Rev.17
32/119
4.12. Setting Group
There are three setting groups and one general settings. The setting group which is active at a specific
moment can be modified in two ways:
•
Changing the active setting group. In general settings there is a setting which establishes
which setting group is active.
•
By means of two inputs. To this end four possibilities are defined.
Input-2 Input-1 Setting group
0
0
This situation is governed by the active setting group.
0
1
Setting group 1
1
0
Setting group 2
1
1
Setting group 3
If none of the inputs is activated (the zero position) the active item is defined by the active setting
group defined in the general group. Regarding other options, regardless of that established by the
settings, the inputs prevail over the settings.
If the use of both inputs is not required, then one can be used, but depending on which is used,
operation can be done with setting group 1 or setting group 2.
If both inputs are activated item is defined by setting group 3.
Содержание SIA-F
Страница 7: ...www fanox com Rev 17 7 119 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Frontal view...
Страница 8: ...www fanox com Rev 17 8 119 2 2 Case dimensions The dimensions are in mm CUT OUT PATTERN...
Страница 9: ...www fanox com Rev 17 9 119 2 3 Connection diagram 3 Phase CT and neutral CT Connection...
Страница 10: ...www fanox com Rev 17 10 119 3 Phase CT and residual neutral Connection...
Страница 18: ...www fanox com Rev 17 18 119 3 5 2 Load curve for relay SIA F 1 3 5 3 Load curve of relay SIA F 5...
Страница 34: ...www fanox com Rev 17 34 119...
Страница 35: ...www fanox com Rev 17 35 119...
Страница 36: ...www fanox com Rev 17 36 119...
Страница 117: ...www fanox com Rev 17 117 119 9 6 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 118: ...www fanox com Rev 17 118 119 NOTES...
Страница 119: ...www fanox com Rev 17 119 119...