FEDERAL PACIFIC PSE Скачать руководство пользователя страница 2

1075 Old Airport Road • Bristol, VA 24201   Phone (276) 669-4084 • FAX (276) 645-8206 • www.federalpacific.com • ISO9001:2015

SECTION IB-2B-800

INSPECTION & MAINTENANCE RECOMMENDATIONS

DEAD-FRONT PAD-MOUNTED SWITCHGEAR TYPE PSE

JUNE 2021, REV. 1.1

Page 2

Barriers, viewing windows and insulators can be cleaned with a non-

alcohol and non-solvent based cleaner that does not leave any residue 

when dry. Residue must be removed.

  3.  Exercising

    Yearly mechanical exercising of the switch is recommended. Refer to 

Instruction Bulletin Section IB-2A-210 for information on operating 

the switch.

Current carrying parts must be completely de-energized from all 

sources before any maintenance is performed on these parts. Follow 

normal system operating practices to de-energize, test for voltage 

and ground these parts before any work is performed.

  4.  Exercise Fuse Mountings

Open and close hinged fuse panels and insure proper latching 

as described on the label on the inside of the compartment door 

and in Instruction Bulletin Section IB-2A-210. Inspect fuse contact 

interfaces for damage and overheating, which will be evidenced 

by distortion or discoloration of the contacts. Note that contacts are 

copper and may be silver plated. There will be normal oxidation of 

these parts. Slight irregularities can be burnished with an emery 

cloth or paper.

  5.  Replacement Parts

   

If parts or labels are required they may be ordered by contacting Federal 

Pacific at 276-669-4084 or your local Federal Pacific Manufacturer's 

Representative. A directory of the representatives can be found at www.

federalpacific.com. If parts are ordered, the unit serial number and date 

of manufacture must be provided along with the part description.

  6.  Maintaining the Exterior

    The exterior finish can be maintained by periodic washing, touch up 

of any scratches and abrasions, and waxing.

    For areas to be touched-up, clean the area removing all rust. Apply a 

red-oxide primer, available in spray cans from a local paint supplier 

or home improvement store. Spray cans of the topcoat finish are 

available from Federal Pacific (specify the original color).

 7.   Verify Security Devices 

    Verify the operational integrity of security devices such as door 

latches, penta-head bolts, hinges and key-interlock systems. Make 

certain padlocks are properly installed on all doors and covers. 

  1.  Switch Operation

    Check switch for proper operation refer to Instruction Bulletin 

IB-2A-210. If the switch is closed on a short circuit within the fault 

closing rating and the short circuit is cleared by circuit breakers or 

fuses, the switch will not sustain damage which would require major 

repairs. However, the switch should be inspected before returning to 

service to determine switch condition. See Lubrication.

  2.  Cleanliness

    Check for cleanliness generally, but particularly for accumulation of 

any foreign material on insulators, barriers and viewing windows. 

The procedures required for operation of the Federal Pacific Auto-jet

®

 II 

Load-Interrupter Switches, the dead-break hinged fuse panels,  the doors, 

the barriers and other accessory components are covered in detail in the 

Federal Pacific Instruction Bulletin Section IB-2A-210. The inspection and 

maintenance recommendations covered in this bulletin are expected to 

be performed in conjunction with a review of IB-2A-210. This bulletin 

does not cover all the detailed and specific operational procedures and 

checks. In addition, these instructions are not intended as a substitute for 

the user’s standard operating practices and procedures. A copy of Instruc-

tion Bulletin Section IB-2A-210 can be printed from the internet at www.

federalpacific.com.  

 

When cleaning components, NEVER use any industrial strength cleaners. 

NEVER apply lubricants to the probe contact or the tulip contact which 

are the interrupting contacts. NEVER use any solvent-based or flammable 

products on any components in the pad-mounted switchgear. Solvents 

and flammable products can attack non-metallic components of the 

equipment and reduce electrical and mechanical properties.

Maintenance

Federal Pacific switchgear does not require routine mechanical or electri-

cal maintenance. However, the following are some recommendations for 

enhancing continued service of the equipment.

NOTICE

WARNING

WARNING

Before Opening the Switchgear

The following inspection and maintenance procedures must be 

performed with the current-carrying parts completely de-energized 

and isolated from voltage. Any attempt to perform the inspection and 

maintenance with the current-carrying parts energized may result in 

electrical arc flash that can cause equipment damage, personal injury 

or death.

DANGER

CAUTION

Do not put any lubricant on switch probe or puffer contacts. Refer to sec-

tion "10. Lubrication".

Отзывы: