![FE PXR4 Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/fe/pxr4/pxr4_operation-manual_3756215050.webp)
50
[Description]
• By these parameters, the SV (Set value) are automati-
cally changed over time according to the patterns set in
advance as shown in the figure below. A maximum of 8
ramp-soak segments can be set in PXR.
• The first ramp starts from the PV (Measured value) just
before performing the program.
• The program can also be started at power-on automati-
cally (Power-on start function).
• A maximum of eight ramp-soak segments can be set. It
is also possible to set 4 ramp-soak segments twice in-
stead.
• When the following parameters are changed under ramp-
soak operation, operation will change the patterns of the
ramp-soak pattern is changed to the new setting.
•
to
•
to
•
to
•
[Parameters]
In order to execute these functions, it is necessary to set
the programs in advance. To set the programs, set the SV
(Setting value) and time desired for the parameters shown
in the table on next page.
Related parameters:
(page 49)
(page 18)
(page 54)
(page 54)
Ramp-soak status display (Display only)
to
1st to 8th target SV (Setting range:
to
) (Option)
to
1st to 8th ramp segment time (Setting range: 0 to 99h 59min) (Option)
to
1st to 8th soak segment time (Setting range: 0 to 99h 59min) (Option)
Ramp-soak modes (Setting range: 0 to 15) (Option)
SV
Time
SV-1
SV-2
SV-3
SV-4
SV-8
SV-5
SV-6
SV-7
4 ramp soaks (PTn=1)
4 ramp soaks (PTn=2)
8 ramp soaks (PTn=3)
TM1r
TM1S
TM2r
TM2S
TM3S
TM3r
TM4r
TM4S
1st
ramp
2nd
soak
3rd
soak
3rd
ramp
1st
soak
2nd
ramp
4th
ramp
4th
soak
Up to SV-8
Up to TM8S, TM8r