Fedders C1018BBD Скачать руководство пользователя страница 5

1.

The installer SHALL check available power to make certain
it matches the unit (Name Plate Rating) and that constant
voltage can be maintained to the unit. Unsatisfactory
performance would otherwise result. The local power
company should be contacted on any problems or questions
concerning power supply.

2.

Install a line service disconnect switch within sight of the
condensing unit. The line voltage service wiring for the
condensing unit should include a fused disconnect switch.

3.

Use correct wire size and fuse size. To ensure that adequate
voltage will be available at the condensing unit, the line
voltage service wiring MUST be of adequate size. Minimum
recommended wire ampacities and maximum fuse sizes are
listed on the unit name plate.

4.

Two holes are provided in the control box.

a. One is for the connection of the line voltage conduit 

or cable. The hole is sized for 

3

/

4

" conduit.

b.  One is for low-voltage wiring. (Refer to the wiring 

diagram attached to electrical box cover for 
connection.)

5.

Be sure to ground the condensing unit by securing the
ground wire to the grounding lug inside the control box.

6.

Be sure to follow National Electrical Code and all local
codes.

ELECTRICAL HOOK-UP

WARNING:

ELECTRICAL

EQUIPMENT SHOULD BE

INSTALLED BY A QUALIFIED, LICENSED ELECTRICIAN.

IMPROPER ELECTRICAL

HOOK-UP

MAY

DAMAGE

EQUIPMENT, CAN CREATE A HAZARD, CAUSE PERSONAL

INJURY OR DEATH,  AND WILL VOID THE WARRANTY.

!

5

When replacing an existing system, it is mandatory that a liquid line filter dryer (if not provided with the condensing unit) and a suction line
filter, conforming to the dryer selection chart below, be installed in the new system if any of the original refrigerant-bearing components are
to be used in the new installation. This is to assure that any contaminants left in the original components will not harm the new system. If
any other evaporator coils other than those manufactured or approved by our company are used in the installation, THE CLAIMED
PERFORMANCE AND WARRANTY WILL BE VOID 
without written notification and approval of such coils by our company.

DRYER SELECTION CHART

(Alco, Parker Hanifin, Sporlan)

TONNAGE

LIQUID LINE

ALCO

SUCTION LINE FILTER

SPORLAN

FILTER DRYER

PARKER HANIFIN

2

053

35S5

SLD 8-5SV

C-165

2.5

053

35S5

SLD 8-5SV

C-305

3

083

45S6

SLD 13-6SV

C-306

3.5

163

45S6

SLD 13-6SV

C-306

4

163

45S6

SLD 13-6SV

C-307

5

165

45S7

SLD 13-7SV

C-307

Selection of dryers smaller than recommended will cause unsatisfactory pollution protection, excessive refrigerant charge and pressure drop.
High pressure drops will result in reduced system capacities, higher system operating cost and increased failure rate.

SPECIAL INSTRUCTIONS FOR REPLACEMENT APPLICATION

Содержание C1018BBD

Страница 1: ...REV 9 22 04 23 23 0418N 003 Installation Operation and Maintenance MODEL C10 C12 SERIES 1 5 THRU 5 TON Split System High Efficiency Air Conditioner...

Страница 2: ...is inspection is completed NOTES TO INSTALLER The words SHALL and MUST indicate a requirement which is essential to satisfactory and safe product performance The words SHOULD and MAY indicate a recomm...

Страница 3: ...vaporator Consider the following factors 1 The air inlet SHALL be located at least 12 from a wall or other obstruction for unrestricted air flow 2 The air outlet SHALL be located so as to direct disch...

Страница 4: ...sweat type copper connecting fittings COPPER SUCTION LIQUID LINES 1 Remove the valve core from the schrader port Wrap a wet rag around the copper stub Flux the joint and braze with silphos rod contai...

Страница 5: ...ED BY A QUALIFIED LICENSED ELECTRICIAN IMPROPER ELECTRICAL HOOK UP MAY DAMAGE EQUIPMENT CAN CREATE A HAZARD CAUSE PERSONAL INJURY OR DEATH AND WILL VOID THE WARRANTY 5 When replacing an existing syste...

Страница 6: ...occurs on the 12 F 6 7 C superheat line ADD CHARGE to obtain 12 F 6 7 C superheat INSTRUCTIONS 1 Measure suction pressure and determine evaporator refrigerant temperature on R 22 scale of low side gau...

Страница 7: ...1 115 C F LINE LIMIT DO NOT ADD CHARGE IF POINT FALLS BELOW THIS LINE Chart based on 350 to 400 CFM ton indoor airflow and 50 relative humidity use on systems that cool with fixed restrictor OUTDOOR T...

Страница 8: ...ARIATION FROM CHART FOR 3 8 AND 11 8 LINE SET CONDENSER MODEL NUMBER AIR HANDLER MODEL NUMBER COIL MODEL NUMBER Included with Air Handler Depending on match ups the indoor piston may need to be change...

Отзывы: