SERIES I4 · Model I4L

Section INDUSTRIAL . ISOLATED SIGNAL CONVERTERS

www.fema.es 

19

13. Configuration menu (cont.)

Password

Version

Factory reset

‘Dead band’

0.0 to 100.0%

 at the ‘

Dead band

’ (

d.bnd

)  parameter  set  a  value  between  ‘0.0’ % 

and ‘100.0’ %. This is a percentage of the ‘

input signal high

’ parameter 

configured at the ‘

Advanced scaling

’ section. Input signals below this 

value, are treated as a ‘0’.

example : instrument configured with code ‘011’ (0/10 mVdc = 4/20 mA) 

and  ‘input  signal  high’  parameter  modified  to  8 mVdc  for  an  effective 

input - output relation of ‘0/8 mVdc = 4/20 mA’. Configure the ‘Dead band’ 

parameter to ‘1.0’ to set a dead band value of 0.08 mVdc. All signals below 

0.08 mVdc will be treated as 0 mVdc, and the output will be 4 mA.

 the ‘

Version

’ (

VEr

) parameter informs about the firmware version 

running in the instrument.

 at the ‘

Password

’ (

PASS

)  parameter  define  a  4  digit  code  to 

block access to the ‘

configuration  menu

’. Activate the password to 

prevent  access  to  the  instrument  configuration  by  non  authorized 

personnel. To activate the ‘

Password

’ function select ‘

on

’, enter the 

code and validate. The password will be requested when accessing 

the ‘

configuration menu

’. The password does not block access to the 

force

’ menu. To deactivate the password, set the parameter to ‘

oFF

’.

 at the ‘

Factory reset

’ (

FAct

) parameter select ‘

yes

’ to activate the 

default  factory  configuration  (see  section  15  for  a  list  of  factory 

default parameters).

Содержание I4 Series

Страница 1: ...www fema es SERIES I4 Model I4L USER S MANUAL ISOLATED SIGNAL CONVERTER Section INDUSTRIAL 5583r00 INDUSTRIAL Weight Kg Load cell mV...

Страница 2: ...ocs 5587_I4L_installation_en pdf CE declaration www fema es docs 5642_CE Declaration_I4_en pdf Warranty www fema es docs 4153_Warranty1_en pdf Web www fema es Series_I4 3 Additional information When t...

Страница 3: ...Read the practical load cell information see section 7 4 Connect the input the output and the power terminals see section 9 error messages may appear in the process of connection see section 16 for ex...

Страница 4: ...ead signal for changes at the excitation voltage The actual value of the excitation voltage is detected by using the sense wires Connect the sense and sense terminals 5 and 2 to the load cell to provi...

Страница 5: ...g 3 load cells is the optimal way to distribute the weight on a plane although it is common to work with 4 load cells in applications with tanks hoppers and similar When working with multiple load cel...

Страница 6: ...trument reads uSEr Code identifies the end of the list it follows code 199 and the list continues with code 010 Select to exit the list without applying changes To calculate the optimal input signal r...

Страница 7: ...dc 7 8 9 common Vdc fuse signal sense Vexc POWER ABC 18 to 265 Vac dc isolated OUTPUT SIGNAL 789 sense common 0Vdc or passive mA current out signal 4 20mA mA current in signal 0 10Vdc or active mA cur...

Страница 8: ...ion voltage terminals OUTPUT SIGNAL The output signal is configurable to 4 20mA active and passive and 0 10Vdc Table 13 Input signal ranges for load cell signals Input range Code for 4 20mA output Cod...

Страница 9: ...ifications OUTPUT SIGNAL The output signal is configurable to 4 20mA active and passive and 0 10Vdc Table 14 Connection examples for millivolt signals 1 2 3 not connected mV not connected 4 5 6 not co...

Страница 10: ...he input with no filter 115 mSec typ 0 to 99 with 50Hzfilter or 60Hzfilter 150mSec typ 0 to 99 with 50 and 60Hz filter 300mSec typ 0 to 99 OUTPUT SIGNAL RANGES active current output 4 20mA active max...

Страница 11: ...SERIES I4 Model I4L Section INDUSTRIAL ISOLATED SIGNAL CONVERTERS www fema es 11 T h i s p a g e b l a n k...

Страница 12: ...t returns to normal mode of operation HOW TO OPERATE INSIDE THE CONFIGURATION MENU Inside the configuration menu use the front keypad to move through menu entries parameters and select configuration v...

Страница 13: ...ee section 13 8 The messages function ends when all the information has been displayed or front keys UP 5 or SQ are pressed The display returns to normal mode of operation 12 5 How to activate the Mes...

Страница 14: ...cted a configuration code see section 13 1 the input signal has been already selected and there is no need to manually select the Mode ModE or Signal range rAnG parameters again At the Mode ModE param...

Страница 15: ...ressed in x xx mA or in x xx Vdc at the Output high signal ou hI parameter configure the high output signal value This value is expressed in x xx mA or in x xx Vdc These four parameters define the rel...

Страница 16: ...citation current EX MA to read the value of the current provided through the excitation voltage terminals for example ExMA 14 3 Display information Input signal value in mV Output signal value Label S...

Страница 17: ...rrected millivolts mV see section 10 1 configure Input signal value InP S to on to see the input signal value and the measurement units for example Inp mV 8 52 This value is expressed in millivolts mV...

Страница 18: ...and to underrange output signal to minimum value in case of input signal underrange at the On SQ on Sq parameter configure the behavior of the output signal when the operator is inside configuration...

Страница 19: ...set a dead band value of 0 08mVdc All signals below 0 08mVdc will be treated as 0mVdc and the output will be 4mA the Version VEr parameter informs about the firmware version running in the instrument...

Страница 20: ...oltage Excitation voltage 0 70mV 0 80mV 10mV 20mV 30mV 40mV 50mV 60mV 70mV 80mV 5mV Output range ok message flashes while the field correction function is being applied and when finished the instrumen...

Страница 21: ...abel2 Alphanumerical 0 0 to 100 0 SOS mode of output On error Output to high Output to low Output standard Power filter No filter Filter for 50Hz Filter for 60Hz Filter for 50Hz and 60Hz On SQ Output...

Страница 22: ...ell cELL Signal range rAnG 10 00mV Excitation voltage V EXc on Output range out 4 20mA Advanced scaling Ad Sc Tare tArE 0 00 mV Input signal low In Lo 0 00 mV Input signal high In hI 10 00 mV Output s...

Страница 23: ...r motor controllers electrovalves together with signal and or control cables The use of shielded cables is recommended to prevent the coupling of environmental electromagnetic noise connected to earth...

Страница 24: ......

Отзывы: