- 8 -
Outputs 5-6 and 7-8 are connected in parallel, which
means that the output signal is available on each output.
power supply voltage
3×230 V+N
minimum operating voltage
(with power from a single phase)
85 V
maximum phase voltage
420 V
frequency
45÷55 Hz
cooperation with power generators
no
maximum load current (AC-1)
16 A
mechanical strength of contacts
1×10⁷
electrical strength of contacts (16 A/AC-1)
1×10⁵
TrueRMS measurement
yes
sampling frequency of the signal
4 kHz
actuator
3× relay
return hysteresis
10 V
setting range Vmin
160÷220 V
setting range Vmax
240÷280 V
voltage measurement error
±1%
switching time
max 200 ms
return time
5÷300 s
indication of the output voltage
3×LED
power consumption
1.5 W
terminal
4.0 mm² screw terminals
tightening torque
0.5 Nm
working temperature
-25÷50°C
dimensions
2 modules (35 mm)
mounting
on TH-35 rail
ingress protection
IP20