background image

Example 2:

Valve pin position

Connect the 

BLUE 

wire to the Neutral.

Connect the 

BLACK

 wire to terminal 

9

.

Connect the 

BROWN

 wire to terminal 

6

.

Fluid

HOT

Fluid

COLD

Fluid

MIXED

Probe Installation

Flow T probe 

The flow T probe is supplied complete with accessories to match different kinds 

of installation:

• 

Kit for the installation direct on the pipeline

• 

1/2” seat

• 

M1”x1/2” reduced plug

7

Using the kit for contact assembly located in the box with the control unit, place 

the probe directly in contact with the supply pipe and secure it with the cable tie.

CONTACT INSTALLATION

1/2 “ Tee fitting 

NOT PROVIDED

1” Tee fitting

NOT PROVIDED

Insert the probe in the 1/2” seat and place it in a suitable Tee fitting with 1/2” 

female connection (NOT SUPPLIED) on the supply pipe.

INSTALLATION WITH 1/2” TEE FITTING 

INSTALLATION WITH 1” TEE FITTING 

Insert the probe in the 1/2” seat. Then screw  the seat of the reduction cap and 

introduce it into a suitable tee fitting with 1” female connection (NOT SUPPLIED) 

on the supply pipe.

www.far-moscow.ru  Москва, ул. Народного Ополчения, д. 34, стр. 3  (499) 519-03-69 

Содержание 9611

Страница 1: ...s that the function is active MAIN SELECTOR Switched off regulation anti freeze only Not provided With external probe nominal room T Fixed point not provided Automatic function Manual operation test B...

Страница 2: ...n connected it is essential to make a jumper between terminals 15 and 16 It is always necessary to create a jumper between terminals 2 and 3 and also between terminals 3 and 10 ROOM THERMOSTAT EXTERNA...

Страница 3: ...rews again and check keep separate the cables of sensors and digital inputs from the inductive and power cables to avoid interference When connecting control units you must Putting the control unit in...

Страница 4: ...ary to change only the value of parameter and it is not necessary to reset any other parameters BUS address 1 Mixing valve dynamics Desired supply T value Parameter description Selector Turning the ha...

Страница 5: ...PROM control function The software loaded on the control unit checks automatically all the preset parameters every 10 minutes If one parameter is not within the limits indicated it will be replaced by...

Страница 6: ...BLACK wire of the actuator to the terminal identified by number 9 Connect the BROWN wire of the actuator to the terminal identified by number 6 For the connection of the regulating units for underflo...

Страница 7: ...ocated in the box with the control unit place the probe directly in contact with the supply pipe and secure it with the cable tie CONTACT INSTALLATION 1 2 Tee fitting NOT PROVIDED 1 Tee fitting NOT PR...

Страница 8: ...g with DIN EN 60529 IP 40 Protection class complying with DIN EN 60730 II totally insulated Permitted ambient temperature during operation 0 a 50 C Permitted ambient temperature for storage 20 to 60 C...

Страница 9: ...FAR 9611 FAR 9611 3 3 1 1 1 1 1 1 6 1 2 1 www far moscow ru 34 3 499 519 03 69...

Страница 10: ...15 16 2 3 3 10 220 50 N N N L 2 www far moscow ru 34 3 499 519 03 69...

Страница 11: ...1 N 220 2 3 10 L 220 4 6 9 15 16 18 19 21 22 90 RESET EE RUN 3 5 40 C 01 15 05 25 20 110 C 20 110 C 0 0 3 0 00 03 20 C 01 12 80 C 40 C 1 2 00 www far moscow ru 34 3 499 519 03 69...

Страница 12: ...12 5 25 18 19 15 16 1 RUN 0 4 0 6 1 0 1 5 4 18 19 21 22 www far moscow ru 34 3 499 519 03 69...

Страница 13: ...RUN 0 7 EEPROM 10 E81 5 24 5 24 5 0 1 2 3 RUN www far moscow ru 34 3 499 519 03 69...

Страница 14: ...FAR 2170 9 6 9 6 9 6 FAR 3490 3491 3568 3569 3570 3571 FAR 301020 301021 301022 9 6 1 N 9 6 6 www far moscow ru 34 3 499 519 03 69...

Страница 15: ...2 N 9 6 1 1 2 7 1 2 1 1 2 1 2 1 2 1 1 1 2 1 2 1 1 www far moscow ru 34 3 499 519 03 69...

Страница 16: ...10 C 9952 20 C 6247 25 C 5000 30 C 4028 40 C 2662 50 C 1801 60 C 1244 70 C 876 80 C 628 90 C 458 100 C 339 110 C 255 120 C 194 DIN IEC 60 038 220 10 5 250 2 2 Corrente max su morsetto L1 6 3 A DIN EN...