SECTION IB-2D-700

INSTALLATION & OPERATION INSTRUCTIONS

PMDF PAD-MOUNTED SWITCHGEAR 

NOVEMBER 2017 VER. 2.1

PAGE 3

Introduction

PMDF pad-mounted switchgear is designed to provide depend-

able on-the-line service and to make installation, operation 

and maintenance as simple as possible. Federal Pacific PMDF 

models meet applicable industry standards, which are ANSI 386 

and IEEE C57.12.28.
High quality materials and careful workmanship have been com-

bined to provide the best switchgear available. The switchgear has 

been thoroughly inspected and adjusted at the factory. However, 

successful operation depends on proper installation and care.
This manual has been written to assist you in obtaining long and 

economical service from your switchgear.

Read this manual before installing and operating your switchgear .

Receiving

Upon receipt of the switchgear, check each item received for 

shipping damage. Each item should be checked against the ship-

ping manifest to assure that the proper number of items were 

received. Should any shortage or damage exist, note it on the 

shipping papers. A claim should be filed at once with the carrier 

and the Federal Pacific agent or sales office should be notified.

The carrier is responsible for all damage occurring during tran-

sit. Receiving personnel must note all damage to equipment on 

shipping papers so that claims can be processed.

Handling

Removable lifting plates are provided to allow the use of hooks to 

lift the complete enclosure. The lifting device should be arranged 

to evenly distribute the lifting force between the lifting plates.  

Do not lift at an angle less than 60° from the horizontal. See 

Figure 2. A spreader bar may be required to maintain the proper 

minimum angles. Failure to comply with this requirement may 

result in damage to the equipment.

The switchgear is securely mounted to a sturdy shipping pallet 

with provisions for forklift use. The use of a forklift truck is not 

recommended, but if this method is used the forks must extend 

completely through the skid to avoid damaging the equipment.

Storage

The switchgear as received may be wrapped in a protective 

plastic film, which must be removed for storage.      

To avoid damage to the enclosure finish, the protective film 

must be removed for outdoor storage of unit.

Export or special packing is available as an option based on 

customer’s requirements and special conditions. Separate in-

structions are available for these situations.

Figure 2.  Lifting Method

General Description

PMDF dead-front pad-mounted 

switchgear consists of one or more 

single-pole 200 ampere bushing 

wells to accommodate 200 ampere 

loadbreak (or non-loadbreak) in-

serts and elbows. Alternately, the 

unit may be optionally equipped 

with  600 ampere bushings to ac-

commodate 600 ampere elbow 

connectors. When used with 200 

ampere bushing wells and load-

break inserts and elbows, and 

other protective devices, the PMDF 

switchgear provides a secure and 

efficient means of single-pole 

switching with elbows on the in-

coming lines.
In addition, the unit may be furnished with metering transformers 

(voltage transformers and current transformers), or provisions 

only for metering transformers, and with optional meter socket 

(mounted on the enclosure or in a low-voltage compartment) 

and associated wiring. When the unit is provided with “Mount-

ing Provisions only for Metering Transformers, the customer is 

responsible for providing, installing, wiring, and connecting all 

metering transformer and associated secondary components.

Security Features

PMDF pad-mounted switchgear meets the security require-

ments in IEEE C57.12.28 and incorporates a number of security 

features to minimize hazards to operating personnel.
1.  Rugged 11-gauge steel, using all welded construction of the 

enclosure, with a bolted roof, and hinged and bolted doors 

assures a tamper-resistant design.

2. Padlockable doors with security bolts provide customer-

controlled access.

3.  200 ampere bushing wells of cycloaliphatic epoxy and with 

removable studs.

NOTICE

 

NOTICE

4. Hazard-alert signs and labels, both external and internal, 

indicate potential hazards to personnel.

5.  Full-width fiberglass barriers (or optional clear polycarbonate 

barriers) behind doors on fuse compartment.

6. Wind brace to secure enclosure door open and a cable-

connected clip to secure inner barriers open.

WARNING

Before energizing the switchgear, remove all yellow and red 

shipping caps on bushings and bushing wells, and replace 

them with a suitable system of insulated separable connectors 

(elbows), insulating protective covers, or plugs, as appropriate.
Failure to replace the shipping caps may result in flashover, 

equipment damage, serious personal injury, or death.

CAUTION

Содержание PMDF Series

Страница 1: ...utility performing and authorizing the work Completion of these instructions implies no further warranty by the manufacturer A Qualified Person is defined in the National Electrical Code NEC NFPA 70 as One who has skills and knowledge related to the construction and op eration of the electrical equipment and installations and has received safety training to recognize and avoid the hazards involved...

Страница 2: ...ent labels are available by contacting Federal Pacific SAFETY PRECAUTION FOLLOWING SAFETY INSTRUCTIONS NOTICE Thoroughly and carefully read this instruction bulletin before installation of the pad mounted switchgear before switching with elbows or installingoraccessingthemeteringtransformers in this equipment and before performing any maintenance on the equipment DANGER Federal Pacific Fuse Mounti...

Страница 3: ...nish the protective film must be removed for outdoor storage of unit Export or special packing is available as an option based on customer s requirements and special conditions Separate in structions are available for these situations Figure 2 Lifting Method General Description PMDF dead front pad mounted switchgearconsistsofoneormore single pole 200 ampere bushing wells to accommodate 200 ampere ...

Страница 4: ...plied between unit base and pad to prevent entry of foreign objects vegetation insects animals and moisture Figure 3 Typical pad layout and associated circuit diagram for one particular PMDF design DO NOT USE FOR CONSTRUCTION PURPOSES 2 Connect the concentric neutral wires to the enclosure ground padsinsidetheenclosuretofacilitategroundsystemconforming to user s grounding procedures The maximum mo...

Страница 5: ... requirements Bushing Wells The 200 ampere bushing wells accommodate 200 ampere elbow separableinsulated loadbreakconnectorsandaccessories The unitsareshippedwithayellowdustcoverovereachbushingwell topreventcontamination DustcoversareNOTcapableofprovid inganyelectricalinsulationatmediumvoltagelevels Therefore if an elbow is not to be connected to a bushing well prior to energization the dust cover...

Страница 6: ...reak Elbows 1 Removethepadlockandfullyloosenthepenta headbolt Pull and lower the door handle cover to open the active elbow compartmentdoorandsecurewiththewindbrace SeeFigures 7 through 14 2 Loosenthetwopentaheadboltsthatsecurethepassiveelbow compartment door and secure it open using the windbrace 3 System operating practices may allow loadbreak elbows to be switched while the associated cable is ...

Страница 7: ...lation of Metering Transformers 1 Removethepadlockandfullyloosenthepenta headbolt Pull and lower the door handle cover to open the active elbow compartmentdoorandsecurewiththewindbrace SeeFigures 7 through 14 2 Loosenthetwopentaheadboltsthatsecurethepassiveelbow compartment door and secure it open using the windbrace 3 Loosenthepenta headboltsoneachinnerbarrierandsecure them open using the pin pro...

Страница 8: ... 315 R6 200 15 95 54 54 51 22 28 14 14 7 NA NA 22 62 62 46 46 PMDF 315 L9 200 15 95 54 54 51 22 28 14 14 7 5 8 5 8 22 62 62 46 46 PMDF 325 R6 200 25 125 66 66 51 24 1 2 30 1 2 17 1 2 16 8 1 2 NA NA 24 74 74 58 58 PMDF 325 L9 200 25 125 66 66 51 24 1 2 30 1 2 17 1 2 16 8 1 2 6 8 3 8 24 74 74 58 58 PMDF 335 R6 200 35 150 76 66 53 24 1 2 33 22 1 2 18 5 16 12 9 16 5 5 8 8 1 2 24 74 84 68 58 34 5 kV de...

Страница 9: ...oor handle See Figures 8 through 10 Figure 13 Padlock cannot be inserted until penta head bolt is fully tightened Figure 14 Always close latch and padlock the enclosure door before leaving the unit or when working on the opposite side Figure 10 Door handle cover is secured closed by a penta head or hex head bolt Turn socket counter clockwise to loosen bolt Figure 9 Door handle is stainless steel F...

Страница 10: ...sformer compartment of the switchgear 2 Checkforcleanlinessgenerally butparticularlyforaccumula tionofanyforeignmaterialoninsulators barriersandmetering transformers Barriersandinsulatorscanbecleanedwithanon alcoholbased cleaner that does not leave any residue when dry Residue must be removed Optional Features Standard options can be supplied that best serve the customer s needs and operating prac...

Страница 11: ...l VA 24201 Phone 276 669 4084 FAX 276 669 1869 www federalpacific com ISO9001 2015 SECTION IB 2D 700 INSTALLATION OPERATION INSTRUCTIONS PMDF PAD MOUNTED SWITCHGEAR NOVEMBER 2017 VER 2 1 PAGE 11 This Page Intentionally Left Blank ...

Страница 12: ...PAD MOUNTED SWITCHGEAR NOVEMBER 2017 VER 2 1 PAGE 12 This Page Intentionally Left Blank Every effort is made to ensure that customers receive an up to date instruction manual on the use of Federal Pacific products however fromtimetotime modificationstoourproductsmaywithoutnoticemaketheinformationcontained herein subject to alteration 2014 Electro Mechanical Corporation ...

Отзывы: