Control Display 

The control display is located in the unit base. It is programmed to display the current 
discharge temperature from the control sensor located inside the center tower at the 
top. 
 

Maximum Run Timer, Before 5/23/12 Only  

The unit is equipped with a maximum run timer that is preset at the factory for 60 
minutes on and 10 minutes off. If the temperature control does not reach cut out set 
point after running for one hour, the timer will turn the compressor off for 10 minutes.  

 

 

REFRIGERATION  OPERATION 

 

Self Contained Models    
 

Refrigeration R404 Charge IMSS60 & IMSS84 

6 Pounds  

Refrigeration R404 Charge IMSS120 

8 Pounds  

 

The self-contained models are shipped from the factory with a completely operational 404A 
refrigeration system and require no modifications or adjustments upon installation. Case must be 
installed as per the installation section of this manual to provide proper condensing air cooling. 
 
 Self Contained Refrigeration Operation 
The unit temperature is controlled by the Electronic control and timers outlined in the control 
section of this manual. 
Note: The condenser fan runs continuously.  
 

 
Remote Models 
Use pressure gauges to set pressure control. 
 

Refrigeration R404 Charge 

CHARGED IN FIELD 

Remote Low Press. Switch Cut In 

50 psi 

Remote Low Press. Switch Cut Out 

15 psi 

Adjustable Head Master 

200 psi 

Remote High Press. Switch Cut Out 

400 psi 

 

The remote models are designed to use 404A refrigerant and shipped from the factory with the 
evaporator coil, expansion valve, sight glass and refrigerant solenoid valve. Drier filter most be 
installed in field for proper operation. Electronic control runs identical to the Self Contained 
models except the electronic control opens and closes a refrigeration solenoid valve located on 
the suction line instead of turning on and off a compressor. The solenoid valve closes and shuts 
off the refrigeration flow to the unit and initiates a pump down cycle. This will allow the remote 
low pressure switch to open and shut off remote compressor.  
The condensing unit and pressure controls are optionally supplied from the factory for remote 
location installation. The condensing unit must be mounted and wired by the installer. The high 

Содержание IMSS120 Series

Страница 1: ...MSS120 MODELS INSTALLATION OPERATIONS MANUAL KEEP THIS MANUAL FOR FUTURE REFERENCE Engineering and technical data are subject to change without notice FEDERAL INDUSTRIES P O Box 290 Belleville WI 5350...

Страница 2: ...COMPONENT LAYOUT IMSS120 11 CONDENSATE EVAPORATOR 12 CONDENSATE PUMP 12 SHELVES 13 14 OPERATING INSTRUCTIONS 15 USER CONTROLS 15 POWER SWITCH 15 LIGHT SWITCH 15 ELECTRONIC CONTROL 15 INITIAL START UP...

Страница 3: ...nts contain technical instructions are intended only for persons qualified to perform electrical work DANGER Improper or faulty hookup of electrical components in the case can result in severe injury...

Страница 4: ...occur if you ignore the message WARNING Severe injury or death can occur if you ignore the message CAUTION Minor injury or damage to your case can occur if you ignore the message NOTICE This is impor...

Страница 5: ...ons such as near cases with water misting or fogging devices Failure to locate this case as stated will reduce the performance of your Island display and will affect temperature of interior of case an...

Страница 6: ...rements of the case See the electrical data plate located on the rear exterior of the case for the proper circuit size for each case The cord is factory installed protruding from the corner of the cas...

Страница 7: ...proper drainage of defrost water to the condensate pump A wrench is included to aid in adjusting leg levelers Check the level of the case where the display overhangs the base Adjust the 4 outside leg...

Страница 8: ...er screws from top of panel The screws will stay on the panel even after they are detached from base 2 Tilt the top of the panel away from the base and pull up on panel to allow the side panel tabs to...

Страница 9: ...tay on the panel even after they are detached from base 2 Tilt the top of the panel away from the base and pull up on panel to allow the side panel tabs to pull out of the side panel slots 3 Set the p...

Страница 10: ...5 1 4 2 Base Component Layout Remote IMSS60 IMSS84 CONTROL PANEL LOCATION CONDENSATE PUMP REMOTE REFRIGERATION LINE ACCESS COVER LIGHT POWER SUPPLY QUANITY MAY DIFFER POWER CONNECTION BOX ELECTRICAL B...

Страница 11: ...Y WIRING DIAGRAM 120 41 40 41 4 3 3 0 3 0 4 3 Base Component Layout Remote IMSS60 IMSS84 REMOTE REFRIGERATION LINE ACCESS COVER 3 8 HIGH PRESS CONNECTION REFRIGERATION SHUT OFF SOLENOID VALVE SIGHT GL...

Страница 12: ...pacity is available a high wattage heater is used The heater turns off automatically when the water level in the pan drops Check that the float is positioned correctly and that the switch operates at...

Страница 13: ...lace the additional shelf brackets in the same height level on the opposite end of case The 2 short brackets must go on the short end and 2 long brackets must go on the long end The short bracket with...

Страница 14: ...the socket is not being used for a shelf light the cap must be plugged into socket to prevent contamination and moisture out of the socket 7 Plug in each shelf light by aligning the male pins on the...

Страница 15: ...e WARM setting is an Off position this position turns the refrigeration off and all indicator lights will also be off at this setting ON The control will be on from the warmest setting at 1 and the co...

Страница 16: ...ntire shelving area Determine desired shelving location before placing product in case Product must be removed to readjust shelf location Allow a minimum of 2 between top of product and bottom of shel...

Страница 17: ...ondenser coil will void condenser warranty This procedure is for Self Contained models The remote condenser coil must also be cleaned at same intervals 1 Disconnect power to the unit 2 On IMSS60 and I...

Страница 18: ...t electrical damage to the case NOTICE Shut off lights and power switches and remove all products from case Allow sufficient time for the unit to reach room temperature before proceeding with cleaning...

Страница 19: ...hazing and yellowing of material Note Detergents are not recommended and do not use abrasive cleaners or pads to prevent scratching of surfaces SHELVES 4 DISPLAY DECK FAN SHROUD FAN SHROUD FAN SHROUD...

Страница 20: ...sembly do not rinse or submerge fan motors 9 Clean the entire interior of the case using warm soapy water Wipe off all soapy water with a damp cloth and allow to dry DO NOT use solvents such as Aceton...

Страница 21: ...ocked evaporator coil Check that paper or foreign materials are not blocking evaporator If the evaporator coil is blocked due to excessive frost put into manual defrost Excessive frost can buildup ove...

Страница 22: ...ase has a receiver tank large enough to hold all the charge you maybe able to pump down the system when service is required If moisture or liquid is observed around or under a Federal Industries case...

Страница 23: ...tries case you should evacuate the refrigerant charge before shipment Federal Industries recommends that the charge be evacuated into a recovery system to prevent the possibility of HCFC s from being...

Страница 24: ...Phase Number of Wires 2 GND 2 GND AMPS VOLTS AMPS VOLTS Compressor 12 230 Condenser Fan QTY 2 5 ea 230 Evaporator Fan Motor QTY 6 0 15 ea 230 0 15 ea 230 Lights Power Supply 12v QTY 4 1 6 230 1 6 230...

Страница 25: ...unit Do not move or relocate this sensor The coil sensor is strapped to the evaporator coil This sensor location is critical for proper operation of the unit Do not move or relocate this sensor The t...

Страница 26: ...troller Operation Temperature Units Fahrenheit F 4 Defrost Termination Method Evaporator Sensor Evaporator Sensor SET POINTS 8 Cut In Warm 14 F 41 F 9 Cut Out Warm 4 F 28 F 10 Cut In Cold 2 F 41 F 11...

Страница 27: ...y the Electronic control and timers outlined in the control section of this manual Note The condenser fan runs continuously Remote Models Use pressure gauges to set pressure control Refrigeration R404...

Страница 28: ...used to flow through tubing while brazing refrigeration lines 4 Suction line must be insulated the entire length with Armaflex or equivalent Do not run liquid line inside insulation with suction line...

Страница 29: ...32 19446 Ribbon Cable display 32 19093 32 19093 32 19093 Probe Temp 32 19094 32 19094 32 19209 Timer Max Run Before 5 23 12 41 17324 41 17324 Condensate Pan Ass y After 9 13 40 19996 40 19996 40 1999...

Страница 30: ...3 R 12 B 22 G 24 G 25 B 17 B 16 R 15 R 14 Y 10 Y 9 R 2 B 1 R 4 B 3 R 20 L2 L1 N B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B POWER SUPPLY B R B...

Страница 31: ...Y 21 R 11 R 23 B 5 B 13 R 12 B 22 G 24 G 25 B 17 B 16 R 15 R 14 Y 10 Y 9 R 2 B 1 R 4 B 3 R 20 L2 L1 N B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B...

Страница 32: ...BL TOP LAMP B B R B BL TOP LAMP B TURN FULL CLOCK WISE 208 240V 60Hz 1PH Y 6 R 15 3 2 4 1 MAX RUN TIMER TURN FULL CLOCK WISE RIBBON CABLE G 26 1 2 3 4 5 6 7 8 9 10 11 RIB RIB TERM BLOCK TEMP PROBE PB...

Страница 33: ...D W WHITE Y YELLOW BL BLUE COLOR CODE BRW BRW BL BL B BL B BL B B B R B R JUMP R Y TURN FULL CLOCK WISE 208 240V 60Hz 1PH Y 6 R 15 3 2 4 1 MAX RUN TIMER TURN FULL CLOCK WISE RIBBON CABLE G 26 1 2 3 4...

Страница 34: ...0 R 2 B 1 R 4 B 3 L2 L1 N B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B POWER SUPPLY B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP...

Страница 35: ...G 24 G 25 B 17 B 16 R 15 R 14 Y 10 R 2 B 1 R 4 B 3 L2 L1 N B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B POWER SUPPLY B R B BL R BL SHELF LAMP...

Страница 36: ...G GREEN DEFROST PROBE IMSS120 SELF CONTAINED 91 19739 9 3 12 B BR G B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B BL B B R TOP LAMP B BL B L1...

Страница 37: ...B B B R B R B BL TOP LAMP B B R B BL TOP LAMP B B R B BL TOP LAMP B 208 240V 60Hz 1PH Y 6 R 15 RIBBON CABLE G 26 1 2 3 4 5 6 7 8 9 10 11 RIB RIB TERM BLOCK TEMP PROBE PB1 DEFROST PROBE PB2 POWER SWIT...

Страница 38: ...PLY BRW BL B R G GREEN B BLACK R RED W WHITE Y YELLOW BL BLUE COLOR CODE BRW BRW BL BL B BL B BL B B B R B R JUMP R Y 208 240V 60Hz 1PH Y 6 R 15 RIBBON CABLE G 26 1 2 3 4 5 6 7 8 9 10 11 RIB RIB TERM...

Страница 39: ...TE 91 19740 9 3 12 B BR G B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B BL B B R TOP LAMP B BL B L1 L2 N LIGHT SWITCH B R G BLK R R BLK Y R BL...

Отзывы: