Too high temperature can be caused by connecting a too 

high load to the sensor.

The brightness level of the signal LED adjusts to the am-

bient brightness (high ambient brightness – high LED bri-

ghtness level). When an overtemperature is indicated, 

the light flashes at maximum brightness.

power supply 

165÷265 V AC

maximum load current 

8 A

detection range (adjustable) 

0.1÷2.0 m

brightness level (adjustable) 

2÷500 lx

switch-on time (adjustable) 

0÷10 min.

detection 

sensor 

ToF laser sensor

wave length 

940 nm

security 1

st

 class

beam scattering 

±18°

power consumption

standby 

0,5 W

on (relay on) 

1 W

terminal 

2.5 mm² screw terminals

tightening torque 

0.4 Nm

working temperature 

-10÷45°C

continued on next page

Technical data

Содержание DRL-60-230

Страница 1: ...elow the value set on the sensor This solution is perfect for switching on lighting circuits for exam ple on open stairs where it is important that the sensor detects presence only on the stairs and i...

Страница 2: ...ct control of electrical circuits with a load of up to 8 A AC 1 Compact size can be mounted in a 60 mm box LED indicating the operating status of the sensor Thermal protection against exceeding the ac...

Страница 3: ...ncorrect operation of the distance and light intensity measurement system 3 Do not mount sensors opposite each other or mirrors as this can lead to unwanted sensor excitation 4 Prepare a hole for the...

Страница 4: ...utomation controllers follow the documentation of the devices to be integrated 8 Use the dials to set the operating parameters of the detector detection range level of brightness below which switching...

Страница 5: ...5 The sensor is designed for a power supply of 165 265 V AC Terminal Function N Sensor supply neutral wire L Sensor supply phase wire OUT Output relay contact Description of control terminals Settings...

Страница 6: ...on condition is also met 2 LUX 2 500 Lx Brightness level setting If the light intensity is lower than the value set by the knob the light will switch on when the presence is detected in the detection...

Страница 7: ...igher than 8 A or a load with a high starting current it is recommended to use external contactors or relays adapted to current surges e g PP 1Z LED 230 V In this case the DRL 60 230 switches an exter...

Страница 8: ...the detection area An obstacle in the detection area has been detected The light was not switched on because the brightness level was too high An obstacle in the detection area has been detected The l...

Страница 9: ...flashes at maximum brightness power supply 165 265 V AC maximum load current 8 A detection range adjustable 0 1 2 0 m brightness level adjustable 2 500 lx switch on time adjustable 0 10 min detection...

Страница 10: ...dealer or directly with us F F Filipowski L P declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibili...