Please follow all applicable codes when installing this unit
1. Equipment should be hung at its proper elevation by using 

temporary fixtures that can be removed after vibration 
hangers are installed.

2. Hanger may be fastened directly to the structure or 

somewhere between suspended unit (be sure not to 
over tighten the neoprene element).

3. Install hangers.
4. Turn nuts on rod assembly clockwise one complete turn 

on each hanger. Repeat this procedure until temporary 
hanging fixtures are loose and load of piping or equipment is
suspended completely on the vibration hangers.

5. Remove temporary hanger fixtures and level piping or 

equipment by taking additional turns on the spring/top 
hanger rod nut – clockwise to raise, counterclockwise to 
lower as required.

6. If equipping fan with isolators (FC Clamps), they should 

be attached at this time.

7. See wiring section to complete installation.

Mounting Illustration 1

Vibration

Mount

Detail

Please follow all applicable codes when installing this unit
1. Install wood supports to structure for fan mounting.
2. If equipping with vibration mounts, attach to supports.
3. Attach fan to vibration mounts (be sure not to overtighten 

the neoprene element).

4. If equipping fan with isolators (FC Clamps), they should be 

attached at this time.

5. See wiring section to complete installation.

Mounting Illustration 2

Please follow all applicable codes when installing this unit
1. Create/Install angle wood supports to structure for fan
mounting.
2. If equipping with with vibration mounts, attach to supports.
3. Attach fan to vibration mounts (be sure not to overtighten
the neoprene element).
4. If equipping fan with isolators (FC Clamps), they should be
attached at this time.
5. See wiring section to complete installation.

Mounting Illustration 3

Mounting

Bracket

Vibration

Mounts

Fan

Bracket

Detail

Please Note: Vibration Mounts and Hardware are not supplied with fan. FC Clamps are sold separately.

Call 1-800-667-8721 anywhere in the US and Canada

-

www.

rangehoods

.com

Fan Tech at

kitchen

::

accessories

U      N      L      I      M      I      T      E      D

::

rangehoods

.

com

Содержание FKD 8XL

Страница 1: ...device such as a tag to the service panel Fan Tech at kitchen accessories U N L I M I T E D INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR MODEL FKD 1 The compactness and adaptability of the FKD Series fans permit easy installation The fans are shipped fully assembled and can be mounted at any angle For various mounting see figures on the following page 2 Because this unit has rotating parts safety...

Страница 2: ...t Detail Please follow all applicable codes when installing this unit 1 Install wood supports to structure for fan mounting 2 If equipping with vibration mounts attach to supports 3 Attach fan to vibration mounts be sure not to overtighten the neoprene element 4 If equipping fan with isolators FC Clamps they should be attached at this time 5 See wiring section to complete installation Mounting Ill...

Страница 3: ... will not be affected 230 Volt Three Phase Fan Notes 1 Contactor should be used Control coil should be wired in series with motor thermal contacts TK leads as shown in diagram to provide thermal motor protection 2 All leads are color coded as well as identified with a band containing an Alpha Alpha or Alpha Numeric code i e TK or Z2 Colors should be verified against code band If code band and colo...

Страница 4: ...st be clearly marked on outside of carton or delivery will be refused All product s must be returned freight prepaid 3 Product s will be repaired replaced and shipped back to buyer no credit will be issued 4 Any out of warranty product will be evaluated and buyer will be notified of cost repair cost will be charged to cus tomer buyer will be responsible for return freight or prod uct may be return...