3 Installation
14
CN2 (RS-232C interface)
Pin
No.
Classification
of signal
Name of
signal
Content
2-3
“
Close
”
at operation
Input power
supply
abnormal signal
(*1)
It is the no-voltage contact signal which is
outputted when the abnormalities, such as
the power failure, occur at an input power
supply.
(In the power failure for 1.5 seconds or
less, it does not operate.)
1-3
“
Close
”
at operation
Battery voltage
drop signal
(*1)
It is the no-voltage contact signal which is
outputted approximately 2 minutes before
(at the rated load) the end of battery
discharge during the battery operation.
8-7
AC output stop
at
‘
H
’
signal
reception
UPS automatic
shutdown signal
(*2)
It is the signal which inputs into the UPS
when stopping the AC output of the UPS.
(1)
The stop of the AC output is possible
only during the battery operation.
(2)
Input this signal (5 to 25 VDC)
approximately 0.6 seconds or more.
6-7
Serial data
input (RX)
9-7
Serial data
output (TX)
7
RS-232C serial
signal
(*3)
Signal ground
(SG)
[Communication system]
Baud rate
: 2400 bps
Data length
: 8 bits
Stop bit
: 1 bit
Parity
: non
Character type
: ASCII
*1 Refer to the graph of the previous page for contact capacity.
When using the UPS monitoring function (using the above contact signal)
preinstalled in the following OS, contact your maintenance staff, since the dedicated
RS-232C cable for contact signal which corresponds to each OS is needed
separately. For more detail on the UPS monitoring function preinstalled in each OS,
refer to an instructions manual, an on-line manual, etc. of each OS.
Windows NT/2000/XP:FiFH/WS9 (RS-232C cable)
*2 In the case of Windows 2000 and XP, although the shutdown of OS can be
performed during the power failure, a subsequent UPS automatic shutdown cannot
be performed.
*3
When performing the RS-232C serial communication, contact your maintenance
staff, since the RS-232C cable is needed separately.
FiFA/WS9 (RS-232C cable)
1
2
5 4 3
6
9 8 7
D-sub 9 pins, female
(#4-40 inch screw)