background image

107

2.1

 Trip class / tripping time (IEC 947-4-1). Relays C, GL, P, PF, G and GEN

The different trip classes / tripping times enable the user to select the overload protection according to the various motor applications in either short or long 
start-ups and for different generator uses.

The class number or the tripping time refers to the maximum approximate time in seconds allowed for the direct start of the motor from a cold condition.

To select the trip class or tripping time (t

6 x 

,

B

) use the corresponding dip switches. The recommended values are listed in the following tables.

Average trip curves (IEC 947-4-1)

Cold curve:

 represents 

the performance of the 
relay without any previous 
current flow, first start.

Warm curve:

 the tripping 

times decrease as the 
current flows, and is 
adapted to the motor 
heating condition based 
on the thermal memory. 
The warm condition (IEC-
255) is reached after a 
current of  0.9 x 

,

N

 (motor 

rated current) flows during 
approximately 2 hours.

Motor with star-delta start

Motor with direct start-up

C

P

PF

GEN

GL

PS

G

Start

time (s)

Trip 

time

Trip classes

Models

Model

Trip classes

Start

time (s)

Trip 

time

Models

Model

Generator’s limit curve

Содержание C 9

Страница 1: ...ed as a model of the thermal image of the motor and is continously compared to the values set on the relay The three power supply cables to the motor are not directly connected to the relay but pass t...

Страница 2: ...igh current busbars In star delta starting the relay or the current transformers must be installed between the fuses or circuit breaker and the contactor Relays used in combination with frequency inve...

Страница 3: ...B use the corresponding dip switches The recommended values are listed in the following tables Average trip curves IEC 947 4 1 Cold curve represents the performance of the relay without any previous c...

Страница 4: ...ad trip level is set by means of a potentiometer with settings from 0 15 to 1 0 Select this value taking into consideration the no load motor cos and that corresponding to the estimated minimum operat...

Страница 5: ...ng three dipswitches To avoid nuisance trips set this level to approximately 10 above the no load motor current Example 2 5 Phase sequence Monitoring the current GL and P relays An incorrect phase seq...

Страница 6: ...ble pumps in service stations and water pumping surface pumps etc Compressors Fans blowers and ventilators Industrial refrigeration and air conditioning Centrifuges Presses Cranes elevators escalators...

Страница 7: ...400 V 50Hz 2 0 2 8 3 8 5 5 7 9 5 13 16 5 24 32 40 47 64 79 92 113 149 183 220 440 460 V 60Hz 1 9 2 5 3 4 4 8 6 7 5 11 15 21 27 33 39 53 65 79 95 120 153 183 MODELS Adjustment range B A MOTOR CHARACTE...

Отзывы: