Faradite FAR-M360-*-VOLF Series Скачать руководство пользователя страница 2

Directive 2014/30/EU (Electromagnetic Compatibility (EMC))

Directive 2012/19/EU (WEEE)

Directive 2011/65/EU (RoHS)

Harmonised standards: EN 61000-6-1 Immunity for residential, commercial and light-industrial environments 

& EN 61000-6-3 Emission standard for residential, commercial and light-industrial environments

INSTALLATION

To install the Faradite Motion 

Sensor 360 - Volt Free, cut a 35mm 

hole using a suitable hole saw. Fold 

the spring clips upwards and push 

through the hole. If you are using 

the optional Fire IDR to achieve a 

60 minute fire rating to BS 476: Part 

21 1987, then a 40mm hole will be 

required.

USE A 35mm 

HOLE SAW FOR 

INSTALLATION

For further support & datasheets in other languages  

 please visit: faradite.com

CONNECTION TO LOXONE

Connection to Loxone is simple: connect 

one side of the relay to a digital input on the 

MiniServer / Extension / Nano DI Tree / Nano 

IO Air and the other side to 24V. Simply provide 

the 24V supply from the power supply in the 

cabinet or the 24V output of a Nano IO Air if 

retrofitting. 

MOUNTING & SAFETY 

PRECAUTIONS

1) Do not under any circumstance 

use these sensors outside the range 

of their ratings shown in the technical 

data.

2) Faradite is committed to making 

products of the highest quality and 

reliability. Nevertheless, all electrical 

components are subject to natural 

deterioration, and the product 

durability will depend on the 

operating environment and 

conditions of use.

3) Please note that the sensor can 

detect heat sources other than the 

human body, such as:

a) Small animals 

b) Direct sun light, incandescent 

lamps, car headlights (even if the heat 

source is outside the detection area)

c) Sudden temperature change inside 

or around the detection area i.e. hot 

or cold winds/drafts or vapour from a 

humidifier can affect the 

performance of the sensor

4) Please note that the sensor will 

have difficulty sensing the heat 

source if it is behind glass, acrylic or 

similar materials, as these materials 

may not allow a correct transmission 

of infrared rays

CONNECTION TO CONTROL4

Connection to Control4 is simple: connect one 

side of the relay to the “SIGNAL” input on a contact 

closure and the other side of the relay to the 12V 

power supply. Simply provide the sensor power 

using the +12V and GND outputs of the contact 

closure or any other 5V-24V supply. When using a 

contact closure the generic motion sensor driver can be used. You might 

need to tick the invert tickbox depending on what contact closure you have 

connected the sensor to as the sensor is “normally open”. 

Janus Technology have written a driver that integrates the Faradite Motion 

Sensor 360 - Volt Free with Control4, via a Brainboxes’ I/O device as an 

alternative to a contact input. Search for “Faradite Janus Technology driver” 

for more info.

CONNECTION TO CRESTRON

Connection to Crestron is simple: connect one 

side of the relay to a digital input and the other 

side to GND (G) and configure the input as a 

dry contact. The sensor can be powered using 

any available 5-24V supply.

INSTALLATION GUIDE FOR VARIOUS CONTROLLERS

THE SENSOR CAN ALSO BE USED WITH MANY OTHER SYSTEMS THAT HAVE A VOLT FREE / DRY CONTACT INTERFACE 

-

 

GND

VF RELAY 

+ 12V DC

VF RELAY

-

 

GND

VF RELAY 

+ 5V-24V DC

VF RELAY

5V-24V POWER SUPPLY

-

 

GND

VF RELAY 

+ 24V DC

VF RELAY

CONNECTION TO LUTRON

Connection to Lutron is simple: One side 

of the relay should be connected to the  

“INPUT” of a contact closure input (CCI) and 

the other side should be connected to the 

“COMMON” of the CCI. Any 5-24V power 

supply can be used to power the sensor.

-

 

GND

VF RELAY 

+ 5V-24V DC

VF RELAY

5V-24V POWER SUPPLY

SENSITIVITY ADJUSTMENT

The sensor has been designed for optimal sensitivity. 

It is not recommended to change the sensitivity 

setting unless it is found to be necessary. To adjust 

the sensitivity, remove the two screws and turn over 

the circuit board. The small potentiometer can be 

used to adjust the sensitivity.

Отзывы: