background image

DESCRIPTION

The FCI 301PL series low profile photoelectronic smoke

detector is specifically designed to meet the performance re-
quirements of fire detection/alarm systems. The 301PL de-
tector uses a state-of-the-art optical sensing chamber and is
designed so that LED failure will not cause an alarm. The de-
tector is designed to provide open area detection, and when
installed in a two-wire base, is compatible with FCI fire
alarm control panels. The detector’s operation and sensitivity
can be tested in place.

The 301PL detector is of plug-in construction and plugs

into the same base as the FCI 301IL series ionization smoke
detectors, making both models interchangeable. Bases are
available for two-wire, four-wire, and 120 VAC four-wire op-
eration, and also with an audible sounder.

Two visible LEDs on each detector flash every ten seconds

indicating that power is being applied to the detector. The
LEDs light steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.

The 301PL is UL Listed for mounting inside ducts up to a

velocity of 3,000 FPM.

Functional testing is performed by placing a test magnet

against the cover. The LED on the detector should light
within 30 seconds.

Field metering of detector sensitivity may be performed

with the aid of a voltmeter and Test Kit, Part No. 119-9010N.

APPROVALS

UL (Std 268)

S 1913

FM

0X5A5.AY

CSFM

Approved

TECHNICAL SPECIFICATIONS

Sensitivity

3.0 %/ft. (nominal)

Operating voltage

8.5 - 35 VDC (24 VDC nominal)

Standby current

120 uA maximum

Operating temperature

32

o

to 120

o

F (0

o

to 49

o

C)

Operating humidity

10 % - 93 % relative humidity

Air velocity

3,000 feet per minute maximum

Construction

Off-white flame retardant plastic

Diameter

6.2 inches (15.5 cm) (flanged base)

Height

1.7 inches (4.2 cm)

Weight

3.6 oz. (104 g)

301PL SERIES

LOW PROFILE, PHOTOELECTRONIC

PLUG-IN SMOKE DETECTOR

9020-0375/Ver. 1.4

301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132

FEATURES

Low Profile Construction

Easy Plug-in of the Head to Base

Tamper-resistant Feature

Test Switch

360

o

View Angle of Alarm LEDs

Compatible with FCI Control Panels

Audible Sounder Base (Optional)

Field Metering of Detector Sensitivity

Removable Insect Screen and Cover

for Field Cleaning

Insect-resistant Screening (.020"/.508

mm Openings)

Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.

© 1997 All Rights Reserved

Отзывы: