background image

7

INSTALLATION EXAMPLES 

(CONT'D)

DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM 
to the FURNACE COLD AIR RETURN

SIMPLIFIED INSTALLATION

(GOOD)

(RETURN/RETURN METHOD)

Suggested installation for:

• When bathroom and kitchen 

already have local exhaust 
system

• May be suitable for 

retrofitting

Benefits: 

Least expensive 

installation type

1.  Furnace blower must operate when ventilation from ERV is required. The furnace should 

be set to run continuously or interlocked with ERV. 

See furnace electrical connection 

on page 15.

2.  A minimum separation of 1m (39’’) is recommended between the two direct 

connections.

3.  In order to prevent exhausting any fresh air, the ERV’s exhaust air connection should be 

upstream of the ERV’s supply air connection when ducting to the furnace’s cold air return.

4.  Due to the difference in pressure between the ERV and the equipment it is being 

connected to the ERV’s airflow must be balanced on site, using the procedure found in the 
section “AIRFLOW BALANCING”

* In the case of a multi-zone system, please contact Fantech customer 

service prior to installing any installation type requiring the use of the 

furnace interlock"

Air from inside

* Unit air flow should be balanced while ERV is on "Normal" speed and 
furnace blower is running.

Outside

1 m (3' 3") 

min.  

recommended

Cold air 

return

* Ductwork layout may dif-
fer depending on model

ERV/Furnace ducting for Simplified Installation - Option 1

Stale air to

outside

Fresh air from

outside

Fresh air to
living areas

Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost preven-

tion do not include an outdoor air motorized damper. If you are using a simplified instal-

lation, i.e. connecting the ERV supply air duct to a furnace's return air duct, the ERV must 

operate continuously. When the ERV is turned off, no warm exhaust air will flow through 

the ERV but the furnace's fan will continue to draw in outdoor air directly into the furnace.  

If it's cold outside, cold air will be introduced, without re-heating, directly into the furnace.

If the ERV is installed such that the homeowner may turn off the ERV during the winter, we 

recommend installing a motorized damper between the HRV's supply air and the furnace's 

return air duct that closes when the ERV is not operating. See wiring diagram (figure 1). 

You may also choose to use a Fantech ERV that uses a recirculation defrost that incorpo-

rates an outdoor air damper. 

Damper 
Motor

24 VAC Transformer

COM

NO

HRV Furnace interlock
See page 15.

24V

120V

Figure 1

*Transformer and Damper motor not included

Motorized 
damper

1 m (3' 3") 

min.  

recommended

Air return

Содержание SER200

Страница 1: ...ode and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components and specifications to maintain their technological leadership position Please visit our website www fantech net for more detailed technical information United States 10048 Industrial Blvd Lenexa KS 66215 Tel 800 747 1762 Fax 800 4...

Страница 2: ...d combustion equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even reliable products will experience occasional failures and this possibility should be recognized by the user If these products are used in a life support ventilation system where failure could result in...

Страница 3: ...rhood Location 8 Installing the ducting to the weatherhood 8 INTERIOR DUCTING INSTALLATION General Tips 9 Installing duct to ERV 9 Supply Exhaust Air Grilles Location 9 ERV INSTALLATION 10 AIRFLOW ADJUSTMENT BALANCING Start up procedure 11 Airflow balancing 11 LOW VOLTAGE CONTROL SYSTEMS 13 WIRING DIAGRAM 14 TROUBLESHOOTING 16 ERV MAINTENANCE CHART 17 ERV CORE WASHING INSTRUCTION 18 PARTS LIST 19 ...

Страница 4: ... 53 25 60 28 501 1000 47 93 45 21 53 24 60 28 68 31 75 35 1001 1500 94 139 60 28 68 31 75 35 83 38 90 42 1501 2000 140 186 75 35 83 38 90 42 98 45 105 49 2001 2500 187 232 90 42 98 45 105 49 113 52 120 56 2501 3000 233 279 105 49 113 52 120 56 128 59 135 63 3001 3500 280 325 120 56 128 59 135 63 143 66 150 70 3501 4000 326 372 135 63 143 66 150 70 158 73 165 77 4001 4500 373 418 150 70 158 73 165 ...

Страница 5: ...The ERV s airflow must be balanced after installation using the procedure found in the section AIRFLOW BALANCING Suggested installation for Hydronic baseboard Infloor heating Electric baseboard Mini split heat pump Benefits Provides the best fresh air distribution in the house lowest operation cost since the furnace air handler unit is not needed Air from inside Unit air flow should be balanced wh...

Страница 6: ...Dedicated System Air from inside Unit air flow should be balanced while ERV is on Normal speed and furnace blower is running Air return 1 m 3 3 min recommended Cold air return Ductwork layout may dif fer depending on model Stale air to outside Fresh air from outside Fresh air to living areas Fantech energy recovery ventilators ERV that use a supply fan shutdown for frost preven tion do not include...

Страница 7: ...balanced while ERV is on Normal speed and furnace blower is running Outside 1 m 3 3 min recommended Cold air return Ductwork layout may dif fer depending on model ERV Furnace ducting for Simplified Installation Option 1 Stale air to outside Fresh air from outside Fresh air to living areas Fantech energy recovery ventilators ERV that use a supply fan shutdown for frost preven tion do not include an...

Страница 8: ...arrier must be completely sealed to the outer wall and the ERV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the inner flexible duct to both the ERV duct connection and the weatherhood prior to securing them To minimize airflow restriction the flexible insulated duct that connects the two outside weatherhoods to the ERV should be stretched ...

Страница 9: ...exible duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal Supply air grilles location In homes without a forced air furnace fresh air should be supplied to all habitable rooms including bedrooms and living areas It should be supplied from high wall or ceiling locations Grilles that diffuse the air...

Страница 10: ...p fan Central vacuum system Bathroom exhaust fans unless they are specifically designed for this purpose These appliances may cause lint dust or grease to collect in the ERV damaging the unit Connecting any of these types of appliances to the ERV will void your warranty Mounting Chain mount Have a nearby power supply 120 volts 60Hz Choose a location which allows the possibility of mounting the uni...

Страница 11: ...s close to room temperature as possible For optimal performance ERV unit should be re balanced after a major renovation or after the installation of extra grilles or registers 1 Remove the nutsert INSTALLING DRAIN LINE Through normal operation and during its defrost mode the ERV may produce some condensation This water should flow into a nearby drain or be taken away by a condensate pump The ERV a...

Страница 12: ...n the duct work so entire airflow is measured Measuring the airflow using station grid method Adjusting airflows A damper is integrated into the Fresh Air to Building collar and on to the Stale Air to Outside This damper replaces the installation of a separate damper into the Fresh Air to Building and on to the Stale Air to Outside ducting line The damper collar is pre set in the fully opened posi...

Страница 13: ...referred indoor relative humidity range and ventilation mode for day and night conditions No battery to replace all programmed settings are retained during power outage Maintenance reminder indicator Error code messages reduce troubleshooting time EDF7 MODE button provides 3 modes of operations Ventilation Recircula tion and Standby User selected fan speed Reduced Medium Normal and 20 minutes per ...

Страница 14: ...14 WIRING DIAGRAM ON MUST HIGH SPEEDS LOW 55V JP5 JP3 75V 120V 90V LOW JP3 JP5 HIGH 120V 90V 75V 55V SPEEDS ON Observe polarity on all accessory controls where applicable ...

Страница 15: ...ECTION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the cooling system If you identify this type of thermostat you must use the Alternate Furnace Interlock Wiring Standard Accessory Control Contact Alternative Accessory Control Contact As per building codes...

Страница 16: ... power supply at site Have electrician check supply voltage Ductwork is restricting airflow Check duct installation Improper speed control setting Increase the speed of the ERV i e change unit control from REDUCED to NORMAL speed ERV airflow improperly balanced Have contractor balance ERV airflows Ducting has fallen down or been disconnected from ERV Have contractor reconnect ducting Supply air fe...

Страница 17: ...mages incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply refurbished parts as replacements Transportation removal and installation fees are the responsibility of the purchaser The purchaser is responsible to adhering to all codes in effect in his area This...

Страница 18: ...ore s air inlets facing down place it in a large sink bathtub or shower 4 Pour clean tap water through the face of the core facing upwards until it runs clear Ensure the entire surface is rinsed 5 Rotate the core so that its other air inlet is facing down and repeat step 5 6 With plates still oriented vertically allow the core to dry normally 2 3 hours 7 Slide back the core into the unit 8 Replace...

Страница 19: ...Replacement Board AC 422677 6 Door Switch 410867 7 Auto Transformer 411963 8 Control Switch 410213 9 Kit Drain Plug 40315 10 Collar 6 Balancing 10mm 412284 11 Collar 6 24mm LIP 410542 15 Temperature Probe 40286 16 Door Assembly 427756 Kit Chain 404261 Wall Support VHR200 422998 Filter MERV 6 11 5x15x0 125 412630 Wiring Diagram 422576 Installation Manual 427787 9 1 2 3 6 8 10 10 11 11 4 5 7 16 ...

Страница 20: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech ...

Отзывы: