EXTERIOR DUCTING INSTALLATION

WEATHERHOOD LOCATION

•   Decide where your intake and exhaust hoods will be located.

Locating the Intake Weatherhood

•  Should be located upstream (if there are prevailing winds) from the 

exhaust outlet.

• At a minimum of 2m (6’) away from dryer vents and furnace exhaust 

(medium or high efficiency furnaces), driveways, oil fill pipes, gas meters, 
or garbage containers.

• At a minimum height of 460mm (18’’) above the ground, or above the level 

of expected snow accumulation.

• At a minimum distance of 1m (3’) from the corner of the building.
• Do not locate in the garage, attic, crawl space, or underneath deck.

Locating the Exhaust Weatherhood

•  At least 460mm (18") above ground or above the depth of expected snow accumulation
• At least 1m (3’) away from the corner of the building
• Not near a gas meter, electric meter or a walkway where fog or ice could create a hazard
• Do not locate in a garage, workshop or other unheated space

INSTALLING THE DUCTING TO THE WEATHERHOODS

A well designed and installed ducting system will allow the HRV to operate at its
maximum efficiency. The inner liner of the flexible insulated duct must be secured to the 
sleeve of the weatherhood (as close to the outside as possible) and to the appropriate duct 
connection on the HRV. The insulation should remain full and not crushed. The outer liner, 
which acts as a vapor barrier, must be completely sealed to the outer wall and the HRV 
using tape and/or caulking. A good bead of high quality caulking (preferably acoustical 
sealant) will seal the inner flexible duct to both the HRV duct connection and the 
weatherhood prior to securing them.
To minimize airflow restriction, the flexible insulated duct that connects the two outside 
weatherhoods to the HRV should be stretched tightly and be as short as possible.
Twisting or folding the duct will severely restrict airflow.

See “Installation Diagram Examples” for installation examples.

1

  Using the duct connection of 

the outside hood, outline the 
intake & exhaust holes to be 
cut. The holes should be slightly 
larger than the duct connection 
to allow for the thickness of the 
insulated flexible duct. Cut a 
hole for both the intake and 
exhaust hoods.

Push the hood into the opening 
and then attach the hood to the 
outside wall with mounting 
screws. 
Repeat the installation 
procedure for both the supply 
and exhaust hoods.

2

  Pull the insulated flexible duct 

through the opening until it is 
well extended and straight. 
Slide the duct’s inner vinyl sleeve 
over the hood duct connection 
and secure. Pull the insulation 
over the duct and pull the vapor 
barrier over the sleeve. Secure 
with appropriate tape or 
sealant.

4

  Using a caulking gun, seal 

around both hoods to prevent 
any leaks.

STEPS FOR HOOD INSTALLATION:

36" (1m)

min.

INTAKE

OUTSIDE CORNER

INSIDE CORNER

EXHAUST

18" (460mm) min.

18" (460mm) min.

6' (2m)

min.

36” (1m)

min.

Содержание VHR150

Страница 1: ...net for more detailed technical information United States 10048 Industrial Blvd Lenexa KS 66215 Tel 800 747 1762 Fax 800 487 9915 Canada 50 Kanalflakt Way Bouctouche NB E4S 3M5 Tel 800 565 3548 Fax 87...

Страница 2: ...vented combustion equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects E...

Страница 3: ...Installing the ducting to the weatherhood 9 INTERIOR DUCTING INSTALLATION General Tips 10 Installing duct to HRV 10 Supply Exhaust Air Grilles Location 10 DUCTING INSTALLATION EXAMPLES 11 HRV INSTALL...

Страница 4: ...oor area Bedrooms 0 1 2 3 4 5 6 7 7 Ft2 m2 CFM L s CFM L s CFM L s CFM L s CFM L s 1500 139 30 14 45 21 60 28 75 35 90 42 1501 3000 139 1 279 45 21 60 28 75 35 90 42 105 50 3001 4500 279 1 418 60 28 7...

Страница 5: ...y areas of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the house bedrooms living room 3 The HRV s airflow must be balanced...

Страница 6: ...Due to the difference in pressure between the HRV and the equipment it is being connected to the HRV s airflow must be balanced on site using the procedure found in the section AIRFLOW BALANCING Fant...

Страница 7: ...ure found in the section AIRFLOW BALANCING Stale air to outside Fresh air from outside Unit airflow should be balanced while HRV is on Normal speed and furnace blower is running Fantech heat recovery...

Страница 8: ...ble for retrofitting Benefits Least expensive installation type Fantech heat recovery ventilators HRV that use a supply fan shutdown for frost preven tion do not include an outdoor air motorized dampe...

Страница 9: ...outer liner which acts as a vapor barrier must be completely sealed to the outer wall and the HRV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will se...

Страница 10: ...exible duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal SUPPLY AIR GRILLES LOCATION In homes wit...

Страница 11: ...edicated system Simplified installation Option 1 Simplified installation Option 2 Bathroom Fresh Air Exhaust Air Central Control optional Fresh air to living room Exhaust CG 4 4 Adjustable Grill FEL 4...

Страница 12: ...designed for this purpose These appliances may cause lint dust or grease to collect in the HRV damaging the unit Mounting Chain mount Have a nearby power supply 120 volts 60Hz Choose a location which...

Страница 13: ...registers In cold climates continuous excessive positive pressure inside the house may drive moisture inside the external walls of the house Moisture present inside the external wall may condense if...

Страница 14: ...one airflow may affect the other airflow as well It is recommended to check each airflow again to make sure the value did not change dramatically during the balancing procedure Make adjustments as ne...

Страница 15: ...ed setpoint the venti lation system operates at Normal speed Once the desired humidity level is achieved your ventilation system resumes to its previous mode of operation EDF1 Press button once for co...

Страница 16: ...16 fantech WIRING DIAGRAM Wiring diagram of complete unit inside of access panel Observe polarity on all accessory controls where applicable...

Страница 17: ...ONNECTION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on th...

Страница 18: ...Inadequate power supply at site Have electrician check supply voltage Ductwork is restricting airflow Check duct installation Improper speed control setting Increase the speed of the HRV i e change u...

Страница 19: ...and installation fees are the responsibility of the purchaser The purchaser is responsible to adhering to all codes in effect in his area The warranty is limited to 5 years on parts and 7 years on the...

Страница 20: ...20 fantech NOTES...

Страница 21: ...e le droit de modifier partiellement ou enti rement en tout moment et sans pr avis les caract ristiques la conception les composants et les sp cifications de ses produits afin de conserver sa position...

Страница 22: ...ls de chauffage vacuation fournaise gaz fournaise mazout po le bois etc Les produits sont con us et fabriqu s pour fournir une performance fiable mais ils ne sont pas garantis 100 sans d faut M me les...

Страница 23: ...ensemble des conduits avec hottes 29 INSTALLATION DES CONDUITS INT RIEURS Conseils pratiques 30 Installation des conduits sur le VRC 30 Emplacement des grilles d approvisionnement et d vacuation 30 EX...

Страница 24: ...air recommand Superficie Chambre coucher 0 1 2 3 4 5 6 7 7 Ft2 m2 Pi3 min L s Pi3 min L s Pi3 min L s Pi3 min L s Pi3 min L s 1500 139 30 14 45 21 60 28 75 35 90 42 1501 3000 139 1 279 45 21 60 28 75...

Страница 25: ...ci est aspir partir des endroits cl s de la maison salle de bains cuisine buanderie 2 L air frais est distribu parmi les pi ces habitables chambres coucher salon 3 Le d bit d air du VRC doit tre confi...

Страница 26: ...ue le ventilateur de la fournaise est en marche Ext rieur Air frais distribu l int rieur 1 m 3pi min recommende Retour d air frais Air vici vacu l ext rieur Air frais provenant de l ext rieur Fournais...

Страница 27: ...age du d bit d air Air vici vacu l ext rieur Air frais provenant de l ext rieur L appareil est quilibr vitesse normale et pendant que le ventilateur de la fournaise est en marche Fournaise air puls Le...

Страница 28: ...comprennent pas un volet motoris pour l air ext rieur Si vous utilisez une installation simplifi e c est dire relier de conduit d alimentation d air du VRC l aire du conduit de retour d une fournaise...

Страница 29: ...tement scell sur le mur ext rieur et le VRC l aide de ruban ou de produit de calfeutrage D posez un cordon de produit de calfeutrage de premi re qualit du mastic d isolation acoustique de pr f rence...

Страница 30: ...ssus des crochets Ensuite installez un attache c ble par dessus le conduit flexible afin de pr venir des fuites entre le conduit et le collet Dans le cas d un conduit galvanis faites le glisser sur le...

Страница 31: ...s Air vacu Commande centrale en option Air frais achemin au salon Grille d vacuation CG4 Grille ajustable 4 po FEL 4 Coude 4 po 460 mm 3m HRV Chambres 460 mm Salle de bains Air frais Air vacu Commande...

Страница 32: ...er l accumulation de charpie de poussi re ou de graisse dans le VRC et l endommager MONTAGE CHAINE Assurez vous d avoir une source d alimentation pr s 120 volts 60Hz Choisissez un emplacement o il y a...

Страница 33: ...la continuelle pression positive excessive l int rieur de la maison peut chasser l humidit l int rieur des murs ext rieurs de la maison L humidit pr sente l int rieur de la paroi externe peut se conde...

Страница 34: ...l e le r glage d un d bit d air peut affecter le d bit d autres aussi Il est donc recommand de v rifier chaque d bit d air nouveau pour s assurer que la valeur n a pas changer consid rablement Faites...

Страница 35: ...au d humidit d sir est atteint votre syst me de ventilation retourne son mode de fonctionnement pr c dent EDF1 Appuyez le bouton pour une vitesse r duite continuelle Appuyez le bouton une seconde fois...

Страница 36: ...36 fantech SCH MAS LECTRONIQUES Sch ma lectrique de l appareil au complet situ l int rieur du paneau d acc s...

Страница 37: ...itation de la borne Y du thermostat et cons quemment la mise sous tension du syst me de refroidissement Si votre syst me est muni d un tel type de thermostat vous devez respecter le c blage de verroui...

Страница 38: ...VRC V rifiez le r seau de conduits Mauvais r glage de la commande de vitesse Augmentez la vitesse du VRC i e changez la vitesse de l appareil de vitesse R DUITE vitesse NORMALE avec le contr le D s q...

Страница 39: ...t tenu de respecter tous les codes en vigueur dans sa r gion Les pi ces y compris les pi ces de rechange pos es ult rieurement sont garanties pendant 5 ans partir de la date d achat de l appareil Les...

Страница 40: ...x 15 402041 3 Heat Recovery Cell 9 x 9 x 15 402063 4 Capacitors 8uF 410012 5 PCB RV CTRL REV 1 5 420459 6 Door Switch 410867 7 Auto Transformer 411963 8 Control Switch 410213 9 Kit Drain Plug 40315 1...

Страница 41: ...41 fantech Notes...

Страница 42: ...42 fantech Notes...

Страница 43: ...43 fantech Notes...

Страница 44: ...make technical changes For updated documentation please refer to www fantech net Fantech Fantech se r serve le droit de faire des changements tech niques Pour de la documentation jour s il vous pla t...

Отзывы: