The Tools tool menu groups several functions at the Input...

Страница 8: ...isplay display refresh 2 times second acquisition per second 2 acquisitions second memory retention values for maximum and minimum reading are stored every 10 minutes INPUT SIGNAL signals accepted 4 2...

Страница 9: ...r than the minimum current needed The instrument is designed to be panel mounted An appropriate ventilation of the instrument must be assured Do not expose the instrument to excess of humidity Maintai...

Страница 10: ...of LP4 loop powered meter placed close to the transmitter using the existing loop to the PLC 4 20mA transmitter Units LP4 loop powered meter PLC The LP4 loop powered meter can be directly inserted int...

Страница 11: ...2 3Protector KIP Wall mount housing Together with the KIP protector offers a full IP65 protection For for 96x48mm panel meters 22 2 4WME wall housing Benchtop housing for for 96x48mm panel meters Han...

Страница 12: ......

Отзывы: