15073 OWNER’S MANUAL
447179 Issue 1 Rev. A
13
2.5.5
Auxiliary Power Supply Output
Figure 2-8. Auxiliary Power Supply Output Connection
2.5.6
Trouble Relay
The 15073 board has a Form C trouble relay built into terminals 7-9 of TB2. The trouble relay will de-
energize under a trouble condition.
A typical application of the trouble relay is to connect the 15073 normally closed (N.C.) contacts in series
with an EOL of a spare IDC or NAC or monitor input from a fire alarm control unit. This will cause a
trouble on the fire alarm control unit when the 15073 opens its trouble contacts.
Note:
The N.C. contact is the relay contact that is closed when the 15073 has power and there are no
trouble conditions.
Figure 2-9. Trouble Relay Connection Example
6 7 8 9
2
1
3
Input 1
5
4
Input 2
12
Trouble
Relay
NAC
10
11
+
-
N.O.
COM
N.C.
IDC EOL
INITIATING CIRCUIT
CONTROL UNIT
IDC
CONNECTION
(SEE CONTROL UNIT
INSTALLATION INSTRUCTIONS)
UNSUPERVISED
LIMITED SOURCE
RESISTIVE FOR POWER
5A @ 30VDC/VAC,
STANDBY CONDITION)
(SHOWN IN NORMAL
RELAY CONTACT
TROUBLE
UNSUPERVISED, POWER LIMITED
3A MAX. @ 24VDC NOMINAL
AUXILLIARY POWER OUTPUT
firealarmresources.com
Содержание 15073
Страница 3: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A ii This page is intentionally blank firealarmresources com...
Страница 7: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A vi This page is intentionally blank firealarmresources com...
Страница 11: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A 4 This page is intentionally blank firealarmresources com...
Страница 21: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A 14 This page is intentionally blank firealarmresources com...
Страница 35: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A 28 This page is intentionally blank firealarmresources com...