background image

IS-F-PRV-2

I N S T A L L A T I O N   I N S T R U C T I O N S

Installation Instructions

1.   The valve should be installed by a licensed contractor in accordance with local codes and ordi-

nances. This valve should be installed where it is accessible with sufficient clearance for cleaning, 

service, or adjustment.

2.   Before installing the valve, be sure that the pipe ends are reamed and threads are cut to size.
3.   Flush the lines to remove all loose scale, dirt and other foreign matter that can damage or clog the 

valve.

4.  Install the regulator with the arrow on the body pointing in the direction of the flow.
5.  Regulator may be installed vertically or horizontally (upright or inverted).
6.  Start Up — Open cold water supply then hot water supply. Inspect for leaks.

Note: 

 The valve should be inspected annually to assure maximum life and performance.

Note:

  PRV-2 — These valves are suitable for outdoors or pit installations.

Series PRV-2

Water Pressure Reducing Valves

Sizes: 

1

2

" - 2" (15 – 50mm)

 

Parallel installations are recommended  

where high flow or low flow demand is  

intermittent/occasional. They are also used  

for installations where service cannot  

be interrupted.

Typical Installation

Series Installation

Parallel Installation

Series installations are recommended where 

very high supply pressure must be reduced to  

a very low downstream pressure. Reducing  

the pressure in stages eliminates whistling  

and noise.

TO FIXTURES

BACKFLOW

PREVENTER

PRESSURE

REGULATOR

TO

 S

IL

C

O

C

K

WATER

METER

SUPPLY

PRESSURE GAUGE

( 2 PLACES )

SHUTOFF VALVE

( 2 PLACES )

TO FIXTURES

BACKFLOW

PREVENTER

PRESSURE

REGULATOR

( 2 PLACES )

TO

 S

IL

C

O

C

K

WATER
METER

SUPPLY

SHUTOFF VALVE

( 2 PLACES )

PRESSURE GAUGE

( 2 PLACES)

TO FIXTURES

WATER

METER

BACKFLOW

PREVENTER

PRESSURE

REGULATOR

( 2 PLACES )

TO

 S

IL

C

O

C

K

SUPPLY

SHUTOFF VALVE

( 6 PLACES )

PRESSURE GAUGE

( 2 PLACES )

PRV-2-U

1

2

" - 1" (15 - 25mm)

PRV-2-DU

1

1

4

" - 2" (32 - 50mm)