background image

140903 FBs-CMGSM User's Manual EN v3-04 

Page #

1 of 7

 

FBs-CMGSM 

User’s Manual 

1.

 

Introduction 

FBs-CMGSM 

(

CMGSM

 for short) is communication module for FATEK PLC systems 

FBs-xxMC. 

CMGSM

 uses the GSM network to transfer the data. 

CMGSM 

is based 

on the quad band GSM module 

(850/900/1800/1900 MHz).  CMGSM 

is backed 

up by Li-Ion accumulator.  
CMGSM offer three different ways of communication with connected PLC. 

The first one is 

monitoring and remote control of PLC via SMS. CMGSM

 reads 

periodically PLC registers containing a flag to send SMS, if the flag is set, 

CMGSM

 

reads  destination  phone  number  and  string  of  characters  (text),  sends  SMS  and 
clears the flag. If there is a SMS received by CMGSM, it is written into PLC registers 

including another flag “SMS received” to be processed by PLC program. At the end 

the PLC program clears this  flag.  So these operational  SMS must be processed by 
PLC program both on SMS reception and SMS sending. Some status and event SMS 

are predefined in CMGSM (e.g. “Connection to PLC failure”) and only the destination 
phone number have to be set in PLC registers. 

 

The second way of communication with PLC via CMGSM is 

dial  up  data  transfer 

via  GSM  network  (CSD). 

The connection can be only incoming for CMGSM, that 

may  be  initiated  from  a  control  center  for  the  purpose  of  remote  system  analysis 

and PLC software tuning and modification by WinProladder SW. 
The  third  way  of  CMGSM  communication  over  the  GSM  network  is 

GPRS  data 

connection

  using  TCP/IP  protocol.    CMGSM  opens  the  connection  in

  TCP  client 

mode. 

Any SIM card, that can provide internet connection over the GSM network, 

can be used.  CMGSM connects to IP  address  and port specified  in from PLC. It is 

important to notice, that the connection can be opened in direction from CMGSM to 
PC (server) only. PC cannot open a connection to CMGSM because CMGSM has no 

server implemented and usually does not have public IP address. GPRS has special 

data transfer properties (data grouping, data transfer delay 1 ... 10 seconds), which 
are  not  suitable  for  WinProladder  SW. 

WinProladder  must  use  dial  up  data 

transfer (so called CSD) only.

   

 
 
Main features 

 

Three  ways  of  GSM  network  use  –  SMS,  GPRS,  Data  Call  CSD  (all  of 

them practically at the same time)

 

 

WinProladder remote GSM dial up data transfer connection (CSD)

 

 

USB port for module monitoring 

 

One digital input IN and one digital output OUT 

 

Firmware update via GSM available 

 

Li-Ion backup accumulator – min. 2 days of operation w/o charging

 

 

Lowest level super watchdog function (Hardware Power OFF)

 

 

FBs-CMGSM can be used directly with PLC FBs-xxMC (Port 3) 

 

SMS functionality is fully under PLC program control

 

 

Configuration of CMGSM means just to set several PLC registers

 

 

No PLC program support is necessary for CSD and GPRS operation 

 

 

LEDs for indication of the CMGSM status and data flow signalization 

 

 

Unlimited  number  of    logical  and  analog  inputs  and  outputs  can  work 

with one CMGSM (PLC network)

 

 

 

 

1)

 

GSM antenna connector 

2)

 

IO connector 

3)

 

SIM card holder  

4)

 

USB connector  

5)

 

DIN rail holder 

6)

 

FUNC button 

7)

 

Indication LEDs Rx, Tx 

8)

 

Flat cable for connection to PLC 

9)

 

Indication LEDs GSM, ERR 

 
 

2.

 

Content of the 

Delivery 

 

1 pc of 

FBS-CMGSM

  

 

1 pc of antenna GSM-ANT05S 

 

1 pc of 6 pin connector, pitch 3.81 mm 

 

1 pc of CD with documentation 

 
 
 
 
 
 

3.

 

Typical Application, Installation 

FATEK PLC

CMGSM

Power  + 5 V

DC

GSM

Antenna

RS 232  Communication

Flat cable

 

Note:  FATEK PLC is not part of the delivery of this  product. It is needed  to order 

independently. 
 

 

Warning 

Turn  off  all  power  supply  during  installation  of 

CMGSM

  to  PLC  to 

prevent damage to equipment! 

 

 

3.1

 

Configuration 

If a SIM card does not need PIN code, no configuration for basic use is necessary. 
For the SIM card with PIN code the configuration in PLC is necessary. Read chapter 

5.1 

Configuration

 for more.  

 
 

3.2

 

Hardware settings 

 

Switch off the power supply of PLC 

 

Connect GSM antenna 

 

Insert SIM card 

 

Connect the flat cable between CMGSM and PLC 

 
 

3.3

 

Startup 

Device  status  is  indicated  with  blue  GSM  LED  on  the  CMGSM  front  panel.  Valid 

statuses are as follows: 

Term 

Description 

permanently off 

No power or STAND BY mode. 

600 ms on / 

600 ms off 

Device is not logged into the GSM network. 
This state occurs after start of device for approx. 30 seconds. 
If it remains, check: SIM card (is inserted?, is valid?) 
Antenna (is connected?)  

Configuration (is SIM PIN correct?) 

75 ms on / 
3 s off 

Device is logged into the GSM network and is idle. (It means 
that no GPRS nor CSD connection is active.) 

75 ms on / 
75 ms off / 

75 ms on / 

3 s off 

GPRS active, no data 

500 ms on / 

50 ms off 

GPRS active, data transfer in progress 

permanently on 

CSD (data connection) in progress 

Expressed line is common operating state. 
 

 

3.4

 

Front Panel 

 
 

Name 

Element 

Description 

ANT 

Connector 

GSM Antenna connector 

GSM 

LED blue 

GSM status  

(see the previous table) 

ERR 

LED red 

Error 

IO 

Connector 

IN (input), OUT (output)  

FUNC 

Button 

Multifunction Button: 

DOUT2  change,  RESTART, 
STAND BY mode. 

SIM 
CARD 

SIM card 
Holder 

Press  the  SIM  card  to 
remove it from holder 

USB 

Connector 

USB  connection  to  PC  for 
debugging purposes 

RCV 

LED yellow 

Receiving SMS 

SND 

LED green 

Sending SMS 

3.4.1

 

Pushbutton “FUNC” 

Pushbutton  “

FUNC

”  has  several  functions.  Short  press 

changes the state of the output OUT (DOUT2). Long press (longer than 3 seconds) 

will  either 

RESTART

  CMGSM  (if  CMGSM  is  powered  by  the  PLC)  or  enter  the 

STAND BY MODE

 (if the CMGSM is powered from the internal accumulator - PLC is 

either disconnected or turned off). 

 

5

9

2

4

6

7

8

3

1

FBs-CMGSM

USB

COMMUNICATION

GSM MODULE

1

1

FUNC

RCV

SND

GSM

+

ERR

-

IN

OUT

SIM

PLC1.ir

Содержание FBs-CMGSM

Страница 1: ...just to set several PLC registers No PLC program support is necessary for CSD and GPRS operation LEDs for indication of the CMGSM status and data flow signalization Unlimited number of logical and analog inputs and outputs can work with one CMGSM PLC network 1 GSM antenna connector 2 IO connector 3 SIM card holder 4 USB connector 5 DIN rail holder 6 FUNC button 7 Indication LEDs Rx Tx 8 Flat cable...

Страница 2: ...800 SendFlag 0x0000 Idle 0x0001 Command to send written by program in PLC 0x0003 SMS is sending written by CMGSM 0x0000 SMS sent successfully written by CMGSM 0x0004 Failed while sending SMS written by CMGSM D3810 D3819 SendDestAddress Phone number where to send the message Length 20 characters D3820 D3899 SendUserData Text of the message Length 160 characters This range of registers cannot be use...

Страница 3: ...respond with confirmation SMS and restart itself PLC is not affected This command is used after change of configuration in PLC register to accept the changes by CMGSM CONFIG Device will respond with current configuration Current configuration is a default configuration with some values changed by configuration string in PLC see Chapter 5 Configuration FACTORY CMGSM will respond with confirmation S...

Страница 4: ...running without restart so called Uptime D3510 D3529 Gprs Reserved for GPRS diagnostics See chapter TCP over GPRS for details D3530 D3539 DiagOperator String with name of operator when registered Empty string if not registered Length 20 characters D3540 D3549 DiagCredit Reserved D3550 D3699 DiagAtCmd Sending AT commands to modem directly Write a command to this place and set D3506 DiagAtFlag to 0x...

Страница 5: ...re shown in table below Unknown keys are ignored no spaces are allowed inside keys or values Order of pairs is not important Keys are not case sensitive values are case sensitive Maximum length of configuration string is 200 characters At the end of each part MUST be character semicolon after last pair MAY be character semicolon and MUST be character dollar 5 2 Basic parameters Key Description Def...

Страница 6: ...ct your LAN against an attack from Internet Port It is a number of a service in your computer Complete address needed to connect your computer is composed from IP address and Port number and may be seen as 11 22 33 44 5700 IP ADDRESS PORT 7 2 Simple Use We recommend this scenario for your first step with CMGSM Internet Firewall Your computer in LAN of your company GSM Network LAN FBs CMGSM FATEK P...

Страница 7: ...998877 because CMGSM reads the configuration until the first character 10 Warranty General warranty period is 12 months after purchase when eventual malfunction device will be repaired free of charge in SEA company while shipping to SEA is paid by customer and SEA pays for shipping back to customer For SW there is 24 months warranty under following conditions Both CPU and PC software is sold as is...

Отзывы: