background image

FEMA ELECTRÓNICA . Series S . S40-P

8

1.10 Configuration menu (cont.)

The instrument provides several functions to personalize the reading 

of the display values
• the ‘

Fixed Digits

’ (‘

FIX.d

’) allows to fix each digit to a fixed value. 

As an example, fix the least significant digit to a ‘0’ in order to block 

noisy fluctuations. To fix a digit, all digits to its right must be also 

fixed. Value ‘-’ means that the digit is not fixed.
• the ‘

Average filter

’ (‘

AVr

’) function allows to reduce reading oscil

-

lations due to noisy signals. It applies a recursive filter on the reading 

value. To activate the average filter set ‘

AVr

’ to ‘

on

’ and assign the fil

-

ter strength between ‘0.0’ and ‘99.9’. Higher values activate stronger 

filter. Stronger filters slow down the reading changes.
•  the  ‘

Steps

’  (‘

StEP

’)  function  allows  to  define  minimum  reading 

steps, which will be done in steps of 1, 2, 5, 10, 20 or 50 counts.

Example - selecting a step of 20 configures the reading to change in 

steps of 20 counts (‘1420’, ‘1440’, ‘1460’, ...).

• the ‘

Left Zero

’ (‘

LZEr

’) function lights all zeros to the left.

• the ‘

Memory of maximum

’ (‘

MAX

’) function displays the maximum 

reading value stored in memory. It also provides a way to reset the 

value. This parameter is eligible for configuration through the ‘

Fast 

access

’ menu 

(see section 1.10.6).

 • the ‘

Memory of minimum

’ (‘

MAX

’) function displays the minimum 

reading value stored in memory. It also provides a way to reset the 

value. This parameter is eligible for configuration through the ‘

Fast 

access

’ menu 

(see section 1.10.6).

• the ‘

Peak & hold

’ (‘

P.hLd

’) function visualizes and hold the maxi

-

mum reading. For test-break applications, where the meter always 

increases its value until the unit under test breaks and the signal falls 

down. The meter maintains the maximum reading before the signal 

fell down.
To free the ‘hold’ reading, press any of the front key pad or wait the 

time configured at the ‘

time

’ parameter.

   Time 0  

hold disabled (Off)

   Time 1 a 3999  seconds waiting
   Time 4000 

infinite hold

While ‘hold’ is active, the instrument alarms are still associated to 

the input signal, therefore still providing control to disconnect the 

application once the test has finished.

1.10.4 

Display filters

Left zeros

Steps

Average filter

0.0 to 99.9

Display

Fixed digits

Fix digits

Memory of 

maximum

Memory of 

minimum

Peak & Hold

Time (Sec.)

Содержание S40-P

Страница 1: ...linearization fast access to alarm setpoints tare function on power up function measure function configurable reading brightness Universal AC and DC power Up to 2 optional modules for output and contr...

Страница 2: ...hold for test break applications see section 1 10 4 Multiple display filters memory for maximum and minimum reading password protection 5 brightness levels 1 1 How to order Index 1 Panel meter S40 P...

Страница 3: ...connections Button UP Logo Alarms Units Button SQ Button LE Configuration menu see section 1 10 Fast access see section 1 10 6 1 6 Mechanical dimensions mm Signal see section 1 5 Jumpers see section...

Страница 4: ...Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20 mA 0 05 FS 11 Ohm 100 mA permanent 10 ppm C 25 ppm C 0 10 Vdc 0 05 FS 932 KOhm 100 Vdc permanent 10 ppm C 25...

Страница 5: ...Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the chang...

Страница 6: ...ed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the offset cor rection generate the minimum input signal and access the Fi...

Страница 7: ...e alarm relays due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set po...

Страница 8: ...ory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see...

Страница 9: ...at the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP...

Страница 10: ...rE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does not...

Страница 11: ...menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this function it is possible to ada...

Страница 12: ...on 1 10 for a description of each menu entry Scaling Input low Display low Input high Display high Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Activation delay Deactivation delay Left zer...

Страница 13: ...ng Activate Reset Number of segments Value 2 to 20 Input 0 Display 0 Input 1 Display 1 On power up Delay Tare Seconds Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configurati...

Страница 14: ...el only You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock the lower clips marked with B...

Страница 15: ...ay 0 seconds Tare off Key LE no function Excitation voltage 20 Vdc Password off Brightness 3 clean by using a humid rag and do NOT use abrasive products such as alcohols solvents etc General recommend...

Страница 16: ...t 1 Power Signal A B C A B C The R1 module provides 1 relay output to to install at digital panel meters from Series S up to a maximum of 2 relays in a single meter Note for more than 2 relays per ins...

Страница 17: ...ayed installation as it does not require soldering or special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more inform...

Страница 18: ...uration Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_i pdf Protocol Modbus RTU Functi...

Страница 19: ...up to 31 modules Frames codified in represent able ASCII characters codes 32 to 255 directly visible using hyper terminal or similar programs Access to display values alarm status memory of maximum a...

Страница 20: ......

Отзывы: