![FCS Multilog2 Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/fcs/multilog2/multilog2_installation-and-setup_3724647042.webp)
39
MAN-147-0018-A
9. A
PPENDIX
2:
C
OMMUNICATING TO LOGGER VIA
SMS
Note: This facility was used mainly with loggers using the 2G and 3G network.
Loggers using 4G modems do not use this feature.
Some networks or service providers or SIM cards do not have SMS messaging
available.
Applying a
Figure 24) to the 10-pin Comms
interface for a period of 10 seconds
will activate the logger’s cellular
communications modem for a period of 5 minutes. This will allow an
installer to send SMS (text) messages from a mobile phone and for the
logger to respond.
(There is an alternative way to do this using IDT).
Close the chamber or cabinet such that everything is in its final position.
Using a standard mobile phone, send a text message to the SMS number of
the logger (check the logger label), including the international dialling code if
needed.
•
The text message should read
TTTT#
After a few seconds/minutes (depending on the network operator) the logger will send a
message back to you with details of its current status.
•
Example response from a logger:
TTTT138-002 V01.70CSQ:1010.9VyouridRT hh:mm ss dd-mm-
yy …
To decipher the message returned, please refer to the table below:
Message
Description
TTTT
Original command text without #
138-002
Logger type number
V01.00
Firmware version in Logger.
CSQ: nn
Signal strength nn (nn = 6 to 30)
10.9V
Operating voltage
yourid
Your Logger ID
RT hh:mm ss dd-mm-yy
Real Time Clock setting
ST hh:mm ss dd-mm-yy
First Time the logger was started
LR hh:mm ss dd-mm-yy
Last Time the logger was re-started
Ch1 (A) 0029.0
Channel 1 29.0 units
Ch2 (A) 0002.2
Channel 2 2.2 pulses/sec
If the CSQ: value in the message is OK, then the installation is complete. The logger will
automatically go back to sleep after 10 minutes.
Figure 24.
Multilog Modem
Activation Key