FEMA ELECTRÓNICA . SERIES B . Models Bxx-T

2

1. Series B, models Bxx-T 

Large format industrial meters for temperature signals

Large format meters for long distance reading, for industrial 

applications. Different formats available with 4 and 6 digits, 

with 60 mm and 100 m digit height. Front keypad to access the 

configuration menu, and optional remote keypad.
Models  to  measure  temperature  signals  from  Pt100 / RTD 

probes with 2 and 3 wires, and thermocouple types J, K, T, E, 

S, R, N, C, L and X. Reading configurable in degrees Celsius (ºC) 

or Fahrenheit (ºF). Configurable compensation of the thermo

-

couple cold junction 

(see section 1.13.2)

Configurable manual 

offset 

(see section 1.13.2)

Configurable behaviour in case of 

sensor break 

(see section 1.13.2)

Output and control options with 1, 2 and 3 relays, transis

-

tor outputs, controls for SSR relays, isolated analog outputs, 

communications in Modbus RTU, RS-485 ASCII and RS-232.

Sturdy  metal  housing  with  full  IP65  protection.  Internal 

connections  by  plug-in  screw  clamp  terminals,  and  output 

through cable glands. Housing prepared for panel, wall and 

hanging mount.

• Configurable ‘

Fast access

’ to selected functions with key 

‘UP’ (

5

(see section 1.13.6)

•  ‘

On power up

’  for  system  protection  on  ‘cold’  start-up 

and / or activation of automatic tare 

(see section 1.13.7)

• alarms with 1 or 2 setpoints, independent activation and 

deactivation delays, hysteresis, manual unlocking, ... 

(see 

section 1.13.3)

Display filters, memory of maximum and minimum reading, 

password protection, 5 brightness levels.

1. Identify the instrument forma

(see section 1.4)

2. Power and signal connections

- open the instrumen

(see section 1.5)

- connect the power 

(see section 1.7)

- connect the signal 

(see section 1.8)

- close the instrumen

(see section 1.5)

3. Configure the instrumen

(see section 1.13)

- configure the sensor connected and configure the tem

-

perature parameter

(see section 1.13.2)

4. Advanced configuration (optional)

- configure the instrument alarms 

(see section 1.13.3)

- configure the fast access 

(see section 1.13.6)

-  configure  other  functions  :  display  filters 

(1.13.5), 

‘on 

power  up’ 

(1.13.7)

,  key  ‘LE’ 

(1.13.8)

,  and  password 

(1.13.11)

1.1 How to use this manual

5.  If  the  instrument  includes  analog  output  (AO)  or  serial 

communications (RTU, S4, S2)

- to include an option to an instrument see section 

1.6

- to configure an installed option, access the option con

-

figuration menu 

(see section 1.13.15)

- see section 

2

 for information regarding the output and 

control options available

6. Install the instrument

- mount on panel, wall or hanging 

(see section 1.16)

- adjust the brightness level according to your environmen

-

tal needs 

(see section 1.13.14)

If this is the first time you are configuring a Series B large 

format meter, below are the steps to follow to install and 

configure the instrument.

Read all the manual sections in order to have a full and clear 

view of the characteristics of the instrument. Do not forget 

to read the installation precautions at section 

1.17

.

Содержание B Series

Страница 1: ...wires and thermocouple types J K T E S R N C L and X Reading configurable in C or F configurable manual offset configurable compensation of the thermocouplecoldjunction breakprobedetectionand5configur...

Страница 2: ...resis manual unlocking see section 1 13 3 Display filters memory of maximum and minimum reading password protection 5 brightness levels 1 Identify the instrument format see section 1 4 2 Power and sig...

Страница 3: ...11 Password configuration 16 1 13 12 Default factory configuration 16 1 13 13 Firmware version 16 1 13 14 Brightness configuration 16 1 13 15 Access to the options configuration menu 16 1 14 Factory...

Страница 4: ...Power Option2 Option1 Remote keypad Signal Power Slot for option 2 Slot for option 1 Input signal terminal Remote keypad terminal C D E Cable glands B F G Panel cut out see Table 2 1 4 2 Format B44 S...

Страница 5: ...1 Size A 436 mm Size B 135 mm Size C 3 mm Size D 55 mm Size E 25 mm Table 5 Sizes B26 Cut out G 418 mm 1 Cut out F 117 mm 1 Table 6 Panel cut out B26 F G Panel cut out see Table 6 1 4 4 Format B46 C D...

Страница 6: ...s are independent and can be installed by accessing the internal circuits of the instrument and connecting the mod ule to the connection jumpers of the selected slot Each module is provided with a cab...

Страница 7: ...al 6 The connections label attached to the outside of the in strument has some free space left to write the color or local code for each cable 7 To comply with security regulation 61010 1 add to the p...

Страница 8: ...ilters steps 1 13 5 On Power Up yes 1 13 7 Alarms simple or double setpoint activation delays deactivation delays hysteresis inverted relays locked alarms 1 13 3 Memory maximum minimum 1 13 6 Password...

Страница 9: ...ge en F Offset thermal drift Span thermal drift includes offset thermal drift Pt100 RTD 800 200 C 0 2 C 1562 328 F 0 05 C 0 10 C Thermocouple J 1200 200 C 2 C 2192 328 F 0 05 C 0 20 C Thermocouple K 1...

Страница 10: ...y acts as an ENTER It enters into the menu option selected and when entering a numerical value it validates the num ber Key UP 5 press the UP 5 key to access the fast ac cess menu Inside the menu the...

Страница 11: ...epted from 100 to 100 counts of display at the Thermoc CJC t cJc parameter activate o de activate the automatic compensation of the thermocouple cold junction When working with real thermocouples comp...

Страница 12: ...delays Each alarm can configure independent activation and deactivation delays These delays affect the alarm as a whole and the delay will affect the front led and the as sociated relay Second setpoin...

Страница 13: ...pply before the alarm is activated Delay starts to count once the setpoint is reached Value from 0 0 to 99 9 seconds at the Deactivation delay dEL 1 parameter config ure the delay to apply before the...

Страница 14: ...t affected by the password func tion This means that the configuration menu can be password blocked while some configured functions or parameters can still be accessible to the operator through the fa...

Страница 15: ...fast access menu the Setpoint2 ALr2 function allows to visualize and modify the alarm2 setpoint through the fast access menu the Setpoint3 ALr3 function allows to visualize and modify the alarm3 setpo...

Страница 16: ...uments in the vicinity or to the darkness or clarity of your environment Minimum Brightness Maximum Standard The Version VEr menu informs about the firmware ver sion installed on the instrument Versio...

Страница 17: ...Alpha 385 Alarms 1 2 and 3 Active off disabled Type as maximum Setpoint 1000 Hysteresis 0 counts Activation delay 0 0 seconds Deactivation delay 0 0 seconds Setpoint 2 off Inverted relay off Locked a...

Страница 18: ...tpoint 2 Active Alarm type Activation delay Deactivation delay Pt100 RTD 2 wires Pt100 RTD 3 wires Thermocouple J Thermocouple K Thermocouple T Thermocouple E Thermocouple S Thermocouple R Thermocoupl...

Страница 19: ...n Power Up Delay Seconds Alarm 1 Alarm 2 Alarm 3 Password Firmwareversion Factory configuration Key LE Alarm unlock No function Option 1 Access to the optional module installed at slot1 Option 2 Acces...

Страница 20: ...ion see the IPB ac cessories at section 3 Side fixations Fixation screws Diameter 4 5mm 30mm between hole centers Figure 11 Hanging mount Diameter 4 5mm 30mm between hole centers Side fixations Fixati...

Страница 21: ...period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse ac cident or manipulation by non authorized personnel In case of malfunction get in contact with your local p...

Страница 22: ...35 Vdc Max current 50 mA Isolation 3500 Veff optoisolated Terminal plug in screw clamp pitch 5 08 mm Installation allowed at slot1 slot2 slot3 The T1 module provides 1 transistor output to install in...

Страница 23: ...on 1 6 on how to install output and control modules For more information http fema es docs 4326_SERIES B_OPTIONS_manual_i pdf 2 3 Module SSR The SSR module provides 1 output for SSR relay control to i...

Страница 24: ...output and control modules Protocol Modbus RTU Bus RS 485 up to 57 6 Kbps Isolation 1000 Vdc Terminal plug in screw clamp pitch 5 08 mm Installation allowed at slot1 slot2 slot3 The RTU module provid...

Страница 25: ...um Configuration is performed from the front keypad of the in strument by accessing the menu entries Opt 1 Opt 2 or Opt 3 according to the slot where the module is installed Modules S2 can be provided...

Страница 26: ...IPB accessories provide IP65 protection to the panel junction Includes 4 accessories for B24 formats JPG 3 3 IPB26 The IPB accessories provide IP65 protection to the panel junction Includes 6 accessor...

Страница 27: ...FEMA ELECTR NICA SERIES B Models Bxx T 27 3 6 Output cable 2 meters of cable output power remote keypad signal JPG...

Страница 28: ......

Отзывы: