Exhaust Air Ducting

The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems 
occur.  Due to its lower capacity, the VHR 704R is designed to vent from a single source point only and to the bath-
room that is closest to the unit or directly out of the furnace return. Additional source points may be drained from if 
designed properly or installed on a separate Fantech fan bath kit to ventilate additional areas. Fantech bath kits are 
listed below and are ideal for both new construction and retro fit.

Fantech bathroom kits for supplemental exhaust:
 • PB100 (H/F) 

100cfm per fan

 • PB190   

190cfm per fan

 • PB230-2 

230cfm per fan

 • PB230 (H/F-2) 

230cfm per fan

 • PB230 (HV/FV-2)  230cfm per fan
 • PB370-2 

370cfm per fan

 • PBW110 (H/F) 

110cfm per fan

PRACTICAL TIPS

INSTALLING

 

DUCTS TO / FROM INSIDE

•   Building Codes and Combustion 

Appliance Installation Codes do not 
allow location of return air grilles or 
any opening such as a “breathing tee” 
in an enclosed room with spillage sus-
ceptible combustion appliances.

•   The fresh air inlet from the HRV needs 

to respect a minimum  
distance from the furnace return drop 
to ensure proper air mixing and tem-
perature at the furnace core. See fur-
nace manufacturer for appropriate 
specifications.

To maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. 45° elbows are preferred to 90º elbows.  
Use “Y” tees instead of 90º tees whenever possible.
All duct joints must be fastened with screws or duct sealant and wrapped with a quality tape to prevent leakage.  Aluminum foil duct tape is recommended. 
Galvanized ducting from the HRV/ERV to the living areas in the house is recommended whenever possible, although flexible duct can be used in moderation when 
necessary.

Warning:

 The VHR 704R should be installed with a 5" (125mm) duct system that has less than 80 ft (25m) of equivalent duct length on the supply and on the 

exhaust side. If longer runs are required, increasing the duct diameter or following the instructions below might help.
It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.  All air movement 
devices have a performance curve.  The amount of air (CFM) that an HRV will deliver is directly related to the total external static pressure (E.S.P.) of the sys-
tem.  Static pressure is a measure of resistance imposed on the blower by length of duct work/number of fittings used in duct work, duct heater etc.

SUPPLY AIR DUCTING

In homes without a forced air furnace, fresh air should be supplied to all habitable rooms including, bedrooms and living areas.  It should be supplied from high 
wall or ceiling locations.  Grilles that diffuse the air comfortably such as Fantech Contour Grilles are recommended.To avoid possible noise transfer through the 
ductwork system, a short length (approximately 12”, 300 mm) of nonmetallic flexible insulated duct should be connected between the HRV and the supply/exhaust 
ductwork system.
If the floor is the only option available, then special care should be taken in locating grilles.  Areas such as under baseboard heaters will help to temper the air. 
Also, optional inline duct heaters are available for mounting in the supply duct work to add heat if required. In homes with a forced air furnace, you may want to 
connect the HRV to the furnace ductwork (see information below).

Содержание VHR704R

Страница 1: ...asuring the airflow of the Heat Recovery or Energy Recovery Ventilators It is always important to assess how the operation of any HRV ERV may interact with vented combustion equipment i e Gas Furnaces...

Страница 2: ...ncurred in the use of the ventilation system Fantech is not responsible for providing an authorized service center near the purchaser or in the general area Fantech reserves the right to supply refurb...

Страница 3: ...e UL 94HF MOTORS Two 2 German manufactured factory balanced ebm motors with backward curved blades Motors come with permanently lubricated sealed ball bearings to guarantee long life and maintenance f...

Страница 4: ...ps Watts 115V 60Hz 0 40A 40W 3 plug in power cord w 3 prong plug Continuous ventilation mode of supply and exhaust airstreams 10 254mm of clear ance is recommended for removal of core Pa in wg L s cfm...

Страница 5: ...p should be made in the drain line This will prevent odors from being drawn back up into the unit MOUNTING EASY WALL MOUNT LOCATION The HRV must be located in a heated space where it will be possible...

Страница 6: ...ropriate port on the HRV The insulation should remain full and not be compressed The outer liner which acts as a vapor bar rier must be completely sealed to outer wall and the HRV using tape and or ca...

Страница 7: ...recommended Galvanized ducting from the HRV ERV to the living areas in the house is recommended whenever possible although flexible duct can be used in moderation when necessary Warning The VHR 704R s...

Страница 8: ...n an enclosed room with spillage susceptible combustion appliances Partially Dedicated System Stale air drawn from key areas of home bathroom Fresh air supplied to main living areas via the forced air...

Страница 9: ...rap is full of water In cold weather check that HRV is defrosted and not in defrost mode Turn HRV fans on high speed Step 3 Taking measurements Ensure measuring gauge is level and secure Magnehelic or...

Страница 10: ...ring the winter months Clean Core and Filters Every 3 6 Months Unplug unit before doing any repairs or maintenance a Open access door b Carefully grip handle of core and pull out Core will slide out o...

Страница 11: ...tire line of SHR VHR series Heat Recovery Ventilators comes equipped with Fantech s new electronic uni control board which offers a wide variety of features making it the ultimate ventilation control...

Страница 12: ...you Adjust the control when needed PRACTICAL TIPS All controls are low voltage 18 to 24 gauge wire is recommended OPTIONAL REMOTE CONTROLS OPERATION CONT D NOTE A dehumidistat is ideal for use in ene...

Страница 13: ...Locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant eg Over a sofa Turn down the HRV sup...

Страница 14: ...2 wires Dehumidistat On Off 4 wires Mechanical Crank Timer 2 wires and or and or 1 only Air Quality Sensor CUR SW DEHUM N C N O TIMER EDF COM FURNACE INTERLOCK IN COM EDF5 or EDF2 not shown EDF1 RTS3...

Страница 15: ...TIMER RED FURNACE INTERLOCK COM PC SW3 COM NO ON J7 J5 J6 J4 J3 ON OFF ON ON ORANGE ORANGE GREEN STAND BY MED BROWN BROWN GREY TR1 RED YELLOW BLACK WHITE BLUE SW1 BLACK T P DAMPER MOTOR LOW RED BROWN...

Страница 16: ...rgizing the R and G termi nals at the furnace has the effect of energizing Y at the thermostat and thereby turning on the cooling system If you identify this type of thermostat you must use the Altern...

Отзывы: