FEMA ELECTRÓNICA . SERIES B . Models Bxx-T

21

This instrument has been designed and verified conforming to 

the 61010-1 CE security regulation, for industrial applications.

Installation of this instrument must be performed by qualified 

personnel only. This manual contains the appropriate informa

-

tion for the installation. Using the instrument in ways not spec

-

ified by the manufacturer may lead to a reduction of the speci

-

fied protection level. Disconnect the instrument from power 

before starting any maintenance and / or installation action.

The instrument does not have a general switch and will start 

operation as soon as power is connected. The instrument does 

not have protection fuse, the fuse must be added during instal

-

lation.

An appropriate ventilation of the instrument must be assured. 

Do not expose the instrument to excess of humidity. Maintain 

clean by using a humid rag and do NOT use abrasive products 

such as alcohols, solvents, etc.

General recommendations for electrical installations apply, and 

for proper functionality we recommend : if possible, install the 

instrument far from electrical noise or magnetic field genera

-

tors such as power relays, electrical motors, speed variators, ... 

If possible, do not install along the same conduits power cables 

(power, motor controllers, electrovalves, ...) together with sig

-

nal and/or control cables.

Before  proceeding  to  the  power  connection,  verify  that  the 

voltage level available matches the power levels indicated in 

the label on the instrument.

In case of fire, disconnect the instrument from the power line, 

fire alarm according to local rules, disconnect the air condition

-

ing, attack fire with carbonic snow, never with water.

1.17 

Installation precautions

Risk  of  electrical  shock.  Instrument  terminals  can  be 

connected to dangerous voltage.

Instrument conforms to CE rules and regulations. 

This  instrument  is  warranted  against  all  manufacturing 

defects  for  a  period  of  24  MONTHS  from  the  shipment 

date. This warranty does not apply in case of misuse, ac

-

cident or manipulation by non-authorized personnel. In 

case of malfunction get in contact with your local provid

-

er to arrange for repair. Within the warranty period and 

after examination by the manufacturer, the unit will be 

repaired or substituted when found to be defective. The 

scope of this warranty is limited to the repair cost of the 

instrument,  not  being  the  manufacturer  eligible  for  re

-

sponsibility on additional damages or costs.

1.18 Warranty

1.19 

CE declaration of conformity

Manufacturer FEMA ELECTRÓNICA, S.A. 

 

Altimira 14 - Pol. Ind. Santiga

 

 

E08210 - Barberà del Vallès 

 

 

BARCELONA  - SPAIN 

 

www.fema.es - [email protected]

Products  

B24-T, B44-T

The manufacturer declares that the instruments indicated com

-

ply with the directives and rules indicated below.
Electromagnetic compatibility directive 2014/30/EU

 

Low voltage directive 2014/65/EU

 

Directive ROHS 2011/65/EU

 

Directive WEEE 2012/19/EU

Security rules EN-61010-1

Instrument   Fixed, Permanently connected

 

Pollution degree 1 and 2 (without condensation) 

 

Isolation  

Basic + Protective union

 

Category 

CAT-II

Electromagnetic compatibility rules EN-61326-1

EM environment

  

Industrial

Immunity levels

EN-61000-4-2  By contact ±4 KV 

Criteria B 

 

By air ±8 KV 

Criteria B

EN-61000-4-3      

Criteria A

EN-61000-4-4   On AC power lines: ±2 KV  

Criteria B 

 

On DC power lines: ±2 KV 

Criteria B 

 

On signal lines

 : ±1 KV 

Criteria B

EN-61000-4-5  Between AC power lines ±1 KV  

Criteria B 

 

Between AC power lines and earth ±2 KV

  Criteria B 

 

Between DC power lines ±1 KV  

Criteria B  

 

Between DC power lines and earth ±2 KV 

Criteria B  

 

Between signal lines and earth ±1 KV 

Criteria B 

EN-61000-4-6     

Criteria A

EN-61000-4-8  30 A/m at 50/60 Hz 

Criteria A

EN-61000-4-11 0 % 1 cycle 

Criteria A 

 

40 % 10 cycles 

Criteria A 

 

70 % 25 cycles 

Criteria B 

 

0 % 250 cycles 

Criteria B

Emission levels

CISPR 11 

Instrument Class A, Group 1 

Criteria A 

Barberà del Vallès July 2017

 

Xavier Juncà - Product Manager

According  to  directive  2012/19/EU,  electronic 

equipment must be recycled in a selective and 

controlled way at the end of its useful life.

Содержание B Series

Страница 1: ...wires and thermocouple types J K T E S R N C L and X Reading configurable in C or F configurable manual offset configurable compensation of the thermocouplecoldjunction breakprobedetectionand5configur...

Страница 2: ...resis manual unlocking see section 1 13 3 Display filters memory of maximum and minimum reading password protection 5 brightness levels 1 Identify the instrument format see section 1 4 2 Power and sig...

Страница 3: ...11 Password configuration 16 1 13 12 Default factory configuration 16 1 13 13 Firmware version 16 1 13 14 Brightness configuration 16 1 13 15 Access to the options configuration menu 16 1 14 Factory...

Страница 4: ...Power Option2 Option1 Remote keypad Signal Power Slot for option 2 Slot for option 1 Input signal terminal Remote keypad terminal C D E Cable glands B F G Panel cut out see Table 2 1 4 2 Format B44 S...

Страница 5: ...1 Size A 436 mm Size B 135 mm Size C 3 mm Size D 55 mm Size E 25 mm Table 5 Sizes B26 Cut out G 418 mm 1 Cut out F 117 mm 1 Table 6 Panel cut out B26 F G Panel cut out see Table 6 1 4 4 Format B46 C D...

Страница 6: ...s are independent and can be installed by accessing the internal circuits of the instrument and connecting the mod ule to the connection jumpers of the selected slot Each module is provided with a cab...

Страница 7: ...al 6 The connections label attached to the outside of the in strument has some free space left to write the color or local code for each cable 7 To comply with security regulation 61010 1 add to the p...

Страница 8: ...ilters steps 1 13 5 On Power Up yes 1 13 7 Alarms simple or double setpoint activation delays deactivation delays hysteresis inverted relays locked alarms 1 13 3 Memory maximum minimum 1 13 6 Password...

Страница 9: ...ge en F Offset thermal drift Span thermal drift includes offset thermal drift Pt100 RTD 800 200 C 0 2 C 1562 328 F 0 05 C 0 10 C Thermocouple J 1200 200 C 2 C 2192 328 F 0 05 C 0 20 C Thermocouple K 1...

Страница 10: ...y acts as an ENTER It enters into the menu option selected and when entering a numerical value it validates the num ber Key UP 5 press the UP 5 key to access the fast ac cess menu Inside the menu the...

Страница 11: ...epted from 100 to 100 counts of display at the Thermoc CJC t cJc parameter activate o de activate the automatic compensation of the thermocouple cold junction When working with real thermocouples comp...

Страница 12: ...delays Each alarm can configure independent activation and deactivation delays These delays affect the alarm as a whole and the delay will affect the front led and the as sociated relay Second setpoin...

Страница 13: ...pply before the alarm is activated Delay starts to count once the setpoint is reached Value from 0 0 to 99 9 seconds at the Deactivation delay dEL 1 parameter config ure the delay to apply before the...

Страница 14: ...t affected by the password func tion This means that the configuration menu can be password blocked while some configured functions or parameters can still be accessible to the operator through the fa...

Страница 15: ...fast access menu the Setpoint2 ALr2 function allows to visualize and modify the alarm2 setpoint through the fast access menu the Setpoint3 ALr3 function allows to visualize and modify the alarm3 setpo...

Страница 16: ...uments in the vicinity or to the darkness or clarity of your environment Minimum Brightness Maximum Standard The Version VEr menu informs about the firmware ver sion installed on the instrument Versio...

Страница 17: ...Alpha 385 Alarms 1 2 and 3 Active off disabled Type as maximum Setpoint 1000 Hysteresis 0 counts Activation delay 0 0 seconds Deactivation delay 0 0 seconds Setpoint 2 off Inverted relay off Locked a...

Страница 18: ...tpoint 2 Active Alarm type Activation delay Deactivation delay Pt100 RTD 2 wires Pt100 RTD 3 wires Thermocouple J Thermocouple K Thermocouple T Thermocouple E Thermocouple S Thermocouple R Thermocoupl...

Страница 19: ...n Power Up Delay Seconds Alarm 1 Alarm 2 Alarm 3 Password Firmwareversion Factory configuration Key LE Alarm unlock No function Option 1 Access to the optional module installed at slot1 Option 2 Acces...

Страница 20: ...ion see the IPB ac cessories at section 3 Side fixations Fixation screws Diameter 4 5mm 30mm between hole centers Figure 11 Hanging mount Diameter 4 5mm 30mm between hole centers Side fixations Fixati...

Страница 21: ...period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse ac cident or manipulation by non authorized personnel In case of malfunction get in contact with your local p...

Страница 22: ...35 Vdc Max current 50 mA Isolation 3500 Veff optoisolated Terminal plug in screw clamp pitch 5 08 mm Installation allowed at slot1 slot2 slot3 The T1 module provides 1 transistor output to install in...

Страница 23: ...on 1 6 on how to install output and control modules For more information http fema es docs 4326_SERIES B_OPTIONS_manual_i pdf 2 3 Module SSR The SSR module provides 1 output for SSR relay control to i...

Страница 24: ...output and control modules Protocol Modbus RTU Bus RS 485 up to 57 6 Kbps Isolation 1000 Vdc Terminal plug in screw clamp pitch 5 08 mm Installation allowed at slot1 slot2 slot3 The RTU module provid...

Страница 25: ...um Configuration is performed from the front keypad of the in strument by accessing the menu entries Opt 1 Opt 2 or Opt 3 according to the slot where the module is installed Modules S2 can be provided...

Страница 26: ...IPB accessories provide IP65 protection to the panel junction Includes 4 accessories for B24 formats JPG 3 3 IPB26 The IPB accessories provide IP65 protection to the panel junction Includes 6 accessor...

Страница 27: ...FEMA ELECTR NICA SERIES B Models Bxx T 27 3 6 Output cable 2 meters of cable output power remote keypad signal JPG...

Страница 28: ......

Отзывы: