CENTRALISED CONTROL FOR VMC UNITS
7.10.1 - RH
IS possible to select the intervention time between:
■
30 min
■
60 min
■
90 min
IS possible to select the intervention threshold from:
■
MAX = --- Off, 40% to 90%
7.10 - SENS
Note:
selecting VOC or RH displays the PROG key.
Then follow the procedure described in points 7.10.1 and 7.10.2
The CH193VMC modulates the ventilation (air flow rate) of the HVAC
according to the values detected by the relative humidity (RH) and room
quality (VOC) sensors on the device.
If the relative humidity in the room exceeds the set point values, the VMC
automatically increases ventilation to re-establish the correct amount of
relative humidity.