Fema Electronica M60-P Скачать руководство пользователя страница 10

FEMA ELECTRÓNICA . Series M . M60-P

10

On power-up

Delay

Tare

Seconds

Tools

1.10 Configuration menu (cont.)

The ‘

On Power Up

’ (‘

on.Pu

’) menu configures functions to apply at 

start-up. It applies only to instrument restart after power loss. It does 

not apply to instrument restart due to change in configuration.
• parameter ‘

Delay

’ (‘

dLAy

’) assigns a waiting time in seconds. The 

instrument waits the configured time before starting normal func

-

tion. During this waiting time, the display shows all decimal points 

on in flash mode, all alarms are in ‘oFF’ state, there is no signal acqui

-

sition and there is no communications or control being performed. 

After  the  configured  time  is  over,  the  instrument  starts  in  normal 

function. Delay value between 0 and 200 seconds.

Application - the start-up process for an automation system implies 

that different parts of the system (engines, actuators, controllers, ...) 

have different start-up times. The ‘Delay’ function gives time to the 

instrument to wait until the slowest part of the system is fully func-

tional before executing actions on the system (signal reading, relay 

activation, ...)

• the ‘

Tare

’ (‘

tArE

’) functions allow to activate an automatic tare of 

the reading each time the instrument is restarted. See section 

1.10.9

 

for more information on the ‘tare’ function.

1.10.8 Menu ‘On Power Up’

The ‘

Tare function

’ (‘

tArE

’) menu allows to operate the instrument 

for load-cell and weight applications. The tare function assigns the 

actual input signal value to a reading of ‘0’ Kilos, by adding an inter

-

nal offset. It does not modify the scaling parameters of the instru

-

ment.
The ‘Tare’ function can be applied pressing button ‘LE’ (

3

) at the 

front keypad 

(see section 1.10.10)

The offset value is eligible for visu

-

alization through the ‘

Fast access

’ menu 

(see section 1.10.6).

To work with load-cell applications it is important to first adjust the 

scaling of the instrument to the load-cell used.

Application - A load cell with 2 mV/V parameter, powered at 10 Vdc, 

with nominal weight of 500 Kilos, together with a signal converter 

that provides 4/20 mA signals for a 0/20 mV signal from the load-cell. 

The scaling to configure at the meter is 4/20 mA = 0/500.0 Kilos. Once 

the meter is scaled, the tare function can be used to ‘tare’ the reading 

to 0 Kilos.

• at the ‘

Reset

’ (‘

rSt

’) menu select ‘

yES

’ to reset the tare offset value 

in memory.

1.10.9 Menu ‘Tare function’

Tare function

Reset

Key LE

Tare

Alarm unlock

No function

1.10.10 Menu ‘Key LE’

The ‘LE’ (

3

) key at the front of the instrument can be configured to 

activate several functions. Only one function can be assigned to the 

‘LE’ (

3

) key

• the ‘

No function

’ (‘

nonE

’)

 

value assigns no function.

• the ‘

Tare

’ (‘

Tare

’) value assigns a tare function 

(see section 1.10.9).

• the ‘

Alarm unlock

’ (‘

A.Lck

’)

 

value assigns the manual unlock of the 

alarms function, for instruments with the ‘

Locked alarms

’ (‘

A.Lck

’) 

function activated 

(see section 1.10.3)

Содержание M60-P

Страница 1: ...fast access to alarm setpoints tare function on power up function measure function configurable reading brightness Universal AC and DC power Up to 3 optional modules for output and control relays tran...

Страница 2: ...m and minimum reading password protection 5 brightness levels Index 1 Panel meter M60 P 2 1 1 How to order 2 1 2 Front view 3 1 3 Rear view 3 1 4 Power connections 3 1 5 Signal connections 3 1 6 Mecha...

Страница 3: ...SQ Button LE Configuration menu see section 1 10 Fast access see section 1 10 6 1 6 Mechanical dimensions mm Signal see section 1 5 Jumpers see section 1 5 Option 1 Option 2 Option 3 Power see sectio...

Страница 4: ...5 W only meter 4 0 W meter with options Configuration 3 buttons front keypad and rear jumper 1 7 Technical specifications Ranges Accuracy Zin Max signal overload 4 20 mA 0 03 FS 11 Ohm 100 mA permanen...

Страница 5: ...E 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the changed pa...

Страница 6: ...imum input signal The Field correction F cor functions allows to correct the instrument scaling parameters when the instrument is being installed on the field providing a fast and easy way to compensa...

Страница 7: ...ing of the alarm relays due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when t...

Страница 8: ...ry of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see s...

Страница 9: ...nt gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu allows to select which f...

Страница 10: ...rE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does not...

Страница 11: ...access the configuration menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this funct...

Страница 12: ...0 to 100 Display Fixed digits Memory of maximum Memory of minimum Peak Hold Time seconds Alarm 2 menu Alarm 3 menu Relay inverted Locked alarm Alarms Alarm 1 Setpoint Hysteresis Active Alarm type Fiel...

Страница 13: ...f segments Value 2 to 31 Input 0 Display 0 Input 1 Display 1 On power up Delay Tare Seconds Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configuration menu for the module ins...

Страница 14: ...that all modules are correctly connected to the pins on the display module Place all the set into the housing assuring that the modules correctly fit into the internal guiding slides of the housing O...

Страница 15: ...d off Brightness 3 strument must be assured Do not expose the instrument to excess of humidity Maintain clean by using a humid rag and do NOT use abrasive products such as alcohols solvents etc Genera...

Страница 16: ...tinuous Isolation 3500 Veff Type of terminal plug in screw terminal pitch 5 08 mm Slots allowed Opt 1 Opt 2 Opt 3 Terminal A Common Terminal B NO Normally open Terminal C NC Normally closed Power Opt...

Страница 17: ...pecial configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manu...

Страница 18: ...Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manu...

Страница 19: ...rograms Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrument front keypad through menu entries Opt 1 Opt 2 or Opt 3 depending on the positi...

Страница 20: ...out front key pad To configure the instrument remove the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument pre...

Страница 21: ...1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Wall mount housing Together with the KIP protector offer a full...

Страница 22: ...FEMA ELECTR NICA Series M M60 P 22 Notes...

Страница 23: ...FEMA ELECTR NICA Series M M60 P 23 Notes...

Страница 24: ......

Отзывы: