background image

- 1 -

OM-633

Power consumption limiters 

with a voltage relay function

The OM-633 power consumption limiter is designed for au-

tomatic disconnection of the power supply of the electrical 

installation circuit in case of exceeding the set value of power 

consumed by the receivers in this circuit as well as for monito-

ring the power supply voltage of this receiver and protecting it 

against the effects of voltage increase or decrease beyond the 

set values.

»

Adjustable threshold of tripping power 1÷10 kW;

»

Protection against the drop of UL power supply voltage 

(150÷210 V);

»

Protection against the rise of UL power supply voltage 

(230÷260 V);

»

Counter of relay actuations with automatic disconnection 

of system power supply after exceeding a set number of 

actuations;

Purpose

Features

F&F Filipowski sp. j.

Konstantynowska 79/81, 95-200 Pabianice, POLAND

phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71

www.fif.com.pl; e-mail: [email protected]

Do not dispose of this device in the trash along with other waste! 

According to the Law on Waste, electro coming from households free of char-

ge  and  can  give  any  amount  to  up  to  that  end  point  of  collec� on,  as  well  as 

to store the occasion of the purchase of new equipment (in accordance with 

the principle of old-for-new, regardless of brand). Electro thrown in the tra-

sh or abandoned in nature, pose a threat to the environment and human health.

Содержание OM-633

Страница 1: ...ainst the rise of UL power supply voltage 230 260 V Counter of relay actuations with automatic disconnection of system power supply after exceeding a set number of actuations Purpose Features F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Do not dispose of this device in the trash along with other w...

Страница 2: ...led circuit results in a disconnection of the power supply to this circuit after a user set time The power supply will be restored automatically after a preset time If the power consumed is still greater than the set value the circuit will be disconnected again Automatic disconnection will also occur if the power consump tion is 8 times higher than the set threshold and if the power consumption ex...

Страница 3: ... of permanent operation of the limiter longer than 10 minutes Operating mode In operating mode the display shows the value of the power consumed Led R indicates contact status off contact open position 7 9 on contact closed position 8 9 After pressing the button the display shows the current measured voltage value After pressing the button the display shows the cur rent measured value of the disco...

Страница 4: ...n with the previous settings Restart After the power supply is switched on the limiter starts working after 10 seconds The display shows the remaining time to start Setting parameters P disconnection power range 1 10 kW step of 0 1 kW UH upper threshold of disconnection voltage range 230 260 V step of 5 V UL lower threshold of disconnection voltage range 150 210 V step of 5 V Cto disconnection cou...

Страница 5: ...mode 1 Turn off the power supply 2 Fix the limiter on a rail in the control box 3 Connect the power supply of the limiter to terminals 1 2 It is essential to connect L to terminal 2 and N to ter minal 1 4 Connect the power supply of the controlled circuit or contac tor coil in series via terminals 8 9 5 Lead the control circuit cable through the through channel points 6 Set the operating parameter...

Страница 6: ... 6 Connection diagram ...

Страница 7: ... lower tripping threshold UL 150 210 V upper tripping threshold UH 230 260 V lower tripping time UL 5 s upper tripping time UH 0 3 s diameter of a through hole 5 mm power consumption 2 5 W working temperature 25 50 C terminal 2 5 mm screw terminals cord 4 0 mm screw terminals wire tightening torque 0 5 Nm dimensions 3 modules 52 5 mm installation on TH 35 rail ingress protection IP20 Technical dat...

Страница 8: ... that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which confor mity is declared can be found at www fif com pl on the product page www fif com pl from the product subpage Warranty CE dec...