- 3 -
1. Switch off power supply.
2. Install indicator on DIN rail.
3. Connect the indicator according to the connection diagram:
»
Connect the power supply of the indicator (230 V AC) to
terminals 5 and 6;
»
The current transformer output is connected to terminals 2
and 8.
4. Switch on the power supply.
If the secondary windings of the measuring transformers
are open (e.g. during assembly) and a current flows thro-
ugh the measured circuit, a dangerous voltage may be
induced at the terminals of the measuring transformer.
It is absolutely necessary to protect oneself from such a
situation by switching off the power supply of measured
circuits or installing additional bridges short-circuiting
the secondary side of a measuring transformer.
The indicator is designed for current measurement using
current transformers with a rated output current of 5 A.
Current flow through the measuring circuit of the indi-
cator of a value higher than 6 A may lead to damage of
the indicator.
For increased safety, it is recommended that one side
of the current transformer be earthed as shown in the
connection diagram.
Mounting
Содержание DMA-1 CT TrueRMS
Страница 2: ...2 1 LCD display 2 SET button Front description...
Страница 4: ...4 Wiring diagram...
Страница 8: ......