- 6 -
The circuit for measuring the voltage and supply of the meter:
15
neutral N-wire
16
L3 phase
17
L2 phase
18
L1 phase
installation 4-wire
rated voltage
3×230/400 V
minimum measured current
0.04 A
base current
3×1.5 A
maximum current
3×5 A
voltage measuring range
160÷265 V
transformer type
200/5 A
measurement accuracy (IEC62052-11, IEC62053-21)
1
rated frequency
50 Hz
insulation protection class
II
own power consumption
<10 VA; <2 W
indication range
0÷9999999 kWh
constant
300 pulses/kWh
current consumption signalling
3× red LED
read-out signalling
red LED
pulse output
type
open collector
maximum voltage
27 V DC
maximum current
27 mA
pulse constant
300 pulses/kWh
pulse time
35 ms
working temperature
-25÷55°C
terminal
25 mm² screw terminals
Technical data