background image

- 9 -

 

1-3 

230 V power supply relay

 

1-6 

24 V power supply relay

 7 

�����

 control signal input

 9 

�����

 control signal input

 11 

���

 contact power input

 

10 

output: break contact (passive)

 

12 

output: closing contact (active)

power supply 

195÷253 V AC

 

21÷27 V AC/DC

maximum load current (AC-1) 

8 A

contact 

separated 1×NO/NC

working time (adjustable) 

0.1 s÷576 h

activation delay 

<50 ms

power supply indication 

green LED 

contacts state indication 

red LED

power consumption 

0.8 W

terminal 

2.5 mm² screw terminals

tightening torque 

0,4 Nm

working temperature 

-25÷50°C

dimensions 

1 module (18 mm)

mounting 

on TH-35 rail

protection level 

IP20

Technical data

Содержание PCS-516 DUO

Страница 1: ...again you need to switch off the power supply voltage and switch it back on Purpose Features of work F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Donotdisposeofthisdeviceinthetrashalongwithotherwaste According to the Law on Waste electro coming from households free of charge and can give any amoun...

Страница 2: ...measured the red LED is on To execute the operating mode of the relay again you need to switch off the power supply voltage and switch it back on C C ON delay cyclic On delay operating mode is carried out cyclically at equal in tervals between the preset operating time and break time D D OFF delay cyclic Off delay operating mode is carried out cyclically at equal in tervals between the preset oper...

Страница 3: ...lses G Generating a single pulse with time t by the trailing edge of the signal During the time measurement the system does not react to pulses H Off delay with back up feature The rising edge of the si gnal causes the relay to be switched on while the trailing edge causes the start of time measurement Applying the signal during the time measurement causes the cycle to be extended ...

Страница 4: ... signal During the time measurement the system does not react to signal When the RESET voltage is applied during the execution of the given function it causes for functions A B C D F the implementation of the operating mode from the beginning for functions F G H I the return of the relay to the initial state and waiting for the signal for function K permanent switching on of the relay contact in p...

Страница 5: ... permanently in position 11 10 Using the time range setting knob T set one of the selected ranges then using the time setting knob T set the selected va lue on a scale from 1 to 12 The product of these values is equal to the operating time for example 1 m 7 7 min Using the dial set one of the functions for example func tion A off delay Working time setting Working mode setting ...

Страница 6: ... time range of 1 12 0 1s 0 1 1 2sec 10m 10 120min 1s 1 12sec 2h 2 24godz 10s 10 120sec 1d 1 12days 24 288h 1m 1 12min 2d 2 24days 48 576h ON when the power supply is on the contact is perma nently closed in position 11 12 OFF when the power supply is on the contact is perma nently closed in position 11 10 1 Turn off the power supply 2 Fix the relay on a rail in the switchboard 3 Connect the power ...

Страница 7: ... 7 4 Connect the power supply circuit of the receiver in series to terminals 11 12 Wiring diagram ...

Страница 8: ... 8 Description of terminals ...

Страница 9: ...y 195 253 V AC 21 27 V AC DC maximum load current AC 1 8 A contact separated 1 NO NC working time adjustable 0 1 s 576 h activation delay 50 ms power supply indication green LED contacts state indication red LED power consumption 0 8 W terminal 2 5 mm screw terminals tightening torque 0 4 Nm working temperature 25 50 C dimensions 1 module 18 mm mounting on TH 35 rail protection level IP20 Technica...

Страница 10: ...owski sp j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which confor mity is declared can be found at www fif com pl on the product page Warranty CE declaration ...