Section INDUSTRIAL . ISOLATED SIGNAL CONVERTERS
19
13. Configuration menu (cont.)
Password
Version
Factory reset
‘Dead band’
0.0 to 100.0%
•
at the ‘
Dead band
’ (
d.bnd
) parameter set a value between ‘0.0’ %
and ‘100.0’ %. This is a percentage of the ‘
input signal high
’ parameter
configured at the ‘
Advanced scaling
’ section. Input signals below this
value, are treated as a ‘0’.
example : instrument configured with code ‘011’ (0/10 mVdc = 4/20 mA)
and ‘input signal high’ parameter modified to 8 mVdc for an effective
input - output relation of ‘0/8 mVdc = 4/20 mA’. Configure the ‘Dead band’
parameter to ‘1.0’ to set a dead band value of 0.08 mVdc. All signals below
0.08 mVdc will be treated as 0 mVdc, and the output will be 4 mA.
•
the ‘
Version
’ (
VEr
) parameter informs about the firmware version
running in the instrument.
•
at the ‘
Password
’ (
PASS
) parameter define a 4 digit code to
block access to the ‘
configuration menu
’. Activate the password to
prevent access to the instrument configuration by non authorized
personnel. To activate the ‘
Password
’ function select ‘
on
’, enter the
code and validate. The password will be requested when accessing
the ‘
configuration menu
’. The password does not block access to the
‘
force
’ menu. To deactivate the password, set the parameter to ‘
oFF
’.
•
at the ‘
Factory reset
’ (
FAct
) parameter select ‘
yes
’ to activate the
default factory configuration (see section 15 for a list of factory
default parameters).