The circuit for measuring the voltage and supply of the meter:

 

15 

neutral N-wire

 

16 

L3 phase

 

17 

L2 phase

 

18 

L1 phase

installation 4-wire

rated voltage 

3×230/400 V

minimum measured current 

0.04 A

base current 

3×1.5 A

maximum current 

3×5 A

voltage measuring range 

160÷265 V

transformer type 

200/5 A

measurement accuracy (IEC62052-11, IEC62053-21) 

1

rated frequency 

50 Hz

insulation protection class 

II

own power consumption 

<10 VA; <2 W

indication range 

0÷9999999 kWh

constant 

300 pulses/kWh

current consumption signalling 

3× red LED

read-out signalling 

red LED

pulse output

type 

open collector

maximum voltage 

27 V DC

maximum current 

27 mA

pulse constant 

300 pulses/kWh

pulse time 

35 ms

working temperature 

-25÷55°C

terminal 

25 mm² screw terminals

Technical data

Содержание LE-03d CT200

Страница 1: ...n in the respective phase Energy consumption in the phase is indicated by a flashing of corre sponding LED L1 L2 L3 The sum of the three phase pulses is indicated by a flashing LED and converted into energy absorbed throughout the three phase system Its value is displayed by the segment LCD display Purpose Functioning F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 4...

Страница 2: ...ou to connect another pulse device SO that reads pulses generated by the meter No additional connected equipment is required for proper ope ration of the meter The meter has sealable input and output terminal covers to pre vent any attempts to bypass the meter Pulse output Sealing ...

Страница 3: ... 3 The meter is marked with individual serial number allowing its unambiguous identification The marking is laser engraved and cannot be removed Meter number Front description ...

Страница 4: ...conductors and con nect the secondary outputs to the terminals in accordance with the markings 1 2 L1 3 4 L2 5 6 L3 5 N wire connect to terminal 15 6 In order to increase the safety of the system and the measu rement accuracy it is recommended to ground the terminals S2 of the secondary side of current transformers 7 Additional pulse receiver connected optional to terminals 9 i 8 Additional pulse ...

Страница 5: ... 5 Current measurement circuits 1 2 L1 phase 3 4 L2 phase 5 6 L3 phase Pulse output open collector 8 transistor emitter 9 transistor collector cont on next page Wiring diagram ...

Страница 6: ...ansformer type 200 5 A measurement accuracy IEC62052 11 IEC62053 21 1 rated frequency 50 Hz insulation protection class II own power consumption 10 VA 2 W indication range 0 9999999 kWh constant 300 pulses kWh current consumption signalling 3 red LED read out signalling red LED pulse output type open collector maximum voltage 27 V DC maximum current 27 mA pulse constant 300 pulses kWh pulse time 3...

Страница 7: ...dealer or contact us directly F F Filipowski sp j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which conformity is declared can be found www fif com pl on the product subpag...

Страница 8: ...ervoltage circuit breakers Before connecting the power supply make sure that all cables are connected correctly It is essential to observe the operating conditions of the meter supply voltage humidity temperature To avoid electric shock or damage to the meter turn off the power supply whenever the connection is changed Do not make any changes to the unit yourself Doing so can re sult in damage to ...