52
Troubleshooting
The indoor fan motor is burned or breaks or
has the heat protector malfunction.
Replace the fan motor or the defective part.
The built-in heat protector of the motor breaks
frequently because the motor is
abnormal.
Replace the fan motor
Wrong connection
Make the correction connection based on the circuit
drawing.
The fan does not
run when it is set
to supply air.
The fan capacitor has open circuit or is dama-
ged.
Replace the fan capacitor of the same type and same
specification.
The outdoor fan motor is damaged.
Replace the fan motor
Wrong connection
Make the correct connection based on the circuit
drawing.
In the cooling and
heating mode, the
compressor runs,
but the outdoor
fan does not run.
The outdoor fan capacitor is damaged.
Replace the fan capacitor
Malfunction of compressor
Replace the compressor
Breakage of running capacitor of compressor
Replace the capacitor
The voltage is too low or too high.
Manostat is recommended.
Wrong wire connection
Connect the circuit diagram correctly
When cooling or
heating, outdoor
fan runs,compressor
doesn't run.
The protector itself has malfunction.
Use the multimeter to check whether the contact of
the compressor is on when it is not overheated. If it
is not on, then replace the protector
The refrigerant is not enough or is too much.
Adjust the volume of the refrigerant
The capillary is blocked and the temperature
rises.
Replace the capillary
The compressor does not run smoothly or is
stuck. The air discharge valve is damaged
Replace the compressor
The compressor is
too hot and leads to
the action of the
protector.
The protector itself has malfunction.
Replace the protector
The torque of the swing motor is not enough
wrong connection
The swing fan does
not run.
The controller is damaged
• •
IC2003 is
damaged, the swing relay can not close,
etc
• •
First, check whether the connection is wrong. If no,
replace the parts
Содержание GWH18MC-D3DNA1A/O
Страница 14: ...12 24K 60cm m c 0 6 m c 0 6 m c 0 0 2 Bolt Nut Wrench 370 920 1000 610 399 427 790 Constrction views ...
Страница 17: ...15 5 2 Printed Circuit Board TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 18: ...16 TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 34: ...38 8 Exploded Views and Parts List 230V 18K R410A Indoor Unit Exploded Views and Parts list ...
Страница 36: ...40 230V 24K R410A Indoor Unit Exploded Views and Parts list ...
Страница 38: ...44 Exploded Views and Parts list 230V 18K R410A Outdoor Unit ...
Страница 40: ...48 Exploded Views and Parts list 230V 24K R410A Outdoor Unit ...