Connecting Batteries to the Charger
Installing the Charger
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572
7
Connecting Four Batteries
Figure 6 shows how to connect four 55 AH batteries to the
charger:
Figure 6 Connecting Four Batteries to a Charger
Table 4 contains instructions for connecting four batteries to the charger:
Warning:
Do not
connect the
Battery
Interconnect Cable
at this time.
Refer to “Starting the
Charger” on page 15.
!
Charger
Power Supply
TB2
TB1
Step Action
1
Remove all power sources to the charger.
2
Tie the batteries in pairs by connecting the battery negative terminals and the
battery positive terminals as shown in Figure 6.
3
Connect the battery negative cable to the TB2 terminal (on the charger labeled
“Battery –”) as shown in Figure 6.
4
Connect the battery positive cable to the TB2 terminal (on the charger) labeled
“B”) as shown in Figure 6.
5
Proceed to the section “Connecting the Charger.”
Do not connect the Battery
Interconnect Cable at this time
—refer to “Starting the Charger” on page 15.
Table 4 Connecting 55 AH Batteries