Federal Signal Corporation SignalMaster 331105 SMC5 Скачать руководство пользователя страница 6

Installation and Programming Instructions

6

 Model 331105 SMC5 SignalMaster Controller

BATTERY EXPLOSION

To avoid a battery explosion, always disconnect the 

negative battery cable first and reconnect it last. Avoid causing a spark when 
connecting near or to the battery. The gases produced by a battery can cause a 
battery explosion that could result in vehicle damage and serious injury.

CONNECTING THE RED AND BLACK WIRES

To avoid damage and ensure 

proper operation, the red and black wires MUST be installed as shown in  
Figure 3 on page 7.

2.

  Connect the black ground wire to the lug as shown in Figure 3 on page 7. Securely tighten the binding 

screw using a 1/4" flat-tip screwdriver passing through the opening in the cover. 

3.

  Route the ground wire through the firewall and toward the battery. Connect it to a good frame ground 

near the battery. For gauge recommendations, see Table 4. In most vehicles a wire from the negative 
terminal of the battery is routed and attached to the screw at the body/frame at the fender. 

4.  Connect the red wire from the nine-conductor cable of the SignalMaster to the vehicle battery through a 

fuse holder that is located as close to the battery as possible. The fuse should be a 20 A to protect a single 
lightbar and 40 A if two lightbars are to be protected by a single fuse. 

Do not install the fuse until 

all other electrical connections have been made.

 To run between the fuses and each SignalMaster, 

use a properly-sized red wire. If a single conductor will be used to provide power to two SignalMaster 
lightbars, ensure that the wire is of the recommended gauge for the total load. For wire gauge 
recommendations, see Table 4 on page 5.

5.

  Select a termination point for the 18 AWG red power wire from the controller. As applicable, route 

the 18 AWG red wire toward the vehicle fuse block or through the firewall toward the battery. If the 
controller power is to be connected to the battery, use an installer-supplied in-line fuse in the 18 AWG 
red wire as close to the battery as possible and terminate it as required. If the red wire is to be terminated 
to the fuse block, and will be active only when powered by the ignition switch, select an appropriate 
fused circuit.

IMPORTANT:

 The termination point of the 18 AWG red wire from the controller determines when the 

directional signal can be activated. When the wire is attached to a vehicle fuse that is powered when the 
ignition switch is in the run or start position, the ignition switch must be in the run position to operate the 
directional signal. When the wire is attached to the vehicle battery, the directional signal can be operated 
at any time. To avoid draining the battery, Federal Signal recommends that the power wire from the 
controller be terminated to a switched source. 

NOTE:

 The controller draws 7 mA (0.007 A) in the off 

position when connected directly to the battery. 

6.

  See Figures 2 and 3 on page 7. Strip 1/4" of insulation from all wires that you plan to connect to the 

15-position terminal block of the controller. Make all of the required connections to the terminal block as 
described in the next section. 

7.

  Connect the 18 AWG red wire to the position labeled on the terminal block for +12

-

24 Vdc.

Содержание SignalMaster 331105 SMC5

Страница 1: ...activate light control while driving in a hazardous situation This product controls high intensity lighting devices To prevent eye damage DO NOT stare into the light beam at close range You should fre...

Страница 2: ...r a halogen lightbar The default pattern is the classic SMC warn pattern with the center lightheads alternating with the lightheads on each end The AUX function provides an installer selectable flash...

Страница 3: ...2 V SignalMaster at 24 V or a 24 V SignalMaster at 12 V or shortened lamp life will result Model 331105 Controller Specifications Electrical Input Voltage 11 Vdc to 28 Vdc Polarity Negative ground onl...

Страница 4: ...not mount the unit near a heater duct NOTE When selecting a mounting location for the control unit it is necessary to keep in mind that some SignalMaster models have cables which are 15 feet long Pla...

Страница 5: ...in an electrical fire The controller is equipped with a 15 position connector and two insulated spade connectors Also required are installer supplied red and black wires of the proper gauge for the c...

Страница 6: ...d to provide power to two SignalMaster lightbars ensure that the wire is of the recommended gauge for the total load For wire gauge recommendations see Table 4 on page 5 5 Select a termination point f...

Страница 7: ...cable to the locations specified in Figure 3 or on the label affixed to the controller housing Figure 3 Wiring from SignalMaster to controller 290A5486C RIGHT TURN SIGNAL INPUT LEFT TURN SIGNAL INPUT...

Страница 8: ...cted to a positive voltage source and protected with a fuse Figure 4 Connections for two four head SignalMasters to the controller BROWN FIVE CONDUCTOR CABLE FROM RIGHT SIGNALMASTER 20 A BAT JOIN THE...

Страница 9: ...the Turn Signal Override The controller can be connected so that a single end module flashes in sync with the vehicle turn signal If any pattern is displayed when the turn signals are flashing the pa...

Страница 10: ...nalMaster Controller on page 13 Figure 5 Model 331105 SMC5 controller 290A5488B FOUR POSITION SLIDE SWITCH AUXILLIARY HEAD LED INDICATORS SIGNALMASTER LED INDICATORS Table 5 Standard warn patterns Pat...

Страница 11: ...5 on page 10 Both buttons remain lit indicating that the controller is now in Programming Mode Select one or more of the following features before exiting Program Mode See Exiting Program Mode at the...

Страница 12: ...he slide switch to OFF Position 1 and then move it to the LEFT ARROW position Position 2 Exiting Program Mode To exit Programming Mode temporarily interrupt the power to the controller by turning off...

Страница 13: ...s a four position switch with OFF and settings for the directional patterns LEFT ARROW CENTER OUT and RIGHT ARROW OFF Position 1 Turns off the directional pattern LEFT ARROW Position 2 Displays a left...

Страница 14: ...nal circuit the controller stops any active pattern and flashes the appropriate end lamps in sequence with the turn signals or hazard lights No operator input is needed to activate this feature if con...

Страница 15: ...washer Ext Tooth 1 4 7075A007 2 Screw Hex Head 1 4 20 Taptite 7011164 08 Returning a Product to Federal Signal Before returning a product to Federal Signal call 800 264 3578 800 433 9132 or 800 824 02...

Страница 16: ...gnal Corporation SignalMaster is a registered trademark of Federal Signal Corp Write the RMA number down so that you can easily check on status of the returned equipment Send all material with the iss...

Отзывы: