18
➢
Remote Port:
Port of the module that the remote PLC belongs to.
➢
Group Size:
When the Group mode is set to Consecutive Station No., this setting
can define a group of station number to compare at a time. For example, if you
want to set the local station number 10~19 to correspond to the remote station
number 20~29 and the remote IP is 192.168.1.3, you can set Local Station=10,
Remote Station=20, Group Size=10, Remote IP=192.168.1.3 1.3, Remote Port is
generally 500. Up to 18 group mapping can be set inside the Ethernet interface
conversion module. When the Group mode is set to Consecutive IP No., this
setting can define a group of IP mapping to compare at a time.
3.1.6 Service Ports
When the CBES expansion board is operating under TCP or UDP server mode, the
external service ports must be set so that the external client work stations can send
service requests according to the set port numbers.
The default FATEK communication service protocol is 500, Modbus communication
service port is 502.
Each service can provide up to 2 service port numbers at the same time, which are