-37-
Figure 9-8. Example of User Calibration When Output Range is 0~5 [V]
Low and High Values for each output range are listed in the
Table 9-3
.
Output Range
Low Value
High Value
0~5 [V]
-1,250~1,250
23,750~26,250
1~5 [V]
-1,250~1,250
23,750~26,250
0~10 [V]
-1,250~1,250
23,750~26,250
-10~10 [V]
-26,250~-23,750
23,750~26,250
0~20 [mA]
0~1,250
23,750~26,250
4~20 [mA]
-1,250~1,250
23,750~26,250
Table 9-3. Low and High Values for Each Output Range
User Calibration Method
9.4.3
Perform the user calibration of output deviation according to the following procedure.
1.
Set the Low Value and High Value to the default values.
-
Analogue Output Calibration Low Value (2302h): Sets Low Value to the default value
-
Analogue Output Calibration High Value (2302h): Sets High Value to the default value
-
Refer to the following table for the default values of Low Value and High Value for each Output
Range.
Output Range
Default Low Value
Default High Value
0~5 [V]
0
25,000
1~5 [V]
0
25,000
0~10 [V]
0
25,000
-10~10 [V]
-25,000
25,000
0~20 [mA]
0
25,000
4~20 [mA]
0
25,000
Table 9-4. Default Low and High Values for Each Output Range
2.
Adjust the Write Analogue Output 16bit (6411h) value to output the Low End value. Record the digital
data when it reaches the Low End output.
Digital Data
Voltage
5 V
25000
0
-0.2
V
5.2 V
-1000
Before Calibration
After Calibration
24000
Содержание Ezi-IO EtherCAT DA
Страница 1: ...User Manual ...
Страница 9: ... 9 Configuration Chapter 2 2 1 Ezi IO EtherCAT DA Part Numbering 2 2 Ezi IO EtherCAT DA Part Number ...
Страница 10: ... 10 2 3 System Configuration ...
Страница 13: ... 13 3 3 Module Dimensions Unit mm Can be installed on 35mm DIN Rail Can be installed on 35mm DIN Rail ...
Страница 14: ... 14 Connection Panel View Chapter 4 4 1 Names and Functions Ezi IO EC DA04 T ...
Страница 20: ... 20 5 2 Internal Circuit Diagram Figure 5 4 Internal Circuit Diagram ...