- 14 -
DMM-5T-3 User manual
To change the current transformer ratio, press the set button while the Figure-58 is on the screen. Figure-69 comes
to the screen. Press right button to move between digits.
Press the down key to change the value of the digit.
You can change the digit value which is the underline. When
you press the set button after entering the ratio, the current
transformer ratio is recorded and the screen shows figure-59.
You can scroll through the parameters in the menu by pres-
sing the right button or you can exit the menu by pressing
the Esc key.
Example
: 100 / 5A current transformer ratio (multiplier value) is 20. The CTR value needs to be set to 0020.
To change the voltage transformer ratio, press the set button while the Figure-60 is on the screen. Figure-70 comes
to the screen. Press right button to move between digits.
Press the down key to change the value of the digit. You can
change the digit value which is the underline. When you
press the set button after entering the ratio, the voltage
transformer ratio is recorded and the screen shows figure-60.
You can scroll through the parameters in the menu by pres-
sing the right button or you can exit the menu by pressing the
Esc key.
Example
: Medium voltage (M.V.) = Enter the ratio of the voltage transformer that converts 34.500 V to 110 V. The
ratio (multiplier) is calculated as 34.500/110 = 313.6 voltage transformer ratio. The VTR value must be set to 313.6.
To change the RS-485 remote communication settings, press the set button while figure-61 is on the screen. Figure-71
comes to the screen. Two parameters can be set here.
Baudrate (br - communication speed) and Modbus ID (Id - the
number that identifies the device on the RS-485 line). Press
the right button to move the point (.) to the parameter you
want to set.
Then change the parameter value by pressing the down key.
When you press the Set button, the changes that you made
are saved and Figure-61 comes to the screen. You can scroll
through the parameters in the menu by pressing the right button or you can exit the menu by pressing the Esc
key. Modbus ID (MBID) value; when more than one communication devices connect to a modem, serial number or
Modbus address must be different. In such cases, enter a different value from other devices.
Baudrate (br):
1200÷115200 bps,
Modbus ID (Id)
: 1÷247,
Stop bits
: 1,
Party
: none.
To delete the records, press the set key while the screen is shown. Figure-71 comes to the screen. You can delete 3
records here. Energy (En), Demand (dE) and Event logs (LE).
Press the right key to move the point (.) to the record which
you want to delete. Then press the down key to change the
value to "yes". The record value which you do not want to
delete must remain in "no".
When you press the Set key, only records with the value "yes"
will be deleted and the Figure-62 comes to the screen. You
can scroll through the parameters in the menu by pressing
the right button or you can exit the menu by pressing the Esc key.
11.1. Setting the current transformer ratio
11.2. Changing voltage transformer ratio
11.3. RS-485 Remote communication settings
11.4. Deleting energy, demand and event records