MX
-500
Dual
Technology
Motion
Sensor
Installation
Instructions
T
T
Step 1
Separate the sensor housings and remove
Printed Circuit Board (PCB).
Use a small screwdriver to unfasten the hous-
ing latch and separate the sensor housings.
Push outward on the PCB latch to lift the PCB
out of the housing.
Step 3
Wire the sensor.
Observing the proper polarity, wire the unit as
shown in the illustration below, use 1.02 to 0.64 mm
(18 to 22 AWG) wire.
Step 2
Mount the sensor.
Break out the mounting/wiring knockouts and
mount the sensor in an appropriate location.
An ideal location meets the following objectives:
•
Allows a clear line-of-sight to all areas to
protect.
•
Does not directly face windows.
•
Avoids close proximity to moving machinery,
fluorescent lights, and heating/cooling
sources.
NOTE:
maximum range is obtained at a
mounting height of 2.3 m (76).
Knockout
Housing
latch
PCB latch
FRONT HOUSING
REAR HOUSING AND PCB
Terminal Block
TB1
PCB
LED
(DS1)
LED Enable
(Cut LED enable
jumper J1 to
disable LED)*
Step 4
Walk-test the sensor.
After returning the PCB to the rear housing,
reassemble the sensor housing. Apply
power to the sensor and begin walk-test
when the red LED is off.
Walk across the detection area at the ranges
to be covered. The red LED should indicate
an alarm condition after 2 to 4 normal steps.
When there is no motion in the detection
area the LED should be off.
Terminal Block
TB2
Alarm
500 mA
30 VDC
Power
25 mA
7.5-16 VDC
(UL: 8.9-14.5 VDC)
TB1
Tamper
50 mA
24 VDC
TB2
* R